  PAK200546_03A   Mar 2020                       ©2020 ELMDENE INTERNATIONAL LTD  

 

O

PERATING 

I

NSTRUCTIONS

 

 

In the event of loss of mains, a battery fault or a GEN fault, the corresponding Fault signal contacts will open. 

If the output of the PSU fails, the cause of the failure should be investigated e.g. short circuit load, 
connection of a deeply discharged battery. The fault should be rectified before restoring power to the PSU. If 
any of the fuses require replacing, ensure the correct fuse rating and type is used.  
 

M

AINTENANCE

   

This unit is intended for use by Service Personnel only.  There are NO USER SERVICEABLE parts inside. 

There is no regular maintenance required of the PSU other than periodic testing, and replacement of the 
standby battery.  

Reference should be made to the battery manufacturer's documentation to determine 

typical/expected battery life with a view to periodic replacement of the battery.  

 

D

IAGNOSTICS

 

 

Local Diagnostics 

Green LED 

On = Mains Present 

Red LED 

Fault Diagnostics according to table: 

 

Red LED 

(fault) 

Green LED 

(mains) 

Status 

OFF 

ON 

Normal:

  Battery fully charged 

One short flash 

every second 

ON 

Normal:

  Battery charging but not fully charged 

Flashing: 

1second On 

1 second Off 

ON 

Fault:

  Output fuse or battery fuse blown, or 

battery/PSU fault 

OFF 

Fault:

  No mains, output fuse blown 

One short flash 

every 3 seconds 

OFF 

Fault:

  No mains, battery supplying load. 

OFF 

OFF 

Fault:

  No mains, No output, battery disconnected 

or completely discharged 

 

C

OMPLIANCE

 

 

This power supply unit meets the essential requirements of the following EU Directives: 
 

EMC: 2014/30/EU 

Low Voltage: 2014/35/EU 

WEEE: 2012/19/EU 

RoHS2: 2011/65/EU 

 
This product is suitable for use in systems designed to comply with 

PD6662:2017 at Grade 3 and Environmental Class II 

 
EN50131-6:2017  

 

Type A Security Grade 3 

 

 

 

Environmental Class II  

 
Certification Body: 

 

Telefication B.V. 

 

 

 

Edisonstraat 12A 

 

 

 

Zevenaar, 6902 PK 

 

 

 

The Netherlands 

 

 

 

+31 (0) 316 - 583 180 

 

 

 

http://www.telefication.com

 

Содержание GEN3-08-y

Страница 1: ...a false loss of mains alarm Two LEDs assist with quick and easy installation by showing presence of mains correct battery charging or a fault condition Comprehensive protection is built in as standar...

Страница 2: ...to 40 C operating 75 RH non condensing 20 to 80 C storage Installation environment Intended for internal indoor installation only Standby Battery Management Warning risk of explosion if incorrect bat...

Страница 3: ...T Relay output for mains fail Open if loss of mains GEN FAULT Relay output for General Fault Open in fault condition BATT Connection to standby battery Use cables provided Observe polarity APS FAULT R...

Страница 4: ...supplied ferrite 1 turn and attach to terminal block note polarity Fasten with cable ties Fig 2 Position of ferrite 9 Apply mains power Check Green Mains LED is ON NOTE Red Fault LED may flash to indi...

Страница 5: ...ent charge to supply the output load 16 Reconnect mains power Check that Green LED is ON 17 Disconnect battery Check that Red Fault LED is indicating a fault refer to diagnostic table on page 7 and th...

Страница 6: ...ews supplied 23 With the unit mounted on the wall check that the rear tamper is not in a position that will affect its operation for example over a mortar course recess or raised area on the wall Chec...

Страница 7: ...with a view to periodic replacement of the battery DIAGNOSTICS Local Diagnostics Green LED On Mains Present Red LED Fault Diagnostics according to table Red LED fault Green LED mains Status OFF ON No...

Страница 8: ...of the product any batteries must be removed and disposed separately via an appropriate approved battery disposal route in accordance with all national and local regulations Package used batteries saf...

Отзывы: