13
1 bit malfunction collection:
……………………………
Object “1 bit malfunction collection”
This object results in a
disjunction of the 1 bit malfunction objects
• do not send
• send in case of change
• send in case of change to 1
• send in case of change to 0
• send in case of change and cyclically
• send in case of change to 1 and cyclically
• send in case of change to 0 and cyclically
Sending cycle
(only if sending “cyclically”)
5 sec • 10 sec • 30 sec • 1 min • … • 2 h
8 bit status collection:
……………………………
Object “8 bit status collection”
• do not send
• send in case of change
• send in case of change and cyclically
Sending cycle
(only if sending “cyclically”)
5 sec • 10 sec • 30 sec • 1 min • … • 2 h
Bit 0 = reset status of the linie
Bit 1 = overload
Bit 2 = external overvoltage
Bit 3 = internal overvoltage
Bit 4 = short circuit
Bit 5 = overtemperature
Bit 6 = current threshold value exceeded
Bit 7 = system defect
Error log:
……………………………
Use error log
No • Yes
If the error log ist used:
Object “message part 1” sends signal:
Error no. (1 = latest error)
Object “message part 2” sends signal:
Error type
Object “message part 3” sends signal:
Date of error start
Object “message part 4” sends signal:
Time of error start