Technical Support: +44(0)23 9269 6638 (option 3) 

 

PAK200790_02A Oct 2019                        ©2019 ELMDENE INTERNATIONAL LTD  

S

PEZIFIKATION

 

 

 
Netzanschluss 

Nennspannung/Leistung 
 
(Betriebsspannung) 

230 V AC/60 W @ In = 2,5 A Nennausgangsstrom 
                                Un = 24 V Nennausgangsspannung  
(195 V AC

265 V AC) 

Frequenz 
Eingang 
Schaltfrequenzbereich 

 
50 Hz nominal 
ca. 20 kHz

125 kHz, abhängig von der Last. 

Eingangsstrom 

< 1,0 A bei Volllast 

Einschaltstrom 

5 A max. bei 25 °C 230 V AC für 10 ms 

Sicherung 

T2,0 A 20 mm, 250 V AC HRC (Typ IEC 60127-2) 

Erde/Neutralsystem 

TN & TT 

PSU (Power Supply Unit) = Netzteil (STV2401), PSE (Power Supply Equipment) = Stromversorgungseinrichtung (Netzteil im Metallgehäuse 
komplett mit Batterien 

 STV2401-x),  

CIE (Control and Indicating Equipment) = Steuer- und Anzeigegeräte (z. B. eine Brandmeldezentrale). 

PSU Ausgangs- 

Spannung 

an der Netzspannung  

(bei Volllast)  

21,6 V DC (Umin)* 

 28,8 V DC (Umax)* 

/

 ** 

Un* = 24,0 V DC +/- 3 % bei 25 °C 

Spannung 

im Batterie-

Bereitschaftsmodus 
(bei Volllast)

 

21,6 V DC

26,0 V DC 

Dauerausgangsstrom 

Keine Aufladung (

Imax B

Mit Aufladung EN54-4 (

Imax A

)

 

1,35 A 

Variiert 

 siehe Abschnitt 20 

Ripple 

< 100 mV s-s max. @ Nennspannung (HF) 

Strombegrenzung 

  Kurzschlussschutz 

Von In* bis In+ 15 % für eine Ausgangsspannung < 50 % Un* 

Sicherung  

Last (OP1 und OP2) 

F 1,0 A (Typ IEC 60127-2) 

Aufladen der Batterie 

Aufladen mit konstantem Ladestrom (Volllastladung) auf 80 % der Kapazität innerhalb 
von 24 Stunden Erhaltungsladung auf 100 % innerhalb von 48 Stunden mit 
überwachter ECO-Aufladung 

Batteriespannung

 

Schwellenspannung für niedrige 
Batteriespannung 
Tiefentladeschutz 

 

23,2 V (gemessen an der Batterie) 

21,6 V (Minimum, gemessen am Ausgang des Netzteils) 

Ruhestrom 

  Ohne Last 
  Bei Batterieabschaltung

 

 

< 60 mA 

< 180 µA  

  

*    Umin/Umax/Un = Maximum/Minimum 

**  Umax wird beim Anschluss der Batterie um ca. +1 % von Un erhöht. Umax = 28,8 V zu allen anderen Zeiten

Mechanisch 

Produktbezeichnung 

STV2401-T 

STV2401-C 

Gehäuseabmessungen 

 H x B x T (mm) 

300 x 240 x 60 

275 x 330 x 80 

Gewicht (kg)

 ohne Batterie 

                       Mit Batterie

 

3,0 kg 

~5 kg/6 kg 

3,0 kg 

~5 kg/9 kg 

Batteriekapazität (2 x 12 V VRLA) 

1,2 Ah/2,1 Ah 

7 Ah 

Material  

1,2 mm Stahl weiß pulverbeschichtet 

 

Umgebung  

Betriebstemperatur 

-10 bis +40 °C (Betrieb) 75 % RH nicht kondensierend 

Lagertemperatur 

-20 bis +80 °C (Lagerung) 

Gehäuseschutzklasse 

IP30 

 

Dieses Netzteil (PSU) ist nur für die Installation als fest angeschlossenes Gerät (Stromversorgungseinrichtung/PSE) geeignet.   
Die PSE EIGNET SICH NICHT für die externe Installation.

 

Содержание 2401ST

Страница 1: ...ion remote fault signalling Load connection 5 Installation cont Battery Charger settings 6 Installation cont Battery installation Battery compatibility 7 Installation cont Battery installation Final c...

Страница 2: ...HF Current Limitation Short circuit protection From In to In 15 for an output voltage 50 Un Fuse Load OP1 and OP2 F1 0 A IEC 60127 2 type Battery Charging Constant current bulk charging to 80 capacit...

Страница 3: ...ns 3 Where the PSE is used for other applications it should be installed according to all relevant safety regulations applicable to that application Cable Sizing 4 Mains input cable must be to the app...

Страница 4: ...isconnect device Connecting the Remote Signalling 14 Connect the EPS and GEN PSU Fault outputs to the appropriate inputs of CIE EPS Fault GEN Fault Condition Possible Cause Action COM TO N C CLOSED CO...

Страница 5: ...to n c CLOSED contact and the GEN PSU Fault monitor shows an com to n c OPEN contact 20 Perform a full functional test of the connected system load including full alarm condition then disconnect the...

Страница 6: ...SE and CIE in separate enclosures is used all cabling between the two boxes should be routed to use separate case entry exit holes from other cabling using suitable cable glands to protect the cables...

Страница 7: ...w Fault LED 3 starts to flash indicating that the PSE is running from its standby batteries 32 If connected verify that the EPS Fault output shows an open contact com and n c terminals open circuit an...

Страница 8: ...with the battery leads Continue to observe caution with all exposed conductors when inserting or removing the meter and when restoring normal battery wiring 40 Close cover and secure using fastening...

Страница 9: ...se Action GREEN YELLOW Fast Flash Battery in process of connecting Battery connecting No action Wait for battery connection to complete GREEN Flash x1 Normal operation Battery connected Battery in bul...

Страница 10: ...charger Return to manufacturer RED Flash x5 Battery Temperature Probe Fault Battery temperature monitor disconnected or damaged PSU running in Safe Mode Check temperature sensor connections and condi...

Страница 11: ...This product falls within the scope of EU Directives 2012 19 EU Waste Electrical and Electronic Equipment WEEE and 2013 56 EU Battery At the end of life the product must be separated from the domestic...

Страница 12: ...A2 EN12101 10 2005 Environmental Class I Equipment Class A Suitable for all systems VdS 2541 1996 12 Environmental Class III Certification Bodies AFNOR CNPP VdS Declaration of Performance DOP2018 020...

Страница 13: ...ezifikation des Netzteils 3 Installation Netzeinspeisung Kabelquerschnitt Montagegeh use 4 Installation Forts Netzanschluss Fernfehlermeldung Lastanschluss 5 Installation Forts Einstellungen des Batte...

Страница 14: ...ung HF Strombegrenzung Kurzschlussschutz Von In bis In 15 f r eine Ausgangsspannung 50 Un Sicherung Last OP1 und OP2 F 1 0 A Typ IEC 60127 2 Aufladen der Batterie Aufladen mit konstantem Ladestrom Vol...

Страница 15: ...ndungen eingesetzt wird sollte sie gem allen f r diese Anwendungen relevanten Sicherheitsvorschriften installiert werden Kabelquerschnitt 4 Das Netzkabel muss dem geltenden Standard entsprechen und ei...

Страница 16: ...P1 Konstant gr n Anzeige Ausgang 1 OK 6 OP2 Konstant gr n Anzeige Ausgang 2 OK F r vollst ndige Details der LED Anzeigen siehe auch Tabelle LED Anzeige f r Status und Fehlerdiagnose 13 Trennen Sie die...

Страница 17: ...hlender Batterie 4 Diagnose Rot BLINKEND x2 wiederholt Anzeige Fehler fehlende Batterie wird angezeigt 5 OP1 Konstant gr n Anzeige Ausgang 1 OK 6 OP2 Konstant gr n Anzeige Ausgang 2 OK 19 Wenn angesch...

Страница 18: ...r jede Batterieoption 24 Stellen Sie sicher dass alle Batterieklemmen ausreichend isoliert sind um ein unbeabsichtigtes Kurzschlie en untereinander oder mit den Metallteilen des Geh uses zu verhinder...

Страница 19: ...lossen werden Dies wird jedoch NICHT EMPFOHLEN da dies auf besch digte Batterien hindeuten k nnte Um Batterien bis zu einer Spannung von 19V anzuschlie en trennen Sie vorsichtig einen wei en Temperatu...

Страница 20: ...als 1 Minute die folgenden Bedingungen erf llt sind LED Symbol Gr n EIN Funktion 1 Batt Konstant gelb Anzeige Batteriefehler fehlende Batterie wird angezeigt 2 Fehler Gelb blinkend x1 wiederholt Anzei...

Страница 21: ...ladenen Batterie Der Fehler sollte behoben werden bevor die Stromversorgung der PSE wiederhergestellt wird Wenn eine der Sicherungen ausgetauscht werden muss stellen Sie sicher dass die richtige Siche...

Страница 22: ...2 Zustand M gliche Ursache Ma nahme GR N GELB Schnelles Blinken Batterie wird gerade angeschlossen Batterieanschluss Keine Ma nahme Warten bis die Batterieverbindung abgeschlossen ist GR N blinkend x...

Страница 23: ...ehler des Batterietemperaturf hlers berwachungsger t der Batterietemperatur nicht angeschlossen oder besch digt Netzteil l uft im abgesicherten Modus Anschl sse des Temperatursensors und Zustand des S...

Страница 24: ...et Netzspannung Ausgang1 Spannung Strom Ausgang2 Spannung Strom Batteriespannung Strom des Ladeger ts GEN Fehlerzustand EPS Fehlerzustand Diagnose Fehlerstatus Zustand 1 6 Batterietemperatur Status de...

Страница 25: ...der Quecksilber Hg beinhalten Weitere Informationen finden Sie unter www recyclethis info Die mit diesem Produkt gelieferte Verpackung kann recycelt werden Bitte entsorgen Sie die Verpackung entsprech...

Отзывы: