Function
The safety evaluation unit monitors connected sensors that are equipped with
an NO and an NC contact.
In the process, the switching sequence of the contacts does not play a role.
The safety evaluation unit switches its safety output acc. to the operating
states of the connected senors and connected external contactors.
In the following situations, the safety evaluation unit switches the safety
output through:
- The sensors are actuated correctly.
- The feedback contacts of the external contactors are closed.
In the following situations, the safety evaluation unit switches the safety
output off:
- An NO contact of a connected sensor is opened.
- An NC contact of a connected sensor is closed.
- A fault is present (safety evaluation unit or connected sensor defective).
The control output of the terminals (24 through 26) signals the status of
the safety output:
- When the safety output is closed, contacts 25 and 26 are closed as well.
- When the safety output is open, contacts 24 and 26 are closed.
LED indicators
Waiting period
The waiting period is the maximum time that may pass on a sensor after both
sensor contacts have been actuated.
Safe state
The safety output is opened and/or highly resistive.
8
Technical specifications
See Technical specifications as of
9
Assembly
- The safety evaluation unit may be installed only in a de-energized state.
- Assembly is permitted only in an installation area that is protected against dust
and moisture.
- Limit the line length for connections to max. 30 m.
- Snap the safety evaluation unit onto a top-hat rail (EN 60715 TH35) in the
switch cabinet.
The safety evaluation unit is fixed into place.
- Connect the safety evaluation unit; see Technical specifications as of
- Ensure that the required safety devices are used; see Technical specifica-
tions as of
- When the safety input is to remain free:
Make sure that the NO contact of this safety input is bypassed.
10 Electrical connection
- The electrical connection may be established only in a de-energized state.
- Make sure that the specifications described in the technical specifications
absolutely must be observed.
When a sensor is connected, the sensor supply voltage (+) and (-) of the terminals
specified in the technical specifications must be used.
Terminal assignment
NOTE
A complete protective insulation acc. to EN 61140 is provided when the device
is installed in a switch cabinet for operation.
11 Commissioning
In any order:
- Actuate the safety sensors.
- Apply operating voltage.
The safety evaluation unit is ready for operation.
The safety evaluation unit switches the safety output through.
NOTE
Please ensure that the EDM input is correctly wired.
NOTE
After the first-time commissioning of a safety evaluation unit, an overall
validation must be performed acc. to the pertinent standards.
12 Maintenance
The inspection of the safety circuit must be performed by specially trained,
authorized personnel acc. to the nationally valid regulations within the required
time periods.
(Recommendation: If no nationally valid regulations are available, the function
check acc. to the applications must be performed pursuant to EN ISO 14119.)
Operational
readiness
Safety
input 1
Safety
input 2
Safety
input 3
Safety
input 4
Safety output
Position
Terminal 2
Termi-
nal 8
Termi-
nal 12
Termi-
nal 15
Termi-
nal 19
Termi-
nal 24
Termi-
nal 25
LED
indicator
1 x
green
1 x
red
1 x
green
LED off
Safety evalu-
ation unit not
ready for
operation
Safety input not actuated
Safety
output
closed
Safety
output
not
closed
LED
flashing
A fault was
detected;
see
Safety input semi-actuated
—
—
LED
lights
up
Safety evalu-
ation unit
ready for
operation
Safety input actuated
Safety
output
not
closed
Safety
output
closed
Danger
Risk to life due to electrical shock!
Make sure that the safety evaluation unit is mounted and
commissioned only by specially trained, authorized person-
nel.
Component
Terminal Definition
Safety input 1
6-9
Connection options:
Sensors with NO/NC contact system
Safety input 2
10-13
Safety input 3
14-17
Safety input 4
18-21
Safety output
3-4
Dependent switching by:
- Safety inputs 1-4
- EDM input
EDM
22-23
Monitoring of external contactors.
If no external contactor is used, this input
must be bypassed!
Control output
24-26
Not suitable for safety functions!
Dependent switching by:
- Safety inputs 1-4
- EDM input
Operating voltage
1-2
24 V AC/DC
Danger
Risk to life due to electrical shock!
Make sure that the safety evaluation unit is mounted and
commissioned only by specially trained, authorized personnel.