Technical Support: +44(0)23 9269 6638 (option 3)             PAK200546-CHUBB_02DC   Feb 2021 

©2021 ELMDENE INTERNATIONAL LTD  

         

                             

 

 
 
 
 

            Fig 4   20182424N 

 

      

               Fig 5   20182423N 

 

 

13)

 

Apply mains power. 

Check that Green Mains LED is ON. 
Check there is no fault indicated by the Red Fault LED, refer to diagnostic table on page 7. 

14)

 

Disconnect mains power. 

Check that the battery continues to supply voltage and current to the output load. 
Check that Green Mains LED is OFF and the control panel displays a Loss of Mains (EPS) fault 

NOTE:

 The battery must have sufficient charge to supply the output load 

15)

 

Reconnect mains power. 

Check that Green LED is ON. 

16)

 

Disconnect battery. 

Check that Red Fault LED is indicating a fault, refer to diagnostic table on page 7, and that the 
control panel is showing an APS fault. 

17)

 

Reconnect battery. 

Check there is no fault indicated by the Red Fault LED, refer to diagnostic table on page 7, and 
that the control panel is not showing an APS fault. 

18)

 

Remove Output fuse. 

Check that Red Fault LED is indicating a fault, refer to diagnostic table on page 7, and that the 
control panel shows a General PSU fault. 

19)

 

Replace Output fuse. 

Check that Red Fault LED is OFF  
Check that EPS, APS and GEN Fault signals (if connected) are cleared at the control panel. 

Battery 

Battery 

Fold up ‘Tabs’ to locate 
battery and secure with 
the rubber band supplied 

Fold up ‘Tabs’ to locate 
battery and secure with the 
rubber band supplied 

Содержание 20182423N

Страница 1: ...tage dips do not create a false loss of mains alarm Two LEDs assist with quick and easy installation by showing presence of mains correct battery charging or a fault condition Comprehensive protection...

Страница 2: ...ng battery 4 0 Material 1 2mm steel white powder coated Environmental Temperature 10 to 40 C operating 75 RH non condensing 20 to 80 C storage Standby Battery Management Warning risk of explosion if i...

Страница 3: ...FAULT Relay output for mains fail Open if loss of mains GEN FAULT Relay output for General Fault Open in fault condition BATT Connection to standby battery Use cables provided Observe polarity APS FAU...

Страница 4: ...oad Output 8 Loop correctly rated load cable through supplied ferrite 1 turn and attach to terminal block note polarity Fasten with cable ties Fig 2 Position of ferrite 9 Apply mains power Check Green...

Страница 5: ...n LED is ON 16 Disconnect battery Check that Red Fault LED is indicating a fault refer to diagnostic table on page 7 and that the control panel is showing an APS fault 17 Reconnect battery Check there...

Страница 6: ...wall Check that the tamper switch is CLOSED when the lid cover is closed and the retaining screws are fitted OPEN when the retaining screws are removed and the lid cover is open Use fine adjustment s...

Страница 7: ...N Normal Battery fully charged One short flash every second ON Normal Battery charging but not fully charged Flashing 1second On 1 second Off ON Fault Output fuse or battery fuse blown or battery PSU...

Страница 8: ...al of the product any batteries must be removed and disposed separately via an appropriate approved battery disposal route in accordance with all national and local regulations Package used batteries...

Отзывы: