4
Technical Support: +44(0)23 9269 6638 (option 3)
PAK200567_01B ©2016 ELMDENE INTERNATIONAL LTD
E
N
L
20m m
2
0
m
m
2)
The G2401BMU and G2402BMU modules have the option of either being DIN rail mounted (using the
integrated DIN rail mount) or by using appropriate fixings using the four available mounting lugs. The
G2403BMU and G2405BMU modules are fixed using the three available mounting points.
I
NSTALLATION AND
S
ET
-U
P
CONTINUED
Mains Power Up
3)
Attach correctly rated mains cable (minimum 0.5mm
2
[3A], 300/500Vac) and secure in enclosure using
cable ties.
4)
Apply mains power. Check for 27.6Vdc on load outputs. Check Green Mains LED is on.
5)
Disconnect mains power.
Load Output
6)
Attach correctly rated load cable and secure in enclosure using cable ties. Note polarity.
7)
Apply mains power. Check green Mains LED is on.
8)
NOTE:
Yellow Fault LED may flash to indicate no battery has been connected; this is normal.
9)
Verify load is operating correctly.
10)
Disconnect mains power.
Signalling Outputs
11)
Connect EPS and GEN fault outputs to appropriate inputs of control equipment.
Standby Battery
12)
Connect battery to terminal block using minimum 32/0.2 (1.0mm
2
CSA) stranded wire.
NOTE:
ensure correct polarity of battery connections. Maximum recommended total battery lead
length = 500mm
13)
Apply mains power. Check Green Mains LED is ON. Check Orange Charging LED is ON.
14)
Check there is no fault indication on Yellow LED.
15)
Disconnect mains power. Check that the batteries continue to supply voltage and current to the load.
Check Green Mains LED is OFF and the control panel displays a Loss of Mains (EPS) fault
NOTE
: Batteries must have sufficient charge to supply the load
16)
Reconnect mains power. Green LED should be on.
17)
Remove Load fuse. Check Yellow Fault LED is ON and control panel shows General PSU fault.
18)
Replace Load fuse. Check Yellow Fault LED is OFF and General PSU fault has cleared at control panel.
E
N
L
20m m
2
0
m
m
N
E
L
G2401BMU &G2402BMU
G2403BMU & G2405BMU
N
E
L
L E N
L E N