PECIFICATION

 

 

 

Mains Input 

Rated Voltage 
(Operational voltage) 

110 

 240V ac  

(90 

 264V ac) 

Frequency 

50/60Hz 

Input current 

< 1.0 Amps at full load 

Inrush current 

5A Max at 25 °C 110V ac for 10ms 

Fuse 

T2.0A 20mm, 250V ac HRC 

 

Output 

Voltage at full load 

 

Mains power 

 

Battery standby 

 
27.0 

 28.3V dc  (27.6V nominal) 

20.3 

 26.0V dc 

Ripple 

<100 mV pk 

 pk max @ Rated Voltage 

Fuse 
 

Load 

 

Battery 

 

F2.5A 
F2.5A 

Battery mode selected 

2.1Ah

 

7Ah

 

17/18Ah 

(Link fitted)

 

Continuous Output Current 

No charging (Imax B) 

With charging  (Imax A) 

 

2.5A 
2.0A 

 

2.5A 
2.0A 

 

2.5A 
1.8A 

Battery Capacity 
eg 

-

 

PowerSonic model 

-

 

Yuasa model 

-

 

Interlogix model 

2 x 2.1Ah 12V 

 

PS12021 

NP2.1-12 

2 x 7Ah 12V 

 

PS12070 

NP7-12 

2 x 17/18Ah 12V 

 

PS12170 
NP17-12 

BS131N 

Battery Charging 

Constant current bulk charging to 80% capacity within 24 hours 
Float charging to 100% within 48 hours 
Eco charging and check every 24 hours 

 (for up to  8 hours pulse 

charge dependent on temperature) 

Constant current charge 

0.3A 

0.7A 

Low battery threshold voltage 

23V 

Deep discharge protection 

Threshold voltage 

 21V 

Quiescent current 

 no load 

<30mA @ 27.6V 

Quiescent current 

 batt cut off 

0mA @ 27.6V 

 

 

Mechanical 

Product Reference 

STX2402-MOD 

Module Dimensions 

 w x h x d (mm) 

150 x 207 x 52 

Weight (kg)

 

0.34 

 

Environmental  

Temperature 

 Operating 

-10 to +40°C (operating) 75% RH non-condensing 

Temperature - Storage 

-20 to +80°C (storage) 

 

Содержание STX2402-MOD

Страница 1: ...mature battery failure when operating from standby for extended periods Two sets of volt free solid state relay fault output signal i loss of mains and ii battery fault charger fault and loss of outpu...

Страница 2: ...2 5A 2 0A 2 5A 1 8A Battery Capacity eg PowerSonic model Yuasa model Interlogix model 2 x 2 1Ah 12V PS12021 NP2 1 12 2 x 7Ah 12V PS12070 NP7 12 2 x 17 18Ah 12V PS12170 NP17 12 BS131N Battery Charging...

Страница 3: ...S Fault GEN Fault Condition Possible Cause Action CLOSED CLOSED Normal operation Mains present Battery healthy None OPEN CLOSED Standby Mode Mains lost Battery driving load Investigate loss of mains C...

Страница 4: ...ctive Battery charging normally but 90 of full charge None 2 PULSES ON No Battery Battery disconnected Battery fuse blown Battery heavily discharged Check battery connections Check battery fuse Check...

Страница 5: ...d with a 5A or greater current capacity i e 0 75mm2 nominal conductor area having a minimum operating voltage of 300 500V ac 2 The low voltage output cable must be sized to carry the rated load curren...

Страница 6: ...and Negative terminals of the batteries to the PCB terminals Batt and Batt using the cables provided See Figure 2 and 3 13 Connect the battery temperature sensor two white wires to the PCB terminals T...

Страница 7: ...a battery fault or a GEN PSU fault the corresponding Fault signal contacts will open If the output of the PSU fails the cause of the failure should be investigated e g short circuit load connection o...

Страница 8: ...oduct any batteries must be removed and disposed separately via an appropriate approved battery disposal route in accordance with all national and local regulations Package used batteries safely for o...

Отзывы: