gi_interval_sec
integer
Time
frame
between
General
Interrogation requests in seconds
Yes
poll_interval_ms
integer
Polling interval in milliseconds.
Time
frame between two telegrams from
master. Default 100
event_history_size
integer
Maximum count of events in event log.
Default 0
poll_timeout_ms
integer
Timeout of waiting for incoming request
serial_delay
integer
Communication device’s serial delay in
milliseconds. Time frame in which master
station is not TX’ing after last RX byte.
Default: 50
poll_retry_count
integer
Number of retries of failed requests
before announcing that device is in Error
state
Table 21: IEC 608705103 parameters for
Signals
tab
Parameter
Type
Description
Mandatory
signal_name
string
Userfriendly name of a signal
device_alias
string
Device alias from a Devices tab
Yes
signal_alias
string
Unique signal name to be used
Yes
source_device_alias
string
device_alias of a source device
For
commands
source_signal_alias
string
signal_alias of a source signal
For
commands
enable
boolean
Enabling/disabling of a signal
Yes
log_size
integer
Space for signal in event log
gi
boolean
Including/excluding
signal
from
General
Interrogation. Default 0 (exclude)
common_address
integer
Address of a device
function
integer
Function number
Yes
info_address
integer
Information address
Yes
info_number
integer
Information number
Yes
data_type
integer
ASDU type identificator
Yes
fleeting
boolean
Mark signal as fleeting type. Fleeting signals
have go to DPI::OFF after defined time
normalise_time_ms
integer
Time in milliseconds between station receiving
DPI::ON
and
automatically
switching
to
DPI::OFF. Default 100.
If fleeting is
used
IEC 608705103 has an additional signal which can be configured to show communication status.
It is used to indicate if the slave device has disconnected from master (WCC Lite). To configure such
signal, two columns should be filled with particular values. To a newly created additional signal one
should make
job_todo
equal to
device_status
and
tag_job_todo
equal to
communication_status
.
104
Содержание WCC Lite
Страница 1: ...ELSETA WCC Lite User manual Elseta 2020 04 07 Doc version 1 4 0 HW version 1 2 FW version 1 4 0...
Страница 62: ...8 5 9 Reboot This reboots the operating system of the device 62...
Страница 78: ...General DHCP settings Resolve and hosts files settings TFTP server settings 78...
Страница 155: ...Figure 37 Screen showing existing user groups Figure 38 Screen for user group editing 154...