2
Technical Support: +44(0)23 9269 6638 (option 3) PAK200546-CHUBB_02DC Feb 2021
©2021 ELMDENE INTERNATIONAL LTD
S
PECIFICATION
Mains Input
Rated Voltage / (Operational Voltage)
100-240Vac / (90 – 265Vac)
Frequency
50/60Hz
Input current
20182423N & 20182424N < 1.0A
at full load
Fuse
T2A 20mm HRC
Output
20182423N
20182424N
Voltage at full load
Mains power
Battery standby
13.2 –14.2Vdc (13.8Vdc nominal)
9.8 – 13.0Vdc
Ripple
<400mV pk – pk max @ Rated Voltage
Fuse:
Load
Battery
F1.0A
F1.0A
F1.6A
F1.6A
Continuous Output Current
*
Mains
Battery for 12 hours
30 hours
60 hours
1.0 A
0.60A with 8Ah Battery
0.26A with 8Ah Battery
0.13A with 8Ah Battery
1.5A
1.5A with 18Ah Battery
0.6A with 18Ah Battery
0.3A with 18Ah Battery
*See below for quiescent current of PSU under battery when calculating total system standby current resources.
Mechanical
Product Reference
20182423N & 20182424N
Enclosure Dimensions
w x h x d (mm)
355 x 330 x 80
Weight (kg)
excluding battery
4.0
Material
1.2mm steel white powder coated
Environmental
Temperature
-10 to +40°C (operating) 75% RH non-condensing
-20 to +80°C (storage)
Standby Battery Management
Warning: risk of explosion if incorrect battery type fitted
Maximum Battery Size
20182423N: 8 Ah 12V Valve Regulated Lead Acid
(Not supplied with unit)
20182424N: 18Ah 12V Valve Regulated Lead Acid
Intelligent Battery Recharge Time:
< 24 hours to 80% - A heavily discharged battery having a
terminal voltage > 9.0V will attempt to be charged. If battery fails
to accept charge in 24 hours it will fail the active load test.
Testing:
Battery not Present: <9.0V battery voltage
Low battery voltage: <11.6V (no mains present)
Active load test at full rated output current
Protection:
Reverse battery connection protection
Overvoltage protection - Trips at 125% of rated O/P voltage
Deep discharge protection - Battery disconnect at 10.5V battery
terminal voltage
Quiescent Current:
64mA when running on battery - less than 1mA after deep
discharge protection.
Battery Cold Start (BCS)
Momentarily link BCS pins together to connect battery to load if
PSU commissioned without any mains