background image

18

19

ELMON 

relay

 32-242

Safety Relay

English

Figure 1: Connection of multiple sensors; in this example: safety contact edge

8.4 Connecting control circuits

The control circuit to be monitored for Channel 1 is to be connected to the terminal pair 

4

5

 and the corre-

sponding control circuit for Channel 2 is to be connected to the terminal pair 

6

7

 .

The control circuits must be protected by a corresponding circuit breaker depending on the rated current or 

the rated current in the control circuits must be limited to the maximum value by other means.

The relay contact may only switch extra low voltages (30V). The switching of low voltages (230V) 

is not permissible .

9. Commissioning and performance testing

After all the electrical contacts have been connected and the supply voltage switched on, the plant / machinery 

must be tested for proper functioning.
Following successful commissioning the safety outputs 

4

5

 and 

6

7

 are activated (relay contacts “closed”). 

Activating the annunciator results in opening the relay contacts.
The safety system must be tested by qualified staff at appropriate intervals. The testing must be comprehen

-

sibly documented at all times. The requirements of the plant / machinery manufacturer must be observed 

and adhered to .

10. Error diagnosis

If the wiring and connecting up of the supply voltage is correct, only the green LED Power should light up. If the 

red LED lights up there is a fault in the system, which can be isolated with the aid of the LED.

*  If the fault is not in the wiring, the functioning of the electronics may be checked by fitting an 8.2 kΩ 

resistance to the annunciator input on the relay. If the electronics then work properly, the annunciator 

must be tested with an ohmmeter. For this the connection between the annunciator and the relay must 

be disconnected and connected to an ohmmeter. With an inactivated annunciator the resistance should 

be 8.2 kΩ ± 500 Ω. If the annunciator is activated, the resistance should not exceed 500 Ω.

11. Decommissioning and disposal

Products manufactured by ASO are intended exclusively for commercial use (B2B). At the end of their service 

the products should be disposed of in accordance with the local, regional and national regulations. ASO will 

be pleased to collect the products for disposal in accordance with the regulations.

LED

Error

Error correction

green LED

Power

does not light up

Supply voltage absent,

too low

or wrongly connected.

Test connections and supply voltage:

- 24 V AC/DC to terminals 

8 9

tolerance range: ±10%

green LED

Power

flashes cyclically (pulse)

Internal fault is shown by the 

number of pulses .

See -> Signal displays

red LED

Channel 1

 / 

Channel 2

lights up

The relevant sensor

is recognised as activated.

- Check connections of the relevant sensors

  (pinched wiring, brittle wiring etc.)

- Check sensor *

red LED

Channel 1

 / 

Channel 2

flashes rapidly

Sensor circuit broken,

sensor not connected,

connected incorrectly or faulty

- Check connections of the relevant sensors

  (pinched wiring, brittle wiring etc.)

- Check sensor *

Содержание 32-242

Страница 1: ...al G ltigkeit siehe letzte Seite ELMON relay 32 242 Sicherheitsschaltger t Operating Manual see last page for validity ELMON relay 32 242 Safety Relay Manuel d utilisation Validit voir la derni re pag...

Страница 2: ...al mounting 17 8 Electrical connection 18 8 1 Supply voltage 18 8 2 Sensor connection 18 8 3 Connecting several sensors per sensor circuit 18 8 4 Connecting control circuits 19 9 Commissioning and per...

Страница 3: ...ut fail The electrical engineering and professional society safety rules are to be observed When working on the relay it must be disconnected from the power supply tested for zero potential and secure...

Страница 4: ...tate of the sensor and the operating voltage supplied are shown by LEDs In the event of a fault alarm all safety outputs are inactive The unit can be used in a household environment as well as an indu...

Страница 5: ...or activated on Sensor circuit broken flashes rapidly Fault self lock flashes slowly 5 Verwendungsbeispiele Circuit diagram in zero potential state Sensor not activated ELMON relay 32 242 24 V DC 0 V...

Страница 6: ...ON relay 32 242 Safety Relay English If there is no fault alarm the operating state is shown via the LED Power on When signalling a fault alarm the number of pulses emitted indicates the nature of the...

Страница 7: ...purpose the individual sensors are connec ted in series according to figure 1 Safety edges SENTIR edge Up to five SENTIR edge may be connected in series The maximum total length oft the SENTIR edge sh...

Страница 8: ...can be isolated with the aid of the LED If the fault is not in the wiring the functioning of the electronics may be checked by fitting an 8 2 k resistance to the annunciator input on the relay If the...

Страница 9: ...12 ms response time Turn off time 500 ms ELMON relay 32 242 100 ms ELMON relay 32 242 K Power on 700ms Assembly Plug in socket to 35 mm DIN snap on rail Housing 11 pol DIN plug in socket housing with...

Страница 10: ...claration of conformity ELMON relay 32 302 ELMON relay 32 312 ELMON relay 32 242 ELMON relay 32 332 ELMON relay 32 302 ELMON relay 32 312 ELMON relay 32 242 ELMON relay 32 332 ELMON relay 32 302 ELMON...

Отзывы: