11
Measured values:
……………………………
Transmission behaviour object “bus voltage”
• do not send
• send cyclically
• send in case of change
• send in case of change and cyclically
Sending cycle
(only if sending “cyclically”)
5 sec • 10 sec • 30 sec • 1 min • … • 2 h
Change in %
(only if sending “in case of change”)
1 … 50
Transmission behaviour object “bus current”
• do not send
• send cyclically
• send in case of change
• send in case of change and cyclically
Sending cycle
(only if sending “cyclically”)
5 sec • 10 sec • 30 sec • 1 min • … • 2 h
Change in %
(only if sending “in case of change”)
1 … 100
Reset of the linie:
……………………………
What shall be used for the reset?
display and keyboard
Yes
object “permanent reset”
1 = reset | 0 = no reset
No • Yes
object “time reset”
1 = 30 seconds reset | 0 = no reset
No • Yes
Use object “reset status of the line”
No • Yes
Other:
……………………………
Maximum telegram quota
1 • 2 • 3 • 5 • 10 • 20 Telegrams per second
General sending delay after
power up and programming
5 sec • 10 sec • 30 sec • 1 min • … • 2 h