background image

 

 

Technical Support: +44(0)23 9269 6638 (option 3) 

 

PAK200790_02A Oct 2019                        ©2019 ELMDENE INTERNATIONAL LTD  

C

OMMISSIONING 

 

 

Connecting the mains supply 

11.

 

With no external connections made to the PSE, connect the mains input wires 
to the terminal block, 

ensuring that the mains isolator (disconnect device) is 

open

. Fasten wiring in place with cable tie to the fixing points provided.  

Note: This equipment MUST be earthed.

 

 

12.

 

Apply mains input. Confirm that all LED indicators flash on briefly proving 
integrity of indicators. After the power-on LED sequence confirm that the 
following conditions are met: 

 

LED 

Symbol 

LED Colour

 

Function

 

Mains 

Constant Green 

Indication: Mains supply = OK 

Batt 

Constant Yellow 

Indication: Battery Fault = missing battery indicated

 

Fault 

Yellow FLASH x1 

(repeating) 

Indication: Fault with PSU = due to missing battery 

Diagnostic 

Red FLASH x2 

(repeating) 

Indication: Fault = missing battery indicated 

OP1* 

Constant Green 

Indication: Output 1 = OK 

OP2* 

Constant Green 

Indication: Output 2 = OK 

(See also ‘

Status and Fault-Diagnostic LED Indication

 table for full details of LED indications.) 

13.

 

Disconnect the mains power using the disconnect device. 

 

Connecting the Remote Signalling 

14.

 

Connect the EPS and 
GEN PSU Fault outputs 
to the appropriate inputs 
of CIE 

 

 

EPS Fault 

GEN Fault 

Condition 

Possible Cause 

Action 

(

COM TO N

/

C

C

LOSED

 

(

COM TO N

/

C

)

 

C

LOSED

 

Normal 

operation. 

Mains present. 

Battery healthy. 

None. 

(

COM TO N

/

C

O

PEN

 

(

COM TO N

/

C

C

LOSED

 

Standby Mode. 

Mains lost (> 8 seconds) 

Battery driving load. 

Investigate loss of mains. 

(

COM TO N

/

C

C

LOSED

 

(

COM TO N

/

C

O

PEN

 

Fault Present. 

Blown fuses. 
Battery fault 

Internal fault. 

Investigate fault source using 

diagnostic LED #4. 

Rectify fault where possible. 

(

COM TO N

/

C

O

PEN

 

(

COM TO N

/

C

O

PEN

 

PSU 

Shutdown. 

Mains lost (> 8 seconds) 

Standby battery exhausted. 

Restore mains as soon as possible. 

 

 

Connecting the Load (

with OUTPUT MONITOR jumper fitted

 

15.

 

When monitoring the PSU outputs, the STV can either consider 
the outputs as 2 individual, unrelated loads or will monitor the 
two outputs as a single dual-power transmission path (see 
section 41 for DUAL-PATH monitoring). With the OUTPUT 
MONITOR jumper fitted, the outputs are considered as two 
individual loads. 

 

Mains 

Input 

Load 

Outputs 

Battery 

Connection 

GEN & EPS 

Relay Outputs 

‘No battery’ 

Select 

Unit Addr 

Select 

RS485 

Link 

Temp Probe 

Inputs 

OP2 

Fuse 

PTC Battery 

Fuse 

OP1 ≠ OP2

 

Select 

 

LED Status 

Indicators 

 

Charger 

Setting 

OP1 

Fuse 

Mains  

Fuse 

 

FAULT RELAY STATES

COM / NO / NC

HEALTHY

COM / NO / NC

FAULT

 

GEN

EPS

COM  / NO/  NC

COM  / NO/  NC

 

Relay Rating: 1A @ 30V dc (60V dc max), Volt-free, change-over (SPDT) form C 

+

+

-

- + -

2x LOAD 

OUTPUTS

T

T

M A INS FUSE

GEN

EPS

FAULT OUTPUTS

FUSE  #1

FUSE  #2

-

LOAD OUTPUT

+

LO AD 1

-

+

LO AD 2

 

Содержание 2401ST

Страница 1: ...ion remote fault signalling Load connection 5 Installation cont Battery Charger settings 6 Installation cont Battery installation Battery compatibility 7 Installation cont Battery installation Final c...

Страница 2: ...HF Current Limitation Short circuit protection From In to In 15 for an output voltage 50 Un Fuse Load OP1 and OP2 F1 0 A IEC 60127 2 type Battery Charging Constant current bulk charging to 80 capacit...

Страница 3: ...ns 3 Where the PSE is used for other applications it should be installed according to all relevant safety regulations applicable to that application Cable Sizing 4 Mains input cable must be to the app...

Страница 4: ...isconnect device Connecting the Remote Signalling 14 Connect the EPS and GEN PSU Fault outputs to the appropriate inputs of CIE EPS Fault GEN Fault Condition Possible Cause Action COM TO N C CLOSED CO...

Страница 5: ...to n c CLOSED contact and the GEN PSU Fault monitor shows an com to n c OPEN contact 20 Perform a full functional test of the connected system load including full alarm condition then disconnect the...

Страница 6: ...SE and CIE in separate enclosures is used all cabling between the two boxes should be routed to use separate case entry exit holes from other cabling using suitable cable glands to protect the cables...

Страница 7: ...w Fault LED 3 starts to flash indicating that the PSE is running from its standby batteries 32 If connected verify that the EPS Fault output shows an open contact com and n c terminals open circuit an...

Страница 8: ...with the battery leads Continue to observe caution with all exposed conductors when inserting or removing the meter and when restoring normal battery wiring 40 Close cover and secure using fastening...

Страница 9: ...se Action GREEN YELLOW Fast Flash Battery in process of connecting Battery connecting No action Wait for battery connection to complete GREEN Flash x1 Normal operation Battery connected Battery in bul...

Страница 10: ...charger Return to manufacturer RED Flash x5 Battery Temperature Probe Fault Battery temperature monitor disconnected or damaged PSU running in Safe Mode Check temperature sensor connections and condi...

Страница 11: ...This product falls within the scope of EU Directives 2012 19 EU Waste Electrical and Electronic Equipment WEEE and 2013 56 EU Battery At the end of life the product must be separated from the domestic...

Страница 12: ...A2 EN12101 10 2005 Environmental Class I Equipment Class A Suitable for all systems VdS 2541 1996 12 Environmental Class III Certification Bodies AFNOR CNPP VdS Declaration of Performance DOP2018 020...

Страница 13: ...ezifikation des Netzteils 3 Installation Netzeinspeisung Kabelquerschnitt Montagegeh use 4 Installation Forts Netzanschluss Fernfehlermeldung Lastanschluss 5 Installation Forts Einstellungen des Batte...

Страница 14: ...ung HF Strombegrenzung Kurzschlussschutz Von In bis In 15 f r eine Ausgangsspannung 50 Un Sicherung Last OP1 und OP2 F 1 0 A Typ IEC 60127 2 Aufladen der Batterie Aufladen mit konstantem Ladestrom Vol...

Страница 15: ...ndungen eingesetzt wird sollte sie gem allen f r diese Anwendungen relevanten Sicherheitsvorschriften installiert werden Kabelquerschnitt 4 Das Netzkabel muss dem geltenden Standard entsprechen und ei...

Страница 16: ...P1 Konstant gr n Anzeige Ausgang 1 OK 6 OP2 Konstant gr n Anzeige Ausgang 2 OK F r vollst ndige Details der LED Anzeigen siehe auch Tabelle LED Anzeige f r Status und Fehlerdiagnose 13 Trennen Sie die...

Страница 17: ...hlender Batterie 4 Diagnose Rot BLINKEND x2 wiederholt Anzeige Fehler fehlende Batterie wird angezeigt 5 OP1 Konstant gr n Anzeige Ausgang 1 OK 6 OP2 Konstant gr n Anzeige Ausgang 2 OK 19 Wenn angesch...

Страница 18: ...r jede Batterieoption 24 Stellen Sie sicher dass alle Batterieklemmen ausreichend isoliert sind um ein unbeabsichtigtes Kurzschlie en untereinander oder mit den Metallteilen des Geh uses zu verhinder...

Страница 19: ...lossen werden Dies wird jedoch NICHT EMPFOHLEN da dies auf besch digte Batterien hindeuten k nnte Um Batterien bis zu einer Spannung von 19V anzuschlie en trennen Sie vorsichtig einen wei en Temperatu...

Страница 20: ...als 1 Minute die folgenden Bedingungen erf llt sind LED Symbol Gr n EIN Funktion 1 Batt Konstant gelb Anzeige Batteriefehler fehlende Batterie wird angezeigt 2 Fehler Gelb blinkend x1 wiederholt Anzei...

Страница 21: ...ladenen Batterie Der Fehler sollte behoben werden bevor die Stromversorgung der PSE wiederhergestellt wird Wenn eine der Sicherungen ausgetauscht werden muss stellen Sie sicher dass die richtige Siche...

Страница 22: ...2 Zustand M gliche Ursache Ma nahme GR N GELB Schnelles Blinken Batterie wird gerade angeschlossen Batterieanschluss Keine Ma nahme Warten bis die Batterieverbindung abgeschlossen ist GR N blinkend x...

Страница 23: ...ehler des Batterietemperaturf hlers berwachungsger t der Batterietemperatur nicht angeschlossen oder besch digt Netzteil l uft im abgesicherten Modus Anschl sse des Temperatursensors und Zustand des S...

Страница 24: ...et Netzspannung Ausgang1 Spannung Strom Ausgang2 Spannung Strom Batteriespannung Strom des Ladeger ts GEN Fehlerzustand EPS Fehlerzustand Diagnose Fehlerstatus Zustand 1 6 Batterietemperatur Status de...

Страница 25: ...der Quecksilber Hg beinhalten Weitere Informationen finden Sie unter www recyclethis info Die mit diesem Produkt gelieferte Verpackung kann recycelt werden Bitte entsorgen Sie die Verpackung entsprech...

Отзывы: