NSTALLATION AND
S
ET
-U
P
CONTINUED
Standby Battery - NOTE: Ensure batteries fitted to this unit are in good condition
10)
Connect battery to terminal block using minimum 32/0.2 (1.0mm
2
CSA) stranded wire.
NOTE:
ensure correct polarity of battery connections.
Maximum recommended total battery lead length = 500mm
11)
Apply mains power. Check Green Mains LED is on.
12)
Check there is no fault indication on Yellow LED.
13)
Disconnect mains power. Check that the batteries continue to supply voltage and current to the load.
The Green LED should be off.
NOTE
: Batteries must have sufficient charge to supply the load
14)
Reconnect mains power. Green LED should be on.
15)
Remove Load fuse and check Yellow Fault LED is on.
16)
Replace Load fuse. Check Yellow Fault LED is off.