Technical Support: +44(0)23 9269 6638 (option 3) 

  PAK200546_03A   Mar 2020                       ©2020 ELMDENE INTERNATIONAL LTD  

Fold up ‘Tabs’ to locate 
battery and secure with 
the rubber band supplied 

Fold up ‘Tabs’ to locate 
battery and secure with the 
rubber band supplied 

         

                             

 

 
 
 
 

            Fig 4   GEN3-18-B 

 

      

               Fig 5   GEN3-08-B 

 

   

      

                        

 

 
 
 

            Fig 6   GEN3-18-C 

 

 

               Fig 7   GEN3-08-C 

 

14)

 

Apply mains power. 

Check that Green Mains LED is ON. 
Check there is no fault indicated by the Red Fault LED, refer to diagnostic table on page 7. 

15)

 

Disconnect mains power. 

Check that the battery continues to supply voltage and current to the output load. 
Check that Green Mains LED is OFF and the control panel displays a Loss of Mains (EPS) fault 

NOTE:

 The battery must have sufficient charge to supply the output load 

16)

 

Reconnect mains power. 

Check that Green LED is ON. 

17)

 

Disconnect battery. 

Check that Red Fault LED is indicating a fault, refer to diagnostic table on page 7, and that the 
control panel is showing an APS fault. 

18)

 

Reconnect battery. 

Check there is no fault indicated by the Red Fault LED, refer to diagnostic table on page 7, and 
that the control panel is not showing an APS fault. 

19)

 

Remove Output fuse. 

Check that Red Fault LED is indicating a fault, refer to diagnostic table on page 7, and that the 
control panel shows a General PSU fault. 

20)

 

Replace Output fuse. 

Check that Red Fault LED is OFF  
Check that EPS, APS and GEN Fault signals (if connected) are cleared at the control panel. 

Battery 

Battery 

Battery 

Fold up ‘Tabs’ to locate 
battery and secure with 
the rubber band supplied 

Fold up ‘Tabs’ to locate 
battery and secure with 
the rubber band supplied 

Battery 

Содержание GEN3-08-y

Страница 1: ...a false loss of mains alarm Two LEDs assist with quick and easy installation by showing presence of mains correct battery charging or a fault condition Comprehensive protection is built in as standar...

Страница 2: ...to 40 C operating 75 RH non condensing 20 to 80 C storage Installation environment Intended for internal indoor installation only Standby Battery Management Warning risk of explosion if incorrect bat...

Страница 3: ...T Relay output for mains fail Open if loss of mains GEN FAULT Relay output for General Fault Open in fault condition BATT Connection to standby battery Use cables provided Observe polarity APS FAULT R...

Страница 4: ...supplied ferrite 1 turn and attach to terminal block note polarity Fasten with cable ties Fig 2 Position of ferrite 9 Apply mains power Check Green Mains LED is ON NOTE Red Fault LED may flash to indi...

Страница 5: ...ent charge to supply the output load 16 Reconnect mains power Check that Green LED is ON 17 Disconnect battery Check that Red Fault LED is indicating a fault refer to diagnostic table on page 7 and th...

Страница 6: ...ews supplied 23 With the unit mounted on the wall check that the rear tamper is not in a position that will affect its operation for example over a mortar course recess or raised area on the wall Chec...

Страница 7: ...with a view to periodic replacement of the battery DIAGNOSTICS Local Diagnostics Green LED On Mains Present Red LED Fault Diagnostics according to table Red LED fault Green LED mains Status OFF ON No...

Страница 8: ...of the product any batteries must be removed and disposed separately via an appropriate approved battery disposal route in accordance with all national and local regulations Package used batteries saf...

Отзывы: