It is recommended to close terminal window when entered firmware upgrade mode.
Device reconnects as mass storage device:
Fig. 6.5
User then must delete existing file “firmware.bin”, and simply upload new firmware file by drag and drop.
Fig. 6.6
Reconnect device, and check firmware version.
e. Testing With “THE VINCI” software
To test IOMOD HT with default settings, user connects device through RS485 to Modbus master. Example will show
“The Vinci Expert” as serial interface converter and adapter to PC with “The Vinci” software. Default settings for
Modbus – 9600 baudrate; 8 data, no parity, 1 stop bit. When opening “The Vinci” software, choose Modbus serial –
Master mode. In settings tab, choose station number (default – 1); configure tags (as described in section 2. Device
working information); Press start and go to “Statistic” tab:
Fig. 6.8