Elseta IOMOD HT Скачать руководство пользователя страница 7

Supported MODBUS functions

01 (0x01) Read Coils Status 

Reads status of relays (Off or On). IOMOD HT has 2 relays on addresses 6 and 7 (Only for IOMOD 

HT Advanced).

03 (0x03) Read Holding Registers

Reads current configuration of relays. Address 2 – Active Mode for 1st relay ( 0 – disabled, 1 - humidity or 2 -

temperature); Address 3 – Lower Active value (minimal value for relays to turn on) for 1st relay; Address 4 – Upper

Active value (maximum value for relays to keep turned on. If parameter reaches threshold bigger than this value, relay

is turned off) for 1st relay. Address 5 – Active Mode for 2nd relay (humidity or temperature); Address 6 – Lower Active

value (minimal value for relays to turn on) for 2nd relay; Address 7 – Upper Active value (maximum value for relays to

keep turned on. If parameter reaches threshold bigger than this value, relay is turned off) for 2nd relay.

04 (0x04) Read Input Registers 

Reads current Humidity and Temperature status. Address 0 – Humidity; Value is multiplied by 10 to show one decimal

place. For example: 23.3 °C will be shown as 233; 50.0 % will be shown as 500 in the Registers.

05 (0x05) Write Single Coil 

(Only for IOMOD HT Advanced). Sets single relay On or Off. 1 Relay address – 6th register; 2 relay – 7th register. 

06 (0x06) Preset Single Register

Sets single configuration (Only for IOMOD HT Advanced). Address 2 – Active Mode for 1 relay: 0- disabled; 1 - humidity

or 2 - temperature; Address 3 – Lower Active value (minimal value for relays to turn on) for 1 relay; Address 4 – Upper

Active value (maximum value for relays to keep turned on. If parameter reaches threshold bigger than this value, relay

is turned off) for 1 relay. Integer; Address 5 – Active Mode for 2 relay: 0- disabled; 1 - humidity or 2 - temperature;

Address 6 – Lower Active value (minimal value for relays to turn on) for 2 relay; Address 7 – Upper Active value

(maximum value for relays to keep turned on. If parameter reaches threshold bigger than this value, relay is turned

off) for 2 relay. 

Содержание IOMOD HT

Страница 1: ...nformity Safety Requirements Equipment s Manual Uses Symbols Introduction Features Device working information Supported MODBUS functions Technical Information Device connection Configuration over USB...

Страница 2: ...duct and the user manual of the right to ownership of the copyright belongs to Elseta These documents and the product properties can not be changed without company Elseta knowledge and written consent...

Страница 3: ...EN 50082 1 immunity test 1 IEC 801 3 Radio frequency electromagnetic field 2 IEC 801 2 Electrostatic discharge 3 IEC 801 4 Quick periodic electrostatic discharges Additional information The device com...

Страница 4: ...e equipment These notes are marked with a warning triangle symbol and the various degrees of risk of falling within signs All work related to electronic systems design installation commissioning adjus...

Страница 5: ...ace Need to understand the equipment components Electrical equipment Have the knowledge and skills to identify a component beneath the voltage To maintain the equipment necessary to always turn off th...

Страница 6: ...h up to 1500 meters and connect up to 30 devices on one line Default Modbus settings are 9600 baudrate 8N1 Slave address 1 To read temperature and humidity user can use device with default settings wi...

Страница 7: ...put Registers Reads current Humidity and Temperature status Address 0 Humidity Value is multiplied by 10 to show one decimal place For example 23 3 C will be shown as 233 50 0 will be shown as 500 in...

Страница 8: ...ge device Electrical Characteristics Basic Advanced 8 Termination Resistor Selectable 120 Selectable 120 9 Power supply 12 24VDC 8mA nominal 5 33VDC full range 24VDC 25mA nominal 18 27VDC full range 1...

Страница 9: ...cable See typical connection diagram on Fig 5 1 Fig 5 1 IOMOD 8DI8DO has 1 8 Unit load receiver which allows to have up to 256 units on line compared to standard 32 units To reduce reflections keep th...

Страница 10: ...x86 driver for 32bit machine or x64 for 64bit machine If not sure select root folder folder in which x64 and x86 lays inside Fig 6 3 b IOMOD HT configuration with PuTTY terminal Configuration of IOMO...

Страница 11: ...a Stop and Parity bits Chooses Stop and parity bits to use default 8N1 4 4 RS485 Terminating Resistor RS485 120 Ohms Terminating Resistor 0 1 off on default 0 5 Relay 1 settings Active mode and active...

Страница 12: ...I software To test IOMOD HT with default settings user connects device through RS485 to Modbus master Example will show The Vinci Expert as serial interface converter and adapter to PC with The Vinci...

Страница 13: ......

Страница 14: ...IOmod HT Humidity and Temperature Device picture...

Отзывы: