Technical Manual Milk Cooling Controller TARN 1600

 Failure Display / Failure Behaviour

Display shows "SEH" and flashes (Sen-
sor Error High), Beeper sounds:

Temperature sensor input is open, wrong
sensor, sensor damaged or cable broken.

Display shows "SEL" and flashes (Sen-
sor Error Low), Beeper sounds:

Temperature sensor cable has short
circuit, wrong sensor or short circuit of
sensor itself.

Display shows "HA" and flashes (High
Alarm), Beeper sounds:

Upper alarm threshold (P12) increased.

Display shows "LA" and flashes (Low
Alarm), Beeper sounds:

Lower alarm threshold (P13) decreased.

 Emergency Mode

If the control sensor fails, the controller starts an emergency mode.

Then the refrigeration relay and the stirrer switch ON in a percentage
rate of a total period of 30 minutes, preset by

 P04.

E.g.: selecting 40% means 12 minutes on, 18 minutes off.

  Technical Data

Supply Voltage ................... TARN 1600 ...........

230 AC / 50 Hz

TARN 21600 .........

115 AC / 60 Hz

Power Consumption ................................................ max. 4,4 VA
Relay  Contact  Rating ......... K1, 10A res., 80A/20 msec, 250V AC

K2, K3 ................................ 5A res.

Operating-/Storage Temperature ........ -10...+50°C / -30...+70°C
Air Humidity ................................max. 80% r.F., not condensing
Temperature Sensors ........ TF 101, TF 201 or TF 501 (Pt1000)
Display .................................. LED, red, character height 13mm

Resolution .............................................................. 0,1°C / 0,2°F
Accuracy .................................................................... typ. +/- 1K
Control-/Display Range

with TF 101 ........................................... -5...+30°C / 23...86°F
with TF 201 .................................... -55...+105°C / -67...221°F
with TF 501 ................................ -110...+120°C / -166...248°F

Data Storage ................................................................ unlimited
Relay Indicator ................................................... LED 3 mm, red
Electrical Connection .......... pluggable screw terminals 2,5mm²
Protection ........................................................... IP 54 from front

Param. Disp. Code Description

Range

Default    Your value

No.

onl.

 P01

X

--

Actual temperature

-30..100°C

 P02

--

Setpoint

0..30,0°C

4

 P03

88

Hysteresis

0,3..10K

1

 P04

88

Emergency mode , x% ON-time of 30 minutes

0..100%

0

 P05

88

Stirrer interval

1..255min

60

 P06

88

Stirrer runtime

0..255sec

10

 P07

88

Temperature correction

-10,0..10,0K

0

 P08

88

Sensor type

1=TF101, 2=PT1000, 3=TF201

1

 P09

88

Display Resolution

1=0,1K    2=1K

2

 P10

88

Display Mode

1=°C 2=°F

1

 P11

88

Alarm delay

0 .. 255min

60

 P12

88

Upper Temperature Alarm Threshold

0..50,0°C

50

 P13

88

Lower Temperature Alarm Threshold

0..P11

0

 P14

88

Stirrer Delay after Power-up

0..30min

0

 P15

--

Code

0..100

- -

ON

30 minutes

Emergency Mode

in %

Cooling OFF

Cooling ON

OFF