background image

Page 6

Technical Manual Temperature-, Humidity-, Pressure-Controller TAR x260

 Functional Description

Sensor connection

The controller operates either with temperature
sensors of the types TF201 (PTCs) and TF 501
(PT1000) or with a 4...20 mA signal. The input
will be selected by parameter P26.
The selection of inputs and sensors depends
on your requests:

Temperature Controller:
For temperatures < 80°C use sensors
TF 201 or TF501.
For temperatures > 80 up to 300°C you
must select an appropriate Pt1000 sensor.
Pressure controller:
4...20mA from pressure transmitter
Humidity controller:
4...20mA from humidity transmitter

Operation modes

The controller can be configured for different
operating modes (with parameter P14):

P14 = 1: 2 control sensors
Sensor 1 effects to setpoint 1, sensor 2
effects to setpoint 2. So you realize 2
independent single stage temperature
controllers in one unit. In this mode the
4...20mA input is de-activated.

P14 = 2: 1 control sensor or transmitter

(dual stage control)

Sensor Input 1 or the 4...20 mA Signal
Input effects to both setpoints (P03 / P04),
Sensor Input 2 is de-activated. P03 is an
absolute value, P04 can be also relative
(adjustable by P05).

P05 = 1: Setpoint 2 (P04) is an absolute

value (used for dual stage control
with individual setpoints)

P05 = 2: Setpoint 2 (P04) is a relative value

(used for dual stage control with
neutral zone, that means that P04
will be shifted the same amount if
P03 is shifted)

P14=3:

1 control 1 sensor for
setpoint shift

Sensor 1 effects to setpoint 1 (P03), sensor
2 may shift setpoint 1. The 4...20 mA input is
de-activated. With this, you realize e.g. an
outdoor temperature guided control.
P19 is the limit from which a rise or lowering
(shift) becomes possible, P20 is the range
of the shift, P21 the amount of the shift.

Example:

- Control Setpoint 1

P03 = 10°C

- Limit value

P19 = 20°C,

that means increasing starts with 20° at
sensor input 2, below that value there's no
shift.

- range of shift

P20 = 5K,

that means shift range is 25K in total, above
25°C at sensor 2 maximum setpoint shift.

- Size of shift

P21 = 8K,

from 25°C the control setpoint is P03 + 8K, in
this example = 18°C.

P18 shows the current shift amount. This
value is a sum of the day/hight shift and
the setpoint shift.

P14 = 4: 2 control sensors, cyclic defrost
function is active.
Sensor 1 effects to setpoint 1, sensor 2
effects to setpoint 2. With this configuration
you realize two independent single stage
controllers in one unit like above, but
parameters 20/21 get a different function.
Cooling via setpoint 1 (i.e. the output
effected by setpoint 1) is disabled in specific
time intervals to enable air flow defrost.
The 4...20 mA input is deactivated.

Actual value display / status display

With temperature sensors:
Temperatures can be displayed in °C or °F
selected by parameter P26 (= sensor type
switch). The resolution is 0.1°C (or 0,2°F).
While operating with temperature sensors,
P01 shows the actual value of sensor 1.
You also come back to this display at P01,
if another parameter is selected and no key
is pressed for about 4 minutes.
In operation modes 1, 3, 4 and 5 P02 shows
the actual temperature value of sensor 2.

With 4...20 mA transmitters:
In op-modes (P14) 2 and 5 the “4...20 mA”-
input is activated and can be read at P01.
The standard current signal can be delivered
by an 4...20 mA source or appropriate
transmitter.

Adapting of  humidity and pressure transmitters,
display correction

A transmitter delivers the measured value as a
4...20 mA signal. With parameter P30/P29 the
measuring scale will be preset.

Example 1: Humidity  transmitter,

Range 0...100% r.H.
P29 = 100, P30 =0

Example 2: Pressure  transmitter,

Range –0,5 ... +9.0 bar
P29 = 9,0 and P30 = -0,5

With P27 the display of actual value P01 can be
corrected, with  P28 a correction of the value
displayed by P02 is possible.

setpoint

amount of shift

P21 (8°)

shifted
setpoint
(18°)

setpoint
P03 (10°)

setpoint course

limit

P19 (20°)range of shift

P20 (5K)

range 

limit

(25°C)

P02

Switching hysteresis

For the setpoints P03 / P04 you can fix a
switching hysteresis with parameters P12 and
P13. The position of the hysteresis (above/
below the setpoint) depends on the selected
relay switching mode (P07 resp. P08).

Setpoint limits

To prevent the setpoints being set to an invalid
value (e.g. not below 0°C), the range of P03 /
P04 can be restricted by parameters P10 and
P11.

Day / night shift - 2

nd

 Setpoint

E. g. to save energy it is possible to work with
other setpoints at any time. By parameter P06
an offset value can be set on which all setpoints
will be shifted if Digital Input OK 1 is activated.

Temperature- resp. Limit Value Alarm

If the value measured with sensor 1 or the
delivered 4...20 mA signal leaves the range
preset by parameters P32 and P33, then an
alarm relay and a buzzer will be activated after
a delay timer (P31) is run down. P22 shows the
remaining time of the alarm delay timer.
P33 (lower limit) is an absolute value and P32
is always a relative value coupled to the current
setpoint (P03 + eventually shift).

Relay switching characteristic

The switching characteristic of relays K1 and
K2 are defined by parameters P07 and P08.
The following options can be selected:

1= Refrigeration (Standard)

Used for standard applications (e.g.
temperatures above 0°C).
The load would be switched by the NO-
contact.

alarm after P31 is run down

alarm after P31 is run down

Lower limit
P 3 3
(absolute)

Upper limit
P 3 2
(relative)

temperatur flow

cold

stage ON

stage OFF

w a r m

setpoint

hysteresis

Содержание TAR 1260

Страница 1: ... Double Single Setpoint Dual Setpoint Proportional PI Controller Step Controller Setpoint shift by 2nd sensor Cold Storage Control with Cyclic Defrost l Output 0 10VDC delivers control deviation or an actual value image Please note Safety Instructions TAR 1260 TAR 3260 TAR 5260 TAR 19260 l Limit value alarm Alarm relay l Inputs for PTC Pt1000 and 4 20 mA for any 2 wire transmitters l 2 setpoint by...

Страница 2: ...e in equipment or systems that are intended to be used under such circumstances that may affect human life Forapplicationsrequiringextremelyhighreliability please contact the manufacturer first Electrical installation and putting into service must be done from authorized personnel Please note the local safety instructions Before installation Check the limits of the controller and your application ...

Страница 3: ...N in op mode 4 Defrost runs 3 All TAR versions are marked in the same way Unlock Keys Topreventun authorizedpersonsfromeditingparametervalues there is a locking function which allows only the most important parameters to be changed at any time All other parameters must be unlocked beforehand This means that at parameter P43 a certain value is to be set see parameter listing Press key P parameter n...

Страница 4: ...h low sensor error 3 activated if P02 is too high low sensor error 4 activated P02 is too high low sensor error P10 x x x x 88 Highest with P03 resp P04adjustable setpoint 50 C 100 300 C P11 x x x x 88 Lowest with P03 resp P04 adjustable setpoint 50 C 100 P10 C P12 x x x x 88 Hysteresis of Setpoint 1 relay 1 2 0 2 20 P13 x x x x 88 Hysteresis of Setpoint 2 relay 2 2 0 2 20 P14 x x x x 70 Operation...

Страница 5: ... 0 P31 x x x x 88 Alarm delay 5 1 99 min P32 x x x x 88 Upper alarm limit Relative related to the active 0 300 potentially shifted setpoint 1 P33 x x x x 88 Lower alarm limit Absolute value 100 100 300 P34 x x x x 88 Digital Input 1 OK 1 0 0 input disabled 1 Night setpoint 2 External Alarm 3 Unit OFF P35 x x x x 88 Delay time for Digital Input OK 1 2 0 99 min P36 x x x x 88 Analog output 10V DC at...

Страница 6: ...air flow defrost The 4 20 mA input is deactivated Actual value display status display With temperature sensors Temperatures can be displayed in C or F selected by parameter P26 sensor type switch The resolution is 0 1 C or 0 2 F While operating with temperature sensors P01 shows the actual value of sensor 1 You also come back to this display at P01 if another parameter is selected and no key is pr...

Страница 7: ...y is activated active or de activated passive if an alarm occurs Minimium idle time If a relay has been switched OFF it can be activated first after timer P15 is run down If the switching characteristic is set to cycling this function is de activated Parameters P23 and P24 show the remaining time until the relays will switch ON again Example for a cycling heater Switching char P07 4 Setpoint 1 P03...

Страница 8: ...trollers can be networked via their built inRS 485 interface Thisnetworkcanbecontrolled by a host unit Normally this host is a PC with a qualified software which allows remote control of units and recording of all parameters Because all units are connected parallel on the data cable every unit has its own network address P42 to ensure a specific communication The communication speed is fixed by P4...

Страница 9: ...t setpoint P03 shift Example P36 10 C P37 10 C P39 3 P03 15 C no current shift Output 0V at P03 P36 25 C voltages 10V at P03 P37 5 C Example Actual Value Image You have a remote display or similar which shows 50 C at 0V input voltage and 50 C at 10V DC P37 50 P36 10 P39 must be 1 Example Proportional Controller You want to control any device with 0 10V input depending on pressure You want it to be...

Страница 10: ... 2 Basic settings P14 2 P07 1 P08 1 P26 1 4 2 stage pressure controller Basic settings P14 2 P07 1 P08 1 P26 5 P29 P30 depends on transmitter Moisturize de humidifying basic settings P14 2 P07 1 P08 3 P26 5 P29 100 P30 0 Temp Feuchte Druckregler Temp Hum Press Control 70 2 76 5 9 Alarm K4 F 2 11 12 24V AC DC F 1 12 13 10 14 15 4 20mA 7 8 6 16 17 18 19 OK1 12 47 56 2 2 4 1 2 3 20 21 DO NDO 22 23 24...

Страница 11: ...V D C 4 20 mA IN 33 32 sensor 1 sensor 2 37 35 36 38 DG x xx 29 10 relay K2 AC 3 2 1 5 4 mains TAR 3260 7 6 8 9 relay K1 24 22 21 20 23 26 25 D O DC 27 28 0 10V DC RS 485 sensor 1 sensor 2 4 20 mA IN 15 11 12 14 13 17 16 N L 19 18 relay K4 alarm OK 1 34 N D O 30 31 33 32 36 35 38 37 29 10 relay K2 DC 5 2 1 3 4 TAR 3260 mains 7 6 8 9 relay K1 AC 24 21 20 22 23 26 25 27 28 D O 0 10V DC sensor 1 sens...

Страница 12: ...5 28 29 30 20V DC f Geber N PE L 1 2 5 6 4 3 8 7 9 10 11 P E 4 20 mA 0 10V RS 485 N D O D O mains relay K1 relay K2 16 22 17 18 21 20 19 23 24 26 25 5 1 2 3 4 0 10V 15 32VDC 4 20mA 13 12 15 14 N OK 1 OK 2 relay K4 alarm 28 29 30 N PE 14 29 L 1 13 2 5 6 4 3 8 7 9 10 12 11 P E 4 20 mA 0 10V RS 485 N D O D O N OK 1 20V DC f transmitter relay K1 relay K2 relay K4 alarm mains 16 22 17 18 21 20 19 23 24...

Страница 13: ...2 sensor 1 16 sensor 2 18 32 RS 485 30 26 28 24 22 20 DO NDO F2 13 19 18 4 20mA 20 24 25 relay 4 alarm z 14 OK2 10 12 8 15 6 2 4 OK1 N 1 PE 14 terminal 0 10V DC F1 4 2 22 23 20VDC 17 26 28 32 30 21 22 24 16 8 4 5 10 14 16 20 18 12 11 12 7 6 6 3 relay 1 relay 2 2 d N L terminal 4 PE 22 20 19 26 28 32 RS 485 30 DO NDO 24 25 24 F2 18 4 20mA Vers Signal 8 15 10 14 16 20 18 13 OK2 12 6 OK1 14 relay 4 a...

Страница 14: ...point relay K2 P05 1 setpoints are absolute values P06 0 no setpoint shift P07 1 relay K1 will be activated by rising humidity de hum P08 3 relay K2 will be activated by falling humidity hum P10 100 P11 0 P12 2 hysteresis for de humidifying relay 2 P13 2 hysteresis for moistening relay 2 P29 100 display value with 20 mA current input P30 0 display value with 4 mA current input P34 0 Digital input ...

Отзывы: