background image

2

 

 

Technical Support: +44(0)23 9269 6638 (option 3) 

 

PAK200566_01B                            ©2016 ELMDENE INTERNATIONAL LTD  

 

S

PECIFICATION

 

 

Input Specification   

Voltage (rated) 

100-240Vac 

Voltage (operating) 

90-264Vac 

Frequency  

50-60Hz 

Max Current 

See Model Specification Table  

Mains Input Fuse 

See Model Specification Table 

Max standby Power 

0.8W (no load and no battery connected) 

Output Specification 

Voltage 

27.0 – 28.0Vdc (27.6vdc nominal) on mains power 
21.0 – 24.7Vdc on battery standby 

Max load current 

See Model Specification Table 

Ripple 

100 mV pk-pk max 

Load output Fuse 

See Model Specification Table below 

Overload 

Electronic shutdown until overload or short circuit removed 
(under mains power only)  

Local Indicators 

MAINS LED (Green)  

Mains present  

FAULT LED (Yellow) 

Fault present: Output or battery fuse fail (requires load & 
battery to be connected), loss of mains, output short circuit 
or low output voltage. 

 

 

Standby Batteries 

 

Battery Type 

2 x 12V Valve Regulated Lead Acid 

Battery Charging Fuse protection 

F630mA 20mm glass 

Mechanical  

Model 

G2401NU 

G2402NU 

G2403NU / G2405NU 

Module Dimensions  
w x h x d (mm / external)

 

134 x 84 x 42 

152 x 106 x 52 

157 x 143 x 55 

Recommended Batteries 

2 x 12V NP7 or NP17 

Weight

 

G2401NU 

G2402NU 

G2403NU / G2405NU 

240g 

280g 

650g 

Environmental  

Temperature  

-10 to +40°C (operating) 95% RH non-condensing 
-20 to +80°C (storage) 

Connections  

+O/P 

+ve voltage O/P to load equipment   

-O/P 

-ve voltage O/P to load equipment   

+BATT 

Red lead to standby battery 1 

-BATT 

Black lead to standby battery 2 

Содержание G240xNU

Страница 1: ...mode design ensures low operating costs while generating less heat The modular construction simplifies maintenance Universal mains input voltage 90 264vac Additional 0 5A to charge 2 x 12V standby bat...

Страница 2: ...cuit removed under mains power only Local Indicators MAINS LED Green Mains present FAULT LED Yellow Fault present Output or battery fuse fail requires load battery to be connected loss of mains output...

Страница 3: ...ly mounted within a robust enclosure having suitable means to prevent unintentional access to the module Suitable notices must be affixed to the outside of the enclosure to warn of high voltages prese...

Страница 4: ...recommended total battery lead length 500mm 11 Apply mains power Check Green Mains LED is on 12 Check there is no fault indication on Yellow LED 13 Disconnect mains power Check that the batteries con...

Страница 5: ...5 Technical Support 44 0 23 9269 6638 option 3 PAK200566_01B 2016 ELMDENE INTERNATIONAL LTD 128 98 42 4 60 51 84 152 106 12 4 19 13 G2402NU 157 128 7 5 128 42 4 19 60 56 5 4 135 143 12 G2403NU G2405NU...

Страница 6: ...tput of the PSU fails the cause of the failure should be investigated e g short circuit load The fault should be rectified before restoring power to the PSU The fuses may need to be replaced Ensure th...

Страница 7: ...7 Technical Support 44 0 23 9269 6638 option 3 PAK200566_01B 2016 ELMDENE INTERNATIONAL LTD This page has been left blank intentionally...

Страница 8: ...Before disposal of the product the standby battery must be removed and disposed separately via an appropriate approved battery disposal route in accordance with all national and local regulations Pack...

Отзывы: