Technical Manual Temperature-, Humidity-, Pressure-Controller TAR x260

  Technical Data

Operating Voltage .............. see type overview
Power Consumption ........... approx. 3,5 VA
Output relays ....................... 3 x potential free
Relay rating ........................ 8A cos phi=1, 3A ind. / 250V AC
Operating Temp. ................ -10...+55°C / 14...131°F
Storage Temp. .................... -30...+70°C / -22...158°F
Air humidity ......................... max. 85% r.H., not condensing
Signal  inputs ....................... 2x TF 201 (PTC) or TF 501 (Pt1000),

1x 4...20 mA, 100 ohms shunt

Transmitter  supply .............. appr. 12VDC unreg., max. 35 mA
Display ................................ LED, character height 13mm

19"-module : char. height 10mm

Resolution ........................... 0,1 / °C, 0,2 / °F
Control-/Display  range ....... -100...+300 (°C, bar, °F up to +572)
Data storage parameters ... typ. 10 years
Relay indicator .................... LED 2 mm, red
Digital Input (Optocpl.) ....... 230V, 3mA (1260: external switch)
Analogue output .................. 0-10 V DC, max. 3 mA
Resolution Analogue Outp. . 8 bit within the set limit values
Data interface ..................... RS-485 (

E-Link)

Electrical connection .......... Screw terminals 2,5mm

19"-module : connector "F"

Housing, Protection

TAR 1260 ................ 77 x 35 mm, IP 54 from front
TAR (2)3260 ............ for 35mm DIN-rail, IP 30
TAR (2)5260 ............ 96 x 48 mm, IP 54 from front
TAR (2)19260 .......... 19"module, 8 TE

Further information you will find in the parameter listing

 Type Overview

TAR 1260 ........... Panel mounting, 12-24V AC/DC
TAR 3260 ........... for 35mm DIN-rail, 230V~, 50-60 Hz
TAR 5260 ........... Panel mounting, 230V~, 50-60 Hz
TAR 19260 ......... 19"-Module, 8TE, 230V~, 50-60 Hz
TAR 23260 ......... for 35mm DIN-rail, 115V~, 60 Hz
TAR 25260 ......... Panel mounting, 115V~, 60 Hz

TAR 29260 ......... 19"-Module, 8TE, 115V~, 60 Hz

  Accessories (please order separately)

- Temperature sensor TF 201 (max. 80°C) 

or PT1000 (max. 300°C)

- Two-wire pressure transmitter, Type DG... or similar with

4-20 mA signal output

- Humidity transmitter FF 2520 with 4...20mA output
- For type TAR 1260: Matching transformer, please contact us.
- For type TAR 19260: Subrack or Panel housing

 Contents

page

Safety Instructions .......................................................... 2
Operating / Operating Elements / Failure Displays .......... 3
Access protection .............................................................. 3
Parameter listing ............................................................... 4-5
Functional Description

Value sources, Operating modes
Alarm, Switching modes, Digital Input, Analogue output

Networking ......................................................................... 9
Dimensions/ Wiring ........................................................... 11
Run-Up Examples ............................................................. 15

Please read before Start-up

• Limit of Application: This product is not designed nor

manufactured for use in equipment or systems that are
intended to be used under such circumstances that may
affect human life.
For applications requiring extremely high reliability, please
contact the manufacturer first

• Electrical installation and putting into service must be

done from authorized personnel.

• Please note the local safety instructions !

• Before installation: Check the limits of the controller and

your application. Before starting up we recommend you to
read the following instructions for use, since only by doing
so you can avoid damage or malfunction and you will
benefit all the advantages offered by this product.

• During installation and wiring never work when the

electricity is not cut-off !

• If the units should be networked, never connect the

secondary coil of 12/24V transformers to PE !

• To control servo drives/actuators, a TAR 1260 must be

supplied by a separate transformer

• Mounting the controller close to power relays is

unfavourable in case of the electro-magnetic interference.

• Before applying voltage to the controller:

Make sure that all wiring has been made in accordance
with the wiring diagram in this manual.
Check, if the supply voltage corresponds to the value
printed on the type label.

• Connect the ‘PE’ terminal carefully to ground because

otherwise the operation of the internal noise filter will be
disabled.

• Respect the environmental limits for temperature and

humidity. Outside these limits malfunctions may occur.

• Never operate unit without housing.

• Observe the maximum admitted current rate for the

relays (see technical data). Compare with the peak start-
up current of the controlled devices (valve, fan,
compressor, heater..)

• Sensor cables may be up to some hundred meters in

length. Use shielded sensor cable only. Don’t install them
in parallel with high-current cables to prevent inductive
interference. A cross section of min. 0,5mm² is sufficient.

• Shielding has to be connected to PE at the end near the

controller

• All used temperature sensors must be identical. Never

use PTC (TF 201) and PT1000 (TF 501) mixed. This will
not work.

• TF-type sensors are moisture-proof but they are not

designed for being immersed in water for a long period of
time (not pressure-proof). In such a case, always use dip-
fittings.

• Be care that the wiring of interface lines meets the

requirements

 CONNECTION & SAFETY INFORMATIONS

Содержание TAR 1260

Страница 1: ... Double Single Setpoint Dual Setpoint Proportional PI Controller Step Controller Setpoint shift by 2nd sensor Cold Storage Control with Cyclic Defrost l Output 0 10VDC delivers control deviation or an actual value image Please note Safety Instructions TAR 1260 TAR 3260 TAR 5260 TAR 19260 l Limit value alarm Alarm relay l Inputs for PTC Pt1000 and 4 20 mA for any 2 wire transmitters l 2 setpoint by...

Страница 2: ...e in equipment or systems that are intended to be used under such circumstances that may affect human life Forapplicationsrequiringextremelyhighreliability please contact the manufacturer first Electrical installation and putting into service must be done from authorized personnel Please note the local safety instructions Before installation Check the limits of the controller and your application ...

Страница 3: ...N in op mode 4 Defrost runs 3 All TAR versions are marked in the same way Unlock Keys Topreventun authorizedpersonsfromeditingparametervalues there is a locking function which allows only the most important parameters to be changed at any time All other parameters must be unlocked beforehand This means that at parameter P43 a certain value is to be set see parameter listing Press key P parameter n...

Страница 4: ...h low sensor error 3 activated if P02 is too high low sensor error 4 activated P02 is too high low sensor error P10 x x x x 88 Highest with P03 resp P04adjustable setpoint 50 C 100 300 C P11 x x x x 88 Lowest with P03 resp P04 adjustable setpoint 50 C 100 P10 C P12 x x x x 88 Hysteresis of Setpoint 1 relay 1 2 0 2 20 P13 x x x x 88 Hysteresis of Setpoint 2 relay 2 2 0 2 20 P14 x x x x 70 Operation...

Страница 5: ... 0 P31 x x x x 88 Alarm delay 5 1 99 min P32 x x x x 88 Upper alarm limit Relative related to the active 0 300 potentially shifted setpoint 1 P33 x x x x 88 Lower alarm limit Absolute value 100 100 300 P34 x x x x 88 Digital Input 1 OK 1 0 0 input disabled 1 Night setpoint 2 External Alarm 3 Unit OFF P35 x x x x 88 Delay time for Digital Input OK 1 2 0 99 min P36 x x x x 88 Analog output 10V DC at...

Страница 6: ...air flow defrost The 4 20 mA input is deactivated Actual value display status display With temperature sensors Temperatures can be displayed in C or F selected by parameter P26 sensor type switch The resolution is 0 1 C or 0 2 F While operating with temperature sensors P01 shows the actual value of sensor 1 You also come back to this display at P01 if another parameter is selected and no key is pr...

Страница 7: ...y is activated active or de activated passive if an alarm occurs Minimium idle time If a relay has been switched OFF it can be activated first after timer P15 is run down If the switching characteristic is set to cycling this function is de activated Parameters P23 and P24 show the remaining time until the relays will switch ON again Example for a cycling heater Switching char P07 4 Setpoint 1 P03...

Страница 8: ...trollers can be networked via their built inRS 485 interface Thisnetworkcanbecontrolled by a host unit Normally this host is a PC with a qualified software which allows remote control of units and recording of all parameters Because all units are connected parallel on the data cable every unit has its own network address P42 to ensure a specific communication The communication speed is fixed by P4...

Страница 9: ...t setpoint P03 shift Example P36 10 C P37 10 C P39 3 P03 15 C no current shift Output 0V at P03 P36 25 C voltages 10V at P03 P37 5 C Example Actual Value Image You have a remote display or similar which shows 50 C at 0V input voltage and 50 C at 10V DC P37 50 P36 10 P39 must be 1 Example Proportional Controller You want to control any device with 0 10V input depending on pressure You want it to be...

Страница 10: ... 2 Basic settings P14 2 P07 1 P08 1 P26 1 4 2 stage pressure controller Basic settings P14 2 P07 1 P08 1 P26 5 P29 P30 depends on transmitter Moisturize de humidifying basic settings P14 2 P07 1 P08 3 P26 5 P29 100 P30 0 Temp Feuchte Druckregler Temp Hum Press Control 70 2 76 5 9 Alarm K4 F 2 11 12 24V AC DC F 1 12 13 10 14 15 4 20mA 7 8 6 16 17 18 19 OK1 12 47 56 2 2 4 1 2 3 20 21 DO NDO 22 23 24...

Страница 11: ...V D C 4 20 mA IN 33 32 sensor 1 sensor 2 37 35 36 38 DG x xx 29 10 relay K2 AC 3 2 1 5 4 mains TAR 3260 7 6 8 9 relay K1 24 22 21 20 23 26 25 D O DC 27 28 0 10V DC RS 485 sensor 1 sensor 2 4 20 mA IN 15 11 12 14 13 17 16 N L 19 18 relay K4 alarm OK 1 34 N D O 30 31 33 32 36 35 38 37 29 10 relay K2 DC 5 2 1 3 4 TAR 3260 mains 7 6 8 9 relay K1 AC 24 21 20 22 23 26 25 27 28 D O 0 10V DC sensor 1 sens...

Страница 12: ...5 28 29 30 20V DC f Geber N PE L 1 2 5 6 4 3 8 7 9 10 11 P E 4 20 mA 0 10V RS 485 N D O D O mains relay K1 relay K2 16 22 17 18 21 20 19 23 24 26 25 5 1 2 3 4 0 10V 15 32VDC 4 20mA 13 12 15 14 N OK 1 OK 2 relay K4 alarm 28 29 30 N PE 14 29 L 1 13 2 5 6 4 3 8 7 9 10 12 11 P E 4 20 mA 0 10V RS 485 N D O D O N OK 1 20V DC f transmitter relay K1 relay K2 relay K4 alarm mains 16 22 17 18 21 20 19 23 24...

Страница 13: ...2 sensor 1 16 sensor 2 18 32 RS 485 30 26 28 24 22 20 DO NDO F2 13 19 18 4 20mA 20 24 25 relay 4 alarm z 14 OK2 10 12 8 15 6 2 4 OK1 N 1 PE 14 terminal 0 10V DC F1 4 2 22 23 20VDC 17 26 28 32 30 21 22 24 16 8 4 5 10 14 16 20 18 12 11 12 7 6 6 3 relay 1 relay 2 2 d N L terminal 4 PE 22 20 19 26 28 32 RS 485 30 DO NDO 24 25 24 F2 18 4 20mA Vers Signal 8 15 10 14 16 20 18 13 OK2 12 6 OK1 14 relay 4 a...

Страница 14: ...point relay K2 P05 1 setpoints are absolute values P06 0 no setpoint shift P07 1 relay K1 will be activated by rising humidity de hum P08 3 relay K2 will be activated by falling humidity hum P10 100 P11 0 P12 2 hysteresis for de humidifying relay 2 P13 2 hysteresis for moistening relay 2 P29 100 display value with 20 mA current input P30 0 display value with 4 mA current input P34 0 Digital input ...

Отзывы: