17
ETS Database Parameters
Intelligent Power Supply KNX PS640-IP 2U
• Version: 21.09.2021 • Technical changes and errors excepted.
Behaviour on alarm activation
• disabled
• send value 0
• send value 1
• set value to 0
• set value to 1
Leaving the working range.
Behaviour on alarm deactivation
• disabled
• send value 0
• send value 1
• set value to 0
• set value to 1
Entering the working range.
Output current
Output current [mA]
disable • enable
Enable/disable group associations, measurement and following settings.
Object type
• 2-byte (DPT7, integer)
• 2-byte (DPT9, float)
• 4-byte (DPT14)
Select datapoint type.
Sending difference
disabled • 5 mA • 10 mA..25 mA • 50 mA
Difference between actual and last sent value which triggers the sending.
Cyclic sending
disabled • 1 min • 2 min…5 min •
10 min • 15 min…30 min • 1 h • 2 h…8 h
Info telegram is sent regularly.
Threshold alarm
disable • enable
Enable/disable the alarm function.
Threshold
0…800 [mA]; 640
Select threshold value to execute the "Behaviour on alarm activation".
Hysteresis
0…640 [mA]; 1
Select hysteresis interval value to execute the "Behaviour on alarm deactivation".
Behaviour on alarm activation
• disabled
• send value 0
• send value 1
• set value to 0
• set value to 1
Select action on entering the threshold range.
Behaviour on alarm deactivation
• disabled
• send value 0
• send value 1
• set value to 0
• set value to 1
Select action on leaving the threshold (+hysteresis) range.