8

Display and operation at the device

Temperature sensor KNX T-B-UP

 • Software version 3.1 and higher

Status: 21/03/2016 • Technical changes and errors excepted.

Priority (points)

One point: Priority 1/priority control. It is not possible to adjust the temperature auto-
mation system manually. Neither the target temperature nor the operating modes can
be changed using the buttons on the unit.

Two points: Priority 2. The target temperature and operating mode can be changed us-
ing the buttons.

3.2. Change ambient temperature with the 

buttons

If the mode display is active, the target ambient temperature and the operating mode
can be changed manually using the buttons. The button functions can be blocked in
the ETS or be suppressed for Priority 1 operating modes. The individual operating
modes can also be locked for manual selection in the ETS.

Eco mode. 
Night target temperature will be 
used.

Building protection mode. 
Building protection target tem-
perature will be used. The sym-
bol will blink when the mode 
has been activated but the acti-
vation delay has not yet expired.

Heating mode. 
Heating will be provided.

Cooling mode 
Cooling will be provided.

Decrease target 
temperature (-)

briefly press 
left button

Ambient temperature in the current 
mode is decreased. 
The sep-size is defined in the ETS 
(0.1°C to 5°C).

Increase target 
temperature (+)

briefly press 
right button

Ambient temperature in the current 
mode is increased. 
The sep-size is defined in the ETS 
(0.1°C to 5°C).

Fig. 8

In "HVAC mode with 2x 8 bits" control mode, points are
shown under the symbol, to indicate the running priority
of the current mode.

Содержание 70358

Страница 1: ...360 70361 EN Elsner Elektronik GmbH Control and Automation Engineering Sohlengrund 16 D 75395 Ostelsheim Phone 49 0 70 33 30 945 0 info elsner elektronik de Germany Fax 49 0 70 33 30 945 20 www elsner...

Страница 2: ...ittings Functions Temperature measurements Composite value from own measured value and external value proportions are adjusted as a percentage Display 1 3 lines measured value or values received via b...

Страница 3: ...similar to RAL 9016 Traffic White Matt aluminium Charcoal matt Stainless steel Special colours on request Assembly Flush mounting Wall mounting in junction box 60 mm 42 mm depth Protection category I...

Страница 4: ...regulations are to be followed Ensure that all lines to be assembled are free of voltage and take precautions against accidental switching on Do not use the device if it is damaged Take the device or...

Страница 5: ...from ducts which lead from other rooms to the junction box in which the sensor is mounted Warming or cooling of the building structure on which the sensor is mounted e g due to sunlight heating or col...

Страница 6: ...ics You must not exceed a relative humidity of 95 Avoid condensation After the bus voltage has been applied the device will enter an initialisation phase last ing a few seconds During this phase no in...

Страница 7: ...y for adjusting the base target value The control position in the image reads Base target val ue reduced Fig 5 Mode display with scale display and number Shows the set target value change The control...

Страница 8: ...in the ETS or be suppressed for Priority 1 operating modes The individual operating modes can also be locked for manual selection in the ETS Eco mode Night target temperature will be used Building pr...

Страница 9: ...an 2 secs Changes between the operating modes Comfort Standby Eco and Building Protection if deblocked in the ETS Extend Comfort mode in Eco mode press both buttons at the same time longer than 2 secs...

Отзывы: