ELREHA TAR 1260 Скачать руководство пользователя страница 14

Page 14

Technical Manual Temperature-, Humidity-, Pressure-Controller TAR x260

 Start-up example: Dual Channel Temperature Controller

Requirements:

Cooling ON at +10°C/ OFF at +9°C, Heating ON at +1°C/OFF at +2°C, the
offset Heating/Cooling remains always equal, Overtemperture Alarm at
+15°C, Undertemperature Alarm at 0°C, both after 30 minutes.
The alarm relay works active-low. At a certain time the setpoint must be
increased by 2K (night operation).
The controller works with the temperature sensor TF 201. The customer
must be prevented from adjusting the setpoint lower than 0°C.

Please always note safety instructions on page 2!

If the TAR is switched ON, the display shows the value of sensor input 1.

Enter code number "70" at parameter P43

P26= 1, Sensor Type TF 201 and display in °C

P14= 2, Operating mode with 1 control sensor (F1) only

Enter code number "88" at parameter P43

P03= 9.0 (cooling setpoint, relay K1)

P04= -7.0 (heating setpoint 7 K below P03, relay K2)

P05= 2 (heating setpoint is relative value, coupled to the cooling
setpoint)

P06= 2.0 (cooling setpoint will be increased by 2K while night
operation)

P07= 1 (relay K1 will be activated with rising temperature)

P08= 3 (relay K2 will be activated with falling temperature = Heating)

P09= 1 (alarm relay K4 will be de-activated with an alarm)

P10= 15 (the setpoint cannot adjusted higher than +15°)

P11= 0 (the setpoint cannot adjusted lower than 0°)

P12= 1 (hysteresis of cooling relay, 1K)

P13= 1 (hysteresis of heating relay, 1K)

P31= 30 (alarm delay 30 minutes)

P32= 5 (overtemperature alarm 5 K higher than cooling setpoint)

P33= 0 (underemperature alarm at 0°)

P34= 1 (digital input open = night shift)

P35= 0 (night shift works immediately)

Display Correction

The Actual Value Display P01 can be adjusted by P27, the Actual Value
Display P02 can be adjusted by P28.

 Start-up example: TAR as Humidity Controller

Requirements:

De-humidifying ON at 80% r.H., Moisten ON at 60% r.H., hysteresis 2%,
both setpoints are absolute values, no alarm, no night shift.
The controller must work with the humidity transmitter FF 2520.
No setpoint limitation for the customer.
The customer want to read the humidity value on a remote display with 0-
10V-input.

Please always note safety instructions on page 2!

If the TAR is switched ON, the display shows the value of sensor input 1.

Enter code number "70" at parameter P43

P26=5, Transmitters with 4-20 mA signal

P14=2, Operating mode with 1 control sensor only

Enter code number "88" at parameter P43

P03=78.0 (de-humidify setpoint, relay K1)

P04=62.0 (moisten setpoint , relay K2)

P05=1 (setpoints are absolute values)

P06=0 (no setpoint shift)

P07= 1 (relay K1 will be activated by rising humidity = de-hum.)

P08= 3 (relay K2 will be activated by falling humidity = hum.)

P10= 100

P11= 0

P12= 2 (hysteresis for de-humidifying relay, 2%)

P13= 2 (hysteresis for moistening relay, 2%)

P29= 100 (display value with 20 mA current input)

P30= 0 (display value with 4 mA current input)

P34= 0 (Digital input disabled)

P36= 100 (Analog output delivers 10V DC at 100% r.H.)

P37= 0 (Analog output delivers 0V at 0% r.H.)

P39= 1 (operating mode of analogue output)

Display Correction

The actual value display P01 can be adjusted by P27.

Installation hint:

If the measured values 'jump' check the following: Is the shielding of the sensor wire connected to PE near the controller unit? Is the PE
terminal of the controller unit connected to PE? If the sensor wire is shielded correctly but the value on the display continues 'jumping', please
try to solve the problem by removing the shield from PE and connecting it to a ground terminal of the TAR.

EG-Statement of Conformity

*The conformity with IEC 1000-4-3 is derived from the IEC 1000-4-2 and IEC 1000-4-4 test results. The correlation with IEC 1000-4-3 is based on test results which
are located on site at the manufacturer.

We state the following: When operated in accordance with the technical manual, the criteria have been met that are outlined in the guidelines
of the council for alignment of statutory orders of the member states on electro-magnetic consistency ( 89/336/EWG ). This declaration is valid
for those products covered by the technical manual which itself is part of the declaration. Following standards were consulted for the confirmity
testing with regard to electromagnetic consistency :

IEC 1000-4-1, IEC 1000-4-2, IEC 1000-4-3*, IEC 1000-4-4, IEC 1000-4-5, EN 55011 B, EN 50081, part 1 and 2;

EN 50082, part 1 and 2, EN 61010 part 1, EN 61010-1/A2 part 1/A1

This statement is made from the manufacturer / importer

by:

ELREHA Elektronische Regelungen GmbH

Klaus Birkner,  Developement and

68766 Hockenheim, Germany

and leader of the EMC-Laboratory

(Name / Anschrift /

 name / adress)

Hockenheim

12.3.98

.............................................

Ort/

city

Datum/

date

Unterschrift/

sign

This manual, which is part of the product, has been set up with care and our best knowledge, but mistakes are still possible.
Technical details can be changed without notice, especially the software. Please note that the described functions are only valid for units containing
the software with the version-number shown on page 1of this manual. Units with an other software number can work a little bit different. You will
find this number on the type label.

set up 23.2.05, tkd/jr

checked:

23.2.05, ek/al

approved:

23.2.05, mv/sha

Содержание TAR 1260

Страница 1: ... Double Single Setpoint Dual Setpoint Proportional PI Controller Step Controller Setpoint shift by 2nd sensor Cold Storage Control with Cyclic Defrost l Output 0 10VDC delivers control deviation or an actual value image Please note Safety Instructions TAR 1260 TAR 3260 TAR 5260 TAR 19260 l Limit value alarm Alarm relay l Inputs for PTC Pt1000 and 4 20 mA for any 2 wire transmitters l 2 setpoint by...

Страница 2: ...e in equipment or systems that are intended to be used under such circumstances that may affect human life Forapplicationsrequiringextremelyhighreliability please contact the manufacturer first Electrical installation and putting into service must be done from authorized personnel Please note the local safety instructions Before installation Check the limits of the controller and your application ...

Страница 3: ...N in op mode 4 Defrost runs 3 All TAR versions are marked in the same way Unlock Keys Topreventun authorizedpersonsfromeditingparametervalues there is a locking function which allows only the most important parameters to be changed at any time All other parameters must be unlocked beforehand This means that at parameter P43 a certain value is to be set see parameter listing Press key P parameter n...

Страница 4: ...h low sensor error 3 activated if P02 is too high low sensor error 4 activated P02 is too high low sensor error P10 x x x x 88 Highest with P03 resp P04adjustable setpoint 50 C 100 300 C P11 x x x x 88 Lowest with P03 resp P04 adjustable setpoint 50 C 100 P10 C P12 x x x x 88 Hysteresis of Setpoint 1 relay 1 2 0 2 20 P13 x x x x 88 Hysteresis of Setpoint 2 relay 2 2 0 2 20 P14 x x x x 70 Operation...

Страница 5: ... 0 P31 x x x x 88 Alarm delay 5 1 99 min P32 x x x x 88 Upper alarm limit Relative related to the active 0 300 potentially shifted setpoint 1 P33 x x x x 88 Lower alarm limit Absolute value 100 100 300 P34 x x x x 88 Digital Input 1 OK 1 0 0 input disabled 1 Night setpoint 2 External Alarm 3 Unit OFF P35 x x x x 88 Delay time for Digital Input OK 1 2 0 99 min P36 x x x x 88 Analog output 10V DC at...

Страница 6: ...air flow defrost The 4 20 mA input is deactivated Actual value display status display With temperature sensors Temperatures can be displayed in C or F selected by parameter P26 sensor type switch The resolution is 0 1 C or 0 2 F While operating with temperature sensors P01 shows the actual value of sensor 1 You also come back to this display at P01 if another parameter is selected and no key is pr...

Страница 7: ...y is activated active or de activated passive if an alarm occurs Minimium idle time If a relay has been switched OFF it can be activated first after timer P15 is run down If the switching characteristic is set to cycling this function is de activated Parameters P23 and P24 show the remaining time until the relays will switch ON again Example for a cycling heater Switching char P07 4 Setpoint 1 P03...

Страница 8: ...trollers can be networked via their built inRS 485 interface Thisnetworkcanbecontrolled by a host unit Normally this host is a PC with a qualified software which allows remote control of units and recording of all parameters Because all units are connected parallel on the data cable every unit has its own network address P42 to ensure a specific communication The communication speed is fixed by P4...

Страница 9: ...t setpoint P03 shift Example P36 10 C P37 10 C P39 3 P03 15 C no current shift Output 0V at P03 P36 25 C voltages 10V at P03 P37 5 C Example Actual Value Image You have a remote display or similar which shows 50 C at 0V input voltage and 50 C at 10V DC P37 50 P36 10 P39 must be 1 Example Proportional Controller You want to control any device with 0 10V input depending on pressure You want it to be...

Страница 10: ... 2 Basic settings P14 2 P07 1 P08 1 P26 1 4 2 stage pressure controller Basic settings P14 2 P07 1 P08 1 P26 5 P29 P30 depends on transmitter Moisturize de humidifying basic settings P14 2 P07 1 P08 3 P26 5 P29 100 P30 0 Temp Feuchte Druckregler Temp Hum Press Control 70 2 76 5 9 Alarm K4 F 2 11 12 24V AC DC F 1 12 13 10 14 15 4 20mA 7 8 6 16 17 18 19 OK1 12 47 56 2 2 4 1 2 3 20 21 DO NDO 22 23 24...

Страница 11: ...V D C 4 20 mA IN 33 32 sensor 1 sensor 2 37 35 36 38 DG x xx 29 10 relay K2 AC 3 2 1 5 4 mains TAR 3260 7 6 8 9 relay K1 24 22 21 20 23 26 25 D O DC 27 28 0 10V DC RS 485 sensor 1 sensor 2 4 20 mA IN 15 11 12 14 13 17 16 N L 19 18 relay K4 alarm OK 1 34 N D O 30 31 33 32 36 35 38 37 29 10 relay K2 DC 5 2 1 3 4 TAR 3260 mains 7 6 8 9 relay K1 AC 24 21 20 22 23 26 25 27 28 D O 0 10V DC sensor 1 sens...

Страница 12: ...5 28 29 30 20V DC f Geber N PE L 1 2 5 6 4 3 8 7 9 10 11 P E 4 20 mA 0 10V RS 485 N D O D O mains relay K1 relay K2 16 22 17 18 21 20 19 23 24 26 25 5 1 2 3 4 0 10V 15 32VDC 4 20mA 13 12 15 14 N OK 1 OK 2 relay K4 alarm 28 29 30 N PE 14 29 L 1 13 2 5 6 4 3 8 7 9 10 12 11 P E 4 20 mA 0 10V RS 485 N D O D O N OK 1 20V DC f transmitter relay K1 relay K2 relay K4 alarm mains 16 22 17 18 21 20 19 23 24...

Страница 13: ...2 sensor 1 16 sensor 2 18 32 RS 485 30 26 28 24 22 20 DO NDO F2 13 19 18 4 20mA 20 24 25 relay 4 alarm z 14 OK2 10 12 8 15 6 2 4 OK1 N 1 PE 14 terminal 0 10V DC F1 4 2 22 23 20VDC 17 26 28 32 30 21 22 24 16 8 4 5 10 14 16 20 18 12 11 12 7 6 6 3 relay 1 relay 2 2 d N L terminal 4 PE 22 20 19 26 28 32 RS 485 30 DO NDO 24 25 24 F2 18 4 20mA Vers Signal 8 15 10 14 16 20 18 13 OK2 12 6 OK1 14 relay 4 a...

Страница 14: ...point relay K2 P05 1 setpoints are absolute values P06 0 no setpoint shift P07 1 relay K1 will be activated by rising humidity de hum P08 3 relay K2 will be activated by falling humidity hum P10 100 P11 0 P12 2 hysteresis for de humidifying relay 2 P13 2 hysteresis for moistening relay 2 P29 100 display value with 20 mA current input P30 0 display value with 4 mA current input P34 0 Digital input ...

Отзывы: