Mains Input 

Rated Voltage / (Operational Voltage) 

100-240Vac / (90 – 265Vac) 

Frequency  

50/60Hz 

Input current 

20182423N & 20182424N < 1.0A 

at full load 

Fuse 

T2A 20mm HRC 

 

Output 

 

20182423N 

20182424N 

Voltage at full load 

 

Mains power 

 

Battery standby 

 
 

13.2 –14.2Vdc (13.8Vdc nominal) 

 

9.8 – 13.0Vdc  

Ripple 

<400mV pk – pk max @ Rated Voltage 

Fuse: 

 

Load 

 

Battery 

F1.0A 
F1.0A 

F1.6A 
F1.6A 

Continuous Output Current

*

 

 

Mains  

 

Battery for 12 hours 

                     30 hours 
                     60 hours 

 

1.0 A 

0.60A with 8Ah Battery 
0.26A with 8Ah Battery 
0.13A with 8Ah Battery 

 

1.5A 

1.5A with 18Ah Battery 
0.6A with 18Ah Battery 
0.3A with 18Ah Battery 

*See below for quiescent current of PSU under battery when calculating total system standby current resources. 

 

Mechanical 

Product Reference 

20182423N & 20182424N 

Enclosure Dimensions

 w x h x d (mm) 

355 x 330 x 80 

Weight (kg)

 excluding battery 

4.0 

Material  

1.2mm steel white powder coated 

 

Environmental  

 

Temperature  

 -10 to +40°C (operating) 75% RH non-condensing  

 

 -20 to +80°C (storage) 

 

Standby Battery Management              

Warning: risk of explosion if incorrect battery type fitted 

 

Maximum Battery Size 

20182423N: 8 Ah 12V Valve Regulated Lead Acid 

(Not supplied with unit) 

20182424N: 18Ah 12V Valve Regulated Lead Acid 

Intelligent Battery Recharge Time:  

< 24 hours to 80%  -  A heavily discharged battery having a 
terminal voltage > 9.0V will attempt to be charged. If battery fails 
to accept charge in 24 hours it will fail the active load test. 

Testing: 

Battery not Present: <9.0V battery voltage 

 

Low battery voltage: <11.6V (no mains present) 

 

Active load test at full rated output current 

Protection: 

Reverse battery connection protection 

 

Overvoltage protection - Trips at 125% of rated O/P voltage 
Deep discharge protection - Battery disconnect at 10.5V battery 
terminal voltage 

Quiescent Current: 

64mA when running on battery - less than 1mA after deep 
discharge protection. 

Battery Cold Start (BCS) 

Momentarily link BCS pins together to connect battery to load if 
PSU commissioned without any mains 

Содержание 20182423N

Страница 1: ...tage dips do not create a false loss of mains alarm Two LEDs assist with quick and easy installation by showing presence of mains correct battery charging or a fault condition Comprehensive protection...

Страница 2: ...ng battery 4 0 Material 1 2mm steel white powder coated Environmental Temperature 10 to 40 C operating 75 RH non condensing 20 to 80 C storage Standby Battery Management Warning risk of explosion if i...

Страница 3: ...FAULT Relay output for mains fail Open if loss of mains GEN FAULT Relay output for General Fault Open in fault condition BATT Connection to standby battery Use cables provided Observe polarity APS FAU...

Страница 4: ...oad Output 8 Loop correctly rated load cable through supplied ferrite 1 turn and attach to terminal block note polarity Fasten with cable ties Fig 2 Position of ferrite 9 Apply mains power Check Green...

Страница 5: ...n LED is ON 16 Disconnect battery Check that Red Fault LED is indicating a fault refer to diagnostic table on page 7 and that the control panel is showing an APS fault 17 Reconnect battery Check there...

Страница 6: ...wall Check that the tamper switch is CLOSED when the lid cover is closed and the retaining screws are fitted OPEN when the retaining screws are removed and the lid cover is open Use fine adjustment s...

Страница 7: ...N Normal Battery fully charged One short flash every second ON Normal Battery charging but not fully charged Flashing 1second On 1 second Off ON Fault Output fuse or battery fuse blown or battery PSU...

Страница 8: ...al of the product any batteries must be removed and disposed separately via an appropriate approved battery disposal route in accordance with all national and local regulations Package used batteries...

Отзывы: