I

NSTALLATION AND 

S

ET

-U

P

 

CONTINUED

 

 

Standby Battery - NOTE: Ensure batteries fitted to this unit are in good condition 

10)

 

Connect  battery  to  terminal  block  using  minimum  32/0.2  (1.0mm

2

  CSA)  stranded  wire. 

NOTE:

 ensure correct polarity of battery connections. 

Maximum recommended total battery lead length = 500mm 

11)

 

Apply mains power. Check Green Mains LED is on. 

12)

 

Check there is no fault indication on Yellow LED. 

13)

 

Disconnect mains power. Check that the batteries continue to supply voltage and current to the load. 
The Green LED should be off.

 

NOTE

: Batteries must have sufficient charge to supply the load 

14)

 

Reconnect mains power. Green LED should be on. 

15)

 

Remove Load fuse and check Yellow Fault LED is on. 

16)

 

Replace Load fuse. Check Yellow Fault LED is off. 

 

 

Module Dimensions 

 

 

50

1

9

124

5

2

114

R

5

4

0

,5

1

6

8

4

 

G2401NU 

Содержание G240xNU

Страница 1: ...mode design ensures low operating costs while generating less heat The modular construction simplifies maintenance Universal mains input voltage 90 264vac Additional 0 5A to charge 2 x 12V standby bat...

Страница 2: ...cuit removed under mains power only Local Indicators MAINS LED Green Mains present FAULT LED Yellow Fault present Output or battery fuse fail requires load battery to be connected loss of mains output...

Страница 3: ...ly mounted within a robust enclosure having suitable means to prevent unintentional access to the module Suitable notices must be affixed to the outside of the enclosure to warn of high voltages prese...

Страница 4: ...recommended total battery lead length 500mm 11 Apply mains power Check Green Mains LED is on 12 Check there is no fault indication on Yellow LED 13 Disconnect mains power Check that the batteries con...

Страница 5: ...5 Technical Support 44 0 23 9269 6638 option 3 PAK200566_01B 2016 ELMDENE INTERNATIONAL LTD 128 98 42 4 60 51 84 152 106 12 4 19 13 G2402NU 157 128 7 5 128 42 4 19 60 56 5 4 135 143 12 G2403NU G2405NU...

Страница 6: ...tput of the PSU fails the cause of the failure should be investigated e g short circuit load The fault should be rectified before restoring power to the PSU The fuses may need to be replaced Ensure th...

Страница 7: ...7 Technical Support 44 0 23 9269 6638 option 3 PAK200566_01B 2016 ELMDENE INTERNATIONAL LTD This page has been left blank intentionally...

Страница 8: ...Before disposal of the product the standby battery must be removed and disposed separately via an appropriate approved battery disposal route in accordance with all national and local regulations Pack...

Отзывы: