background image

 

 

Technical Support: +44(0)23 9269 6638 (option 3) 

  PAK200546_03A   Mar 2020                       ©2020 ELMDENE INTERNATIONAL LTD  

 

S

PECIFICATION

 

 

 

Mains Input 

Rated Voltage / (Operational Voltage) 

100-240Vac / (90 – 265Vac) 

Frequency  

50/60Hz 

Input current 

GEN3-08 

GEN3-18 < 1.0A 

at full load 

Fuse 

T2A 20mm HRC 

 

Output 

 

GEN3-08-y 

GEN3-18-y 

Voltage at full load 

 

Mains power 

 

Battery standby 

 
 

13.2 –14.2Vdc (13.8Vdc nominal) 

 

9.8 – 13.0Vdc  

Ripple 

<400mV pk – pk max @ Rated Voltage 

Fuse: 

 

Load 

 

Battery 

F1.0A 
F1.0A 

F1.6A 
F1.6A 

Continuous Output Current

*

 

 

Mains  

 

Battery for 12 hours 

                     30 hours 
                     60 hours 

 

1.0 A 

0.60A with 8Ah Battery 
0.26A with 8Ah Battery 
0.13A with 8Ah Battery 

 

1.5A 

1.5A with 18Ah Battery 
0.6A with 18Ah Battery 
0.3A with 18Ah Battery 

*See below for quiescent current of PSU under battery when calculating total system standby current resources.

 

 

Mechanical 

Product Reference 

GEN3-08-A 

GEN3-08-B 
GEN3-18-B 

GEN3-08-C 
GEN3-18-C 

Enclosure Dimensions

 w x h x d (mm) 

230 x 200 x 80 

355 x 330 x 80 

330x 275 x 80 

Weight (kg)

 excluding battery 

2.0 

4.0 

3.3 

Material  

1.2mm steel white powder coated 

 

Environmental  

Temperature  

-10 to +40°C (operating) 75% RH non-condensing  

 

-20 to +80°C (storage) 

Installation environment: 

Intended for internal / indoor installation only. 

 

Standby Battery Management              

Warning: risk of explosion if incorrect battery type fitted 

 

Maximum Battery Size 

GEN3-08:  8 Ah 12V Valve Regulated Lead Acid 

(Not supplied with unit) 

GEN3-18:  18Ah 12V Valve Regulated Lead Acid 

 

Intelligent Battery Recharge Time:  

< 24 hours to 80% - If a heavily discharged battery, having a 
terminal voltage > 9.0V, is connected the PSU will attempt to 
charge it. If battery fails to accept charge in 24 hours it will fail 
the active load test. 

Minimum energy level: 

(EN50131-6_2017 §6.0 ref. y’) Percentage of SD (battery) rated 
capacity available to support the load = 100% (8Ah or 18Ah) 

 

Testing: 

Battery not Present: <9.0V battery voltage 

 

Low battery voltage: <11.6V (no mains present) 

 

Active load test at full rated output current 

 

Protection: 

Reverse battery connection protection 

 

Overvoltage protection - Trips at 125% of rated O/P voltage 
Deep discharge protection - Battery disconnect at 10.5V battery 
terminal voltage 

 

Quiescent Current: 

64mA when running on battery - less than 1mA after deep 
discharge protection. 

Battery Cold Start (BCS) 

Momentarily link BCS pins together to connect battery to load if 
PSU commissioned without any mains 

Содержание GEN3-08-y

Страница 1: ...a false loss of mains alarm Two LEDs assist with quick and easy installation by showing presence of mains correct battery charging or a fault condition Comprehensive protection is built in as standar...

Страница 2: ...to 40 C operating 75 RH non condensing 20 to 80 C storage Installation environment Intended for internal indoor installation only Standby Battery Management Warning risk of explosion if incorrect bat...

Страница 3: ...T Relay output for mains fail Open if loss of mains GEN FAULT Relay output for General Fault Open in fault condition BATT Connection to standby battery Use cables provided Observe polarity APS FAULT R...

Страница 4: ...supplied ferrite 1 turn and attach to terminal block note polarity Fasten with cable ties Fig 2 Position of ferrite 9 Apply mains power Check Green Mains LED is ON NOTE Red Fault LED may flash to indi...

Страница 5: ...ent charge to supply the output load 16 Reconnect mains power Check that Green LED is ON 17 Disconnect battery Check that Red Fault LED is indicating a fault refer to diagnostic table on page 7 and th...

Страница 6: ...ews supplied 23 With the unit mounted on the wall check that the rear tamper is not in a position that will affect its operation for example over a mortar course recess or raised area on the wall Chec...

Страница 7: ...with a view to periodic replacement of the battery DIAGNOSTICS Local Diagnostics Green LED On Mains Present Red LED Fault Diagnostics according to table Red LED fault Green LED mains Status OFF ON No...

Страница 8: ...of the product any batteries must be removed and disposed separately via an appropriate approved battery disposal route in accordance with all national and local regulations Package used batteries saf...

Отзывы: