![Elseta IOMOD HT Скачать руководство пользователя страница 8](http://html1.mh-extra.com/html/elseta/iomod-ht/iomod-ht_user-manual_2396489008.webp)
System
1.
Dimensions
26 (H) x 71 (W) x 71 (L), mm
2.
Case
ABS, white
3.
Working environment
Indoors
4.
Working temperature
-20 ÷ +70°C
5.
Recommended operating conditions
5 – 60°C and 20 – 80%RH;
6.
Configuration
USB or Modbus
7.
Firmware upgrade
USB – mass storage device
Electrical Characteristics
Basic
Advanced
8.
Termination Resistor
Selectable 120Ω
Selectable 120Ω
9.
Power supply
12-24VDC, 8mA (nominal); 5-
33VDC (full range)
24VDC, 25mA (nominal); 18-
27VDC (full range)
10.
Relays
-
2 (Normally Open);
Relay specifications
Basic
Advanced
12.
Resistive load (cosφ=1)
-
5 A at 250 VAC, 5 A at 30 VDC
13.
Inductive load (cosφ=0.4,
L/R=7ms)
-
2 A at 250 VAC, 2 A at 30 VDC
14.
Max. switching power
-
1,250 VA, 150 W