Connections and Signalling outputs 

Load / - 

Screw terminals Voltage output to load 

GEN PSU Fault (normally 

closed contact) 

0.10 A @ 60 Vdc 16Ω solid state relay contacts, volt free

 

Open if Mains failed and battery voltage < 23 V or fault PSU fault 

condition, (see below) 

EPS Fault (normally closed 

contact) 

0.10A @ 60 Vdc 16Ω solid state relay contacts, volt free

 

Open if loss of mains for > 10 seconds 

Temperature sensor 

Thermistor input from supplied battery terminal thermistor. 

BATT + / - 

Connection to back up battery using supplied battery lead. 

 

 

Optional Serial interface 

5 pin header (For details contact Elmdene Technical Support) 

 

 

Fault Outputs 

EPS Fault 

GEN Fault 

Condition 

Possible Cause 

Action 

C

LOSED 

C

LOSED 

Normal 

operation 

Mains present 

Battery healthy 

None 

O

PEN 

C

LOSED 

Standby 

Mode 

Mains lost 

Battery driving load 

Investigate loss of mains 

C

LOSED 

O

PEN 

Fault 

Present 

Blown fuses 

Battery fault 

 

Internal fault 

Investigate fault source 

using diagnostic LED 

Rectify fault where 

possible 

O

PEN 

O

PEN 

PSU 

Shutdown 

Mains lost 

Standby battery exhausted 

Restore mains as soon 

as possible 

 

LED Indication 

YELLOW LED 

Fault LED 

GREEN LED 

Mains supply On 

DIAGNOSTICS 

Diagnostic LED (Not visible through front panel) 

 

Fault Diagnostic table – Front panel - User 

Yellow LED 

Fault 

Green LED 

Mains 

Condition 

Possible Cause 

Action 

O

FF 

O

Normal 

operation 

Mains present 

Battery healthy 

None 

 

F

LASH 

C

ONTINUOUS 

 

O

or O

FF 

 

Fault 

Blown fuses 

Battery fault 

 

Internal fault 

 

Contact service 

engineer 

1 P

ULSE 

O

FF 

Standby Mode 

Mains lost 

Battery driving load 

Investigate loss of 

mains 

S

IGNALLING AND 

D

IAGNOSTICS

 

www.acornfiresecurity.com

www.acornfiresecurity.com

Содержание STX2402 Series

Страница 1: ...relay fault output signal i loss of mains and ii battery fault charger fault and loss of output In addition there is an optional plug in serial interface that can provide diagnostic and fault reportin...

Страница 2: ...I 2 x 17 Ah 12 V PS12170 NP17 12I Battery Charging Constant current bulk charging to 80 capacity within 24 hours Float charging to 100 within 48 hours Eco charging and check every 24 hours for up to 8...

Страница 3: ...tion Mains present Battery healthy None OPEN CLOSED Standby Mode Mains lost Battery driving load Investigate loss of mains CLOSED OPEN Fault Present Blown fuses Battery fault Internal fault Investigat...

Страница 4: ...lled no further than 10cm from the CIE and close coupled byconduit This unit must be fed from a mains power source having a separate approved disconnect device and fitted with a fuse or other over cur...

Страница 5: ...eing used to power the CIEdirectly 8 Fix to wall or other structure in correct orientation i e with hinge on left hand side using screws of sufficient size and length through the mounting holes 9 Prot...

Страница 6: ...hole Figure 3 Connections Battery Select Mains ON Diagnostic LED Fault LED L E N Mains Temperature Sensor connect To Load 6 Re apply mains Verify that the green Mains LED illuminates and the yellow Fa...

Страница 7: ...t the green Mains LED illuminates and the yellow Fault LED extinguishes 18 If connected verify that the EPS Fault monitor shows a closed contact and the GEN PSU Fault monitor shows a closed contact 19...

Страница 8: ...batteries must be removed and disposed separately via an appropriate approved battery disposal route in accordance with all national and local regulations Package used batteries safely for onward tra...

Отзывы: