8. Electrical connection

Connection to the wrong terminals may damage the relay.

Wiring laid in the open or outside the control box must be properly protected.

The signal wiring may not be connected parallel to the motor wiring or other power wiring.

The limits shown in the “Technical Data” for the supply voltage and relay switching capacity must 

be observed. Sufficient fuse protection must be provided on all output contacts with capacitive 

and inductive loads.

8.1 Supply voltage

The supply voltage is to be connected to the terminal pair 

8 9

 24 V AC/DC. The supply wiring to the relay must 

be protected by a suitable circuit breaker. The supply voltage must meet the requirements for low voltage 

protection (SELV).

8.2 

Sensor connection

Connect the sensor for Channel 1 to the terminal pair 

3 11

 . Connect the sensor for Channel 2 to the terminal 

pair 

3 10

 .

If a channel is not used, it must be fitted with an 8.2 kΩ resistance.

8.3 Connecting multiple sensors per sensor circuit

ASO sensors must not be connected in parallel.

One or more sensors can be connected to sensor input . For this purpose, the individual sensors are connec-

ted in series according to figure 1.

Safety edges SENTIR edge:

Up to five SENTIR edge may be connected in series. The maximum total length oft the SENTIR edge shall 

not exceed 100 m.

The length of one SENTIR edge may be up to 25 m . 

The total cable length oft the in series connected SENTIR edge must not exceed 25 m.

Safety bumper SENTIR bumper:

Up to five SENTIR bumper may be connected in series. The maximum total length oft the SENTIR bumper

 

shall not exceed 15 m.

The length of one SENTIR bumper may be up to 3 m . 

The total cable length oft the in series connected SENTIR bumper must not exceed 25 m.

Safety contact mat SENTIR mat:

Up to ten SENTIR mat may be connected in series. The maximum total area shall not exceed 10 m

2

 .

The maximum size of an SENTIR mat is 1350 x 2350 mm. The total cable length oft the in series connected 

SENTIR mat must not exceed 25 m.
Before connecting the sensors that are connected in series, it is recommended that the resistance value of 

the arrangement is to be measured. The resistance must be 8.2 kΩ ± 500 Ω when the sensor is inactive and 

must not exceed 500 Ω when it is active.

Safety Relay

English

Sensor „n“

Sensor 2

Sensor 1

Opening

Figure 1: Connection of multiple sensors; in this example: safety contact edge

2

2

2

2

Содержание 32-242

Страница 1: ...al G ltigkeit siehe letzte Seite ELMON relay 32 242 Sicherheitsschaltger t Operating Manual see last page for validity ELMON relay 32 242 Safety Relay Manuel d utilisation Validit voir la derni re pag...

Страница 2: ...al mounting 17 8 Electrical connection 18 8 1 Supply voltage 18 8 2 Sensor connection 18 8 3 Connecting several sensors per sensor circuit 18 8 4 Connecting control circuits 19 9 Commissioning and per...

Страница 3: ...ut fail The electrical engineering and professional society safety rules are to be observed When working on the relay it must be disconnected from the power supply tested for zero potential and secure...

Страница 4: ...tate of the sensor and the operating voltage supplied are shown by LEDs In the event of a fault alarm all safety outputs are inactive The unit can be used in a household environment as well as an indu...

Страница 5: ...or activated on Sensor circuit broken flashes rapidly Fault self lock flashes slowly 5 Verwendungsbeispiele Circuit diagram in zero potential state Sensor not activated ELMON relay 32 242 24 V DC 0 V...

Страница 6: ...ON relay 32 242 Safety Relay English If there is no fault alarm the operating state is shown via the LED Power on When signalling a fault alarm the number of pulses emitted indicates the nature of the...

Страница 7: ...purpose the individual sensors are connec ted in series according to figure 1 Safety edges SENTIR edge Up to five SENTIR edge may be connected in series The maximum total length oft the SENTIR edge sh...

Страница 8: ...can be isolated with the aid of the LED If the fault is not in the wiring the functioning of the electronics may be checked by fitting an 8 2 k resistance to the annunciator input on the relay If the...

Страница 9: ...12 ms response time Turn off time 500 ms ELMON relay 32 242 100 ms ELMON relay 32 242 K Power on 700ms Assembly Plug in socket to 35 mm DIN snap on rail Housing 11 pol DIN plug in socket housing with...

Страница 10: ...claration of conformity ELMON relay 32 302 ELMON relay 32 312 ELMON relay 32 242 ELMON relay 32 332 ELMON relay 32 302 ELMON relay 32 312 ELMON relay 32 242 ELMON relay 32 332 ELMON relay 32 302 ELMON...

Отзывы: