background image

15

Disposal

Weather Station Suntracer KNX-GPS light

 • Version: 30.09.2020 • Technical changes reserved. Errors reserved.

in danger (e.g. moving windows/awnings if a rain/wind alarm has 
been triggered while cleaning).

Always isolate the device from the mains for servicing and cleaning 

 

(e. g. switch off or remove the fuse).

The device must regularly be checked for dirt twice a year and cleaned if necessary. In
case of severe dirt, the sensor may not work properly anymore.

ATTENTION

The device can be damaged if water penetrates the housing.

Do not clean with high pressure cleaners or steam jets.

5.

Disposal

After use, the device must be disposed of or recycled in accordance with the legal reg-
ulations. Do not dispose of it with the household waste!

Содержание 3090

Страница 1: ...Suntracer KNX GPS light Weather Station Item numbers 3090 230V AC 3094 20 32 V DC EN Installation and Adjustment ...

Страница 2: ......

Страница 3: ...ing of the device at the bus 14 4 Maintenance 14 5 Disposal 15 6 Transmission protocol 16 6 1 List of all communication objects 16 7 Setting of parameters 24 7 1 General settings 24 7 2 Location 25 7 3 Position of the sun 26 7 3 1 Position of the sun in sector 1 2 3 4 5 26 7 4 Temperature 27 7 4 1 Temperature threshold value 1 2 3 4 27 7 5 Wind force 28 7 5 1 Wind force threshold value 1 2 3 29 7 ...

Страница 4: ...leshooting of the device must only be carried out by a competent electrician Safety advice Safety advice for working on electrical connections components etc DANGER indicates an immediately hazardous situation which will lead to death or severe injuries if it is not avoided WARNING indicates a potentially hazardous situation which may lead to death or severe injuries if it is not avoided CAUTION i...

Страница 5: ...shed electronically and thus noiseless and reliable even in case of hail snow and minus temperature Air swirls and up draught in the radius of the weather station are collected too Precipitation perception The surface of the sensor is heated so that only drops and flakes are recognised as precipitation but not fog or dew If it stops raining or snowing the sensor dries quickly and the precipitation...

Страница 6: ...or 20 32 V DC An appropriate power supply unit can be obtained from Elsner Elektronik Auxiliary current 230 V AC version max 20mA 20 32 V DC version max 81 mA at 24 V DC Residual ripple 10 Bus current max 8 mA Data output KNX bus terminal plug Group addresses max 254 Allocations max 255 Communication objects 222 Heating rain sensor approx 1 2 W Measurement range temperature 40 80 C Resolution temp...

Страница 7: ...ating instructions voids any and all warranty and guarantee claims After unpacking the device check it immediately for possible mechanical damage If it has been damaged in transport inform the supplier immediately The device may only be used as a fixed site installation that means only when assem bled and after conclusion of all installation and operational start up tasks and only in the surroundi...

Страница 8: ...d wind Temperature measurements can also be affected by external influences such as by warming or cooling of the building structure on which the sensor is mounted sun light heating or cold water pipes Temperature variations from such sources of inter ference must be corrected in the ETS in order to ensure the specified accuracy of the sensor temperature offset Magnetic fields transmitters and inte...

Страница 9: ... strips to the rear side of the housing Fasten the holder vertically to the wall or pole Fig 3 The weather station must be mounted in the horizontal transverse direction horizontally Horizontal Fig 4 For installation in the northern hemisphere the weather station must be aligned to face south For installation in the southern hemisphere the weather station must be aligned to face north North South ...

Страница 10: ... optional accessories for flexible installation of the weather station on a wall pole or beam Example of the use of a mounting arm Due to flexible ball joints the sensor can be brought into ideal position Fig 8 Example use of the hinge arm mounting With the hinge arm mounting the weather sta tion projects from beneath the roof overhang Sun wind and precipitation can act upon the sensors without hi...

Страница 11: ... light Version 30 09 2020 Technical changes reserved Errors reserved 2 1 4 Rear view and drill sketch Oblong hole 7 5 x 5 mm Fig 10 a b Drill sketch Dimensions of the rear side of the housing with holder dimensions in mm Divergences are possible for technical reasons ...

Страница 12: ...nnection in case of 230 V AC version cable with plug in case of 20 32 V DC version Push the power supply and bus connection cable through the rubber seal on the bot tom of the weather station and connect voltage and bus to the provided clamps For 20 32 V DC devices the connection cable must be plugged in between the cover and circuit board Fig 11 1 Screw on cover 230V device 2 Cover 3 Cover snaps ...

Страница 13: ...th fine wires Terminal configuration independ ent from polarity or 2 KNX clamp 3 Slot for cable connection to the rain sensor in the housing cover 4 Programming pushbutton for the teach in of the device 5 Programming LED 6 Control LED GPS reception Depending on the parameter setting in the ETS the LED blinks 1x per second to show GPS reception or it stays always off After the auxiliary supply volt...

Страница 14: ...Fig 14 1 Slot for cable connection to the rain sensor in the housing cover 2 Tension clamp for power supply 230 V AC For massive conductors of up to 1 5 mm or conductors with fine wires 3 KNX clamp 4 Control LED GPS reception Depending on the parameter setting in the ETS the LED blinks 1x per second to show GPS reception or it stays always off After the auxiliary supply voltage has been connected ...

Страница 15: ...r station can be simply pulled upwards out of the mount against the resistance of the fastening Fig 15 Make sure the cover and bottom part are properly snapped together This picture is looking at the closed sensor from under neath Fastening Fig 16 With the 230V model screw the cover on to the underpart to prevent unauthorised or ac cidental opening Fig 17 Push the housing from above into the fas t...

Страница 16: ... 60 seconds after the supply voltage has been connected After the auxiliary voltage has been applied the device will enter an initialisation phase lasting a few seconds During this phase no information can be received or sent via the bus 3 Addressing of the device at the bus The device is supplied with the bus address 15 15 255 You can program another ad dress into the ETS by overwriting the 15 15...

Страница 17: ... cleaning e g switch off or remove the fuse The device must regularly be checked for dirt twice a year and cleaned if necessary In case of severe dirt the sensor may not work properly anymore ATTENTION The device can be damaged if water penetrates the housing Do not clean with high pressure cleaners or steam jets 5 Disposal After use the device must be disposed of or recycled in accordance with th...

Страница 18: ... Name Function EIS type Flags 0 date 4 C R W T 1 time 3 C R W T 2 Date and time requirement 1 C R W 3 Switching output dawn 1 C R T 4 Switching output rain 1 C R T 5 Logic input 1 1 C R W 6 Logic input 2 1 C R W 7 Logic input 3 1 C R W 8 Logic input 4 1 C R W 9 Logic input 5 1 C R W 10 Logic input 6 1 C R W 11 Logic input 7 1 C R W 12 Logic input 8 1 C R W 13 Sun position azimuth 5 C R T 14 Sun po...

Страница 19: ...get value 5 C R W 32 Temperature threshold value 4 Actual value 5 C R T 33 Switching output temperature threshold value 1 1 C R T 34 Switching output temperature threshold value 2 1 C R T 35 Switching output temperature threshold value 3 1 C R T 36 Switching output temperature threshold value 4 1 C R T 37 Measured value of wind force 5 C R T 38 Requirement max wind force Requirement 1 C R W 39 Hig...

Страница 20: ...e period 1 sequence 1 Calendar time switch 3 C R W 61 Switch off time period 1 sequence 1 Calendar time switch 3 C R W 62 Switching output calendar time switch Period 1 sequence 1 1 C R T 63 Activation time period 1 sequence 2 Calendar time switch 3 C R W 64 Switch off time period 1 sequence 2 Calendar time switch 3 C R W 65 Switching output calendar time switch Period 1 sequence 2 1 C R T 66 Acti...

Страница 21: ...1 C R T 87 Switching output week time switch Monday 2 1 C R T 88 Switching output week time switch Monday 3 1 C R T 89 Switching output week time switch Monday 4 1 C R T 90 Activation time Tuesday 1 Week time switch 3 C R W 91 Switch off time Tuesday 1 Week time switch 3 C R W 92 Activation time Tuesday 2 Week time switch 3 C R W 93 Switch off time Tuesday 2 Week time switch 3 C R W 94 Activation ...

Страница 22: ...itch Thursday 2 1 C R T 124 Switching output week time switch Thursday 3 1 C R T 125 Switching output week time switch Thursday 4 1 C R T 126 Activation time Friday 1 Week time switch 3 C R W 127 Switch off time Friday 1 Week time switch 3 C R W 128 Activation time Friday 2 Week time switch 3 C R W 129 Switch off time Friday 2 Week time switch 3 C R W 130 Activation time Friday 3 Week time switch ...

Страница 23: ...itch Sunday 2 1 C R T 160 Switching output week time switch Sunday 3 1 C R T 161 Switching output week time switch Sunday 4 1 C R T 162 AND logic 1 Switching output 1 C R T 163 AND logic 1 8 Bit output A 6 C R T 164 AND logic 1 8 Bit output B 6 C R T 165 AND logic 2 Switching output 1 C R T 166 AND logic 2 8 Bit output A 6 C R T 167 AND logic 2 8 Bit output B 6 C R T 168 AND logic 3 Switching outp...

Страница 24: ... 8 Bit output A 6 C R T 200 OR logic 5 8 Bit output B 6 C R T 201 OR logic 6 Switching output 1 C R T 202 OR logic 6 8 Bit output A 6 C R T 203 OR logic 6 8 Bit output B 6 C R T 204 OR logic 7 Switching output 1 C R T 205 OR logic 7 8 Bit output A 6 C R T 206 OR logic 7 8 Bit output B 6 C R T 207 OR logic 8 Switching output 1 C R T 208 OR logic 8 8 Bit output A 6 C R T 209 OR logic 8 8 Bit output ...

Страница 25: ...tracer KNX GPS light Version 30 09 2020 Technical changes reserved Errors reserved 219 Temperature sensor failure Output 1 C R T 220 Wind sensor failure Output 1 C R T 221 Date and time synchronised Output 1 C R T No Name Function EIS type Flags ...

Страница 26: ...ith these data until it receives a valid GPS signal for the first time If date and time are set by a communication object There must not be a change in date between the sending of date and the sending of time both must be sent to the weather station on the same day Measured values send all cyclically 5 sec 2 h Date and time are set by Radio signal and not sent Radio signal and sent cyclically Radi...

Страница 27: ...g output night The output reacts with a delay of approx 1 minute night is recognised when light is below 10 lux do not send send in case of change send inverted in case of change send in case of change and cyclically send inverted in case of change and cyclically as in case of all switching outputs Communication object Switching output rain After approx 8 minutes without rain the output is reset a...

Страница 28: ...azimuth 180 360 elevation 0 90 If the position of the sun is defined by azimuth and elevation All data in degree Northern latitude in degrees 90 90 Northern latitude in minutes 59 59 Azimuth and elevation do not send send cyclically send in case of change send in case of change and cyclically From a change of 1 15 degrees 3 degrees Sector 1 2 3 4 5 not active active Definition of the position of t...

Страница 29: ...un azimuth Marked area Azimuth from 135 up to 270 Height of sun elevation Marked area Elevation from 45 up to 90 Measured value not send send cyclically send in case of change send in case of change and cyclically From a temperature change of 0 5 C 1 C 2 C 3 C 4 C 5 C Temperature offset in 0 1 C 50 50 0 Send and reset of the min and max temperature value on request do not release release Threshold...

Страница 30: ...resholds set at last by communication objects are saved in EEPROM in order to maintain them in case of voltage breakdown and to provide them as soon as there is voltage supply again 7 5 Wind force Threshold value is set by Communication object Threshold value in 0 1 C valid until 1st communication 300 800 200 Threshold value is set by Com object with saving of the last value Hysteresis of the thre...

Страница 31: ...eshold value is set by Parameter Communication object Com object with saving of the last value Threshold value in 0 1 m s 0 350 40 Hysteresis of the threshold value in 0 1 m s 0 250 20 Start threshold value in 0 1 m s 0 350 40 Hysteresis of the threshold value in 0 1 m s 0 250 20 Measured value not send send cyclically send in case of change send in case of change and cyclically From change of onl...

Страница 32: ... Threshold value 1 2 3 not active active Theshold value is set by Parameter Communication object Com object with saving of the last value Threshold value in lx 1 1000 200 Hysteresis of the threshold value in lx 0 1000 50 Start threshold value in lx 1 1000 200 Hysteresis of the threshold value in lx 0 1000 50 Period 1 2 3 not active active From Month January December Day 1 29 1 30 1 31 depending on...

Страница 33: ...d can be used as communiction object Week time switch 1 for own logic links Switch off time hours 0 23 Switch off time minutes 0 59 Communication object switching output period 1 2 3 sequence 1 2 not send send in case of change send inverted in case of change send in case of change and cyclically send inverted in case of change and cycli cally Monday Sunday not active active Setting of switching t...

Страница 34: ...bject value 1 0 if logic 0 object value 1 0 Communication object AND Logic 1 sends in case of the change of logic in case of the change of logic to 1 in case of the change of logic to 0 in case of the change of logic and cyclically in case of the change of logic to 1 and cyclically in case of the change of logic to 0 and cyclically send cyclically every only if sending cyclically 5 sec 2 h Logic o...

Страница 35: ...ration Logic 0 released logic 1 blocked The Communication objects logic inputs must be released in the General Settings for this porpose and the communication object logic 1 must be linked with the button via group addresses Wind threshold value 1 inverted Activates the automatic function after the end of a wind alarm shading is extended if all other conditions are complied with 7 10 2 Linkage inp...

Страница 36: ... time switch 2 period Nr 2 Calendar time switch 2 period Nr 2 inverted Calendar time switch 3 period Nr 1 Calendar time switch 3 period Nr 1 inverted Calendar time switch 3 period Nr 2 Calendar time switch 3 period Nr 2 inverted Communication object logic input 1 Communication object logic input 1 inverted Communication object logic input 2 Communication object logic input 2 inverted Communication...

Страница 37: ...old value 2 Wind threshold value 2 inverted Wind threshold value 3 Wind threshold value 3 inverted Week time switch Monday 1 Week time switch Monday 1 inverted Week time switch Monday 2 Week time switch Monday 2 inverted Week time switch Monday 3 Week time switch Monday 3 inverted Week time switch Monday 4 Week time switch Monday 4 inverted Week time switch Tuesday 1 Week time switch Tuesday 1 inv...

Страница 38: ...k time switch Friday 4 inverted Week time switch Saturday 1 Week time switch Saturday 1 inverted Week time switch Saturday 2 Week time switch Saturday 2 inverted Week time switch Saturday 3 Week time switch Saturday 3 inverted Week time switch Saturday 4 Week time switch Saturday 4 inverted Week time switch Sunday 1 Week time switch Sunday 1 inverted Week time switch Sunday 2 Week time switch Sund...

Страница 39: ...provided with the following inputs AND logic output 1 AND logic output 1 inverted AND logic output 2 AND logic output 2 inverted AND logic output 3 AND logic output 3 inverted AND logic output 4 AND logic output 4 inverted AND logic output 5 AND logic output 5 inverted AND logic output 6 AND logic output 6 inverted AND logic output 7 AND logic output 7 inverted AND logic output 8 AND logic output ...

Страница 40: ...mbH Control and Automation Engineering Sohlengrund 16 75395 Ostelsheim Phone 49 0 70 33 30 945 0 info elsner elektronik de Germany Fax 49 0 70 33 30 945 20 www elsner elektronik de Technical support 49 0 70 33 30 945 250 ...