22
Insert the lead from side “
K
” of the Current Transformers of
Line
1
through the bottom of the CT core
I
1A, (top left looking from
back), of the
ElNet
Energy & Powermeter
.
ARNING
Repeat the procedure for
Line 2
and
Line 3
(In ElNet PQ repeat
also for
Neutral
Line I
N
)
.
Connect the rest of the connections to the
ElNet
Energy &
Powermeter
by means of terminal connector plugs.
The Rear Panel (See Figure 2.7.
)
has all connections printed and
are simple to follow. (See table 2-1 for connections)
•
Ensure the leads from leg
“K
” of the Current
Transformer on
Line 1
pass through the bottom of
CT core I1A.
•
Ensure the other end of the lead emerging from the
top of C T core
I
1A is connected to leg “L” of the
Current Transformer on
Line 1
WARNING!
Never allow an open circuit between the two Current
Transformers.