Reconnect the mains. Verify that the green Mains LED illuminates and the yellow Fault LED extinguishes. 

19)

 

If connected, verify that the EPS Fault monitor shows a 

closed

 contact and the GEN PSU Fault monitor 

shows a 

closed

 contact. 

 

NOTE: Batteries must be connected before mains power is applied to enable the 
batteries to be utilised. When replacing batteries, re-connect new batteries and then 
cycle the mains power.  

 

 

O

PERATING 

I

NSTRUCTIONS

 

 

 
In the event of loss of mains, a battery fault or a GEN PSU fault, the corresponding Fault signal contacts will 
open.  
 
If the output of the PSU fails, the cause of the failure should be investigated e.g. short circuit load, 
connection of a deeply discharged battery. The fault should be rectified before restoring power to the PSU. If 
any of the fuses require replacing, ensure the correct fuse rating and type is used. 
 

M

AINTENANCE

   

 

This unit is intended for use by Service Personnel only.  There are NO USER SERVICEABLE parts inside. 
 
There is no regular maintenance required of the PSU other than periodic testing, and replacement of the 
standby battery.  

Reference should be made to the battery manufacturer's documentation to determine 

typical/expected battery life with a view to periodic replacement of the battery.  

Содержание STX2402-MOD

Страница 1: ...mature battery failure when operating from standby for extended periods Two sets of volt free solid state relay fault output signal i loss of mains and ii battery fault charger fault and loss of outpu...

Страница 2: ...2 5A 2 0A 2 5A 1 8A Battery Capacity eg PowerSonic model Yuasa model Interlogix model 2 x 2 1Ah 12V PS12021 NP2 1 12 2 x 7Ah 12V PS12070 NP7 12 2 x 17 18Ah 12V PS12170 NP17 12 BS131N Battery Charging...

Страница 3: ...S Fault GEN Fault Condition Possible Cause Action CLOSED CLOSED Normal operation Mains present Battery healthy None OPEN CLOSED Standby Mode Mains lost Battery driving load Investigate loss of mains C...

Страница 4: ...ctive Battery charging normally but 90 of full charge None 2 PULSES ON No Battery Battery disconnected Battery fuse blown Battery heavily discharged Check battery connections Check battery fuse Check...

Страница 5: ...d with a 5A or greater current capacity i e 0 75mm2 nominal conductor area having a minimum operating voltage of 300 500V ac 2 The low voltage output cable must be sized to carry the rated load curren...

Страница 6: ...and Negative terminals of the batteries to the PCB terminals Batt and Batt using the cables provided See Figure 2 and 3 13 Connect the battery temperature sensor two white wires to the PCB terminals T...

Страница 7: ...a battery fault or a GEN PSU fault the corresponding Fault signal contacts will open If the output of the PSU fails the cause of the failure should be investigated e g short circuit load connection o...

Страница 8: ...oduct any batteries must be removed and disposed separately via an appropriate approved battery disposal route in accordance with all national and local regulations Package used batteries safely for o...