2.1 General Installation Notes

2.2 Wire Size & Breaker

•  Please read the entire installation instructions to get familiar with the installation steps before installation.
•  Be very careful when installing the batteries, especially flooded lead-acid battery. Please wear eye protection, and have  
    fresh water available to wash and clean if any contact with battery acid
•  Keep the battery away from any metal objects, which may cause short circuit of the battery.
•  Explosive acid battery gases may come out from the battery during charging, so make sure ventilation condition is good.   
•  Ventilation is highly recommended if mounted in an enclosure. Never install the controller in a sealed enclosure with   
    flooded batteries! Battery fumes from vented batteries will corrode and destroy the controller circuits.
•  Lead-acid battery is only recommended, other kinds please refer to the battery manufacturer.
•  Loose connections and corroded wires may result in high heat that can melt wire insulation, burn surrounding materials, 
    or even cause fire. Ensure tight connections and use cable clamps to secure cables and prevent them from swaying in 
    motion.
•  Battery connection may be wired to one battery or a bank of batteries. The following instructions refer to a singular 
    battery, but it is implied that the battery connection can be made to either one battery or a group of batteries in a battery 
    bank.
•  Select the system cables according to 5A/mm2 or less current density in accordance with Article 690 of the National 
    Electrical Code, NFPA 70.   
•  For outdoor installation, keep out of the direct sunshine and rain infiltration.   
•  High voltage still exists inside the inverter/charger after switching off the power switch, do not turn on or touch the 
    internal units, conduct the associated operation only after discharging the electric capacity.   
•  Do not place the inverter/charger in a damp, oily, inflammable and explosive or a severe environment with a large amount 
    of dust accumulation.   
•  Prohibit reverse connection at DC input end otherwise it may damage the equipment or unpredictable danger will occur.   
The utility input and AC output are of high voltage, do not touch the wire connetion. 

The wiring and installation methods must  follow all national and local electrical code requirements. 

Recommended wire and circuit breaker of PV

2. Installation Instructions

 

Model

PV wire size  

Breaker

 

FBIC3000VA/24V
FBIC3000VA/48V

FBIC3000VA/24V
FBIC3000VA/48V

FBIC3000VA/24V

FBIC3000VA/48V

10mm

2

/8AWG  

2P— 63A

 

6mm

2

/10AWG  

2P— 32A

 

NOTE: When the PV modules connect in series, the open circuit voltage of the PV array must not exceed max. 
PV input voltage at 250C environment temperature. 

NOTE: The utility input has the circuit breaker already and there is no need to add any more.

NOTE: 

Type of circuit breaker is selected based on non-independent connection of inverter at the battery end 

where there is no antherinverter connected.

Recommended wire of Utility

Recommended wire and circuit breaker of battery

 

Model  

Utility wire size

6mm

2

/10AWG

6mm

2

/10AWG

 

Model

Battery  wire size  

Breaker  

35mm

2

/2AWG  

2P— 200A

16mm

2

/6AWG  

2P— 100A

Содержание FBIC3000VA/24V

Страница 1: ...3000VA Inverter Charger FBIC3000VA 24V FBIC3000VA 48V User Manual Please read this guide carefully before using this product...

Страница 2: ...devices The UPower series is a new type of the inverter charger combining with solar utility charging and AC output which adopts a multi core processor design and advanced MPPT control algorithm and...

Страница 3: ...vanced interface Multiple LED indicators that instantly indicate the operating state of the system 2P circuit breaker provided at the utility input end Independent control of AC output by AC OUT butto...

Страница 4: ...Schematic Diagram for Connections Warning Confirm the AC load power compatible with the power of the inverter charger AC load selected exceeding the maximum output power of inverter charger is prohib...

Страница 5: ...t density in accordance with Article 690 of the National Electrical Code NFPA 70 For outdoor installation keep out of the direct sunshine and rain infiltration High voltage still exists inside the inv...

Страница 6: ...above wire and the circuit breaker size are for recommended use only please choose the suitable wire and circuit breaker according to the practical situation WARNING Risk of explosion Never install th...

Страница 7: ...he thicker wire wire is not less than 4mm2 the grounding point shall be as close as possible to the inverter charger the grounding wire shall be as short as possible AC output Ground and PV wiring ter...

Страница 8: ...d Utility Turn on the AC load when the AC output is normal NOTE The temperature sensor short circuited or damaged the inverter charger will be charging or discharging at the default temperature 250C N...

Страница 9: ...t On Solid Load output Green OFF Relay turn off On Solid Relay turn on Green OFF Inputvoltage 3 3 12VDC On Solid No Inputvoltage Green OFF Inverter output On Solid Utility output Red OFF Device normal...

Страница 10: ...ace 9 Icon instruction Icon instruction Utility connected PV connected No Utility No PV Load ON Load OFF Battery capacity level 8 25 Battery capacity level25 50 Battery capacity level 50 75 Battery ca...

Страница 11: ...Battery Type AGW GEL FLD USER INPUT Solar priority The battery is charged in solar priority modeand when the battery voltage is lower than Auxiliary Module ON Voltage VAON the utility starts charging...

Страница 12: ...on again for confirmaton Step 4 Press the button to exit the setting interface Setting Item LCD Instruction Default Range 1 BTP Battery type AGM AGM GEL FLD USER 2 CSP Charge source priority Solar pri...

Страница 13: ...module ON voltage 28 0VDC User 24 0 29 6VDC Step size 0 2VDC 16 AON 24 0 VDC 17 DON 22 2 VDC User 21 6 24 0VDC Step size 0 2VDC 18 DOF Dry connect OFF voltage Dry connect ON voltage 24 0 VDC User 24 0...

Страница 14: ...is energized and the switch is turned on The dry contact can drive resistive loads 125VAC 1A 30VDC 1A NOTE When the utility input is abnormal this dry contact can control the generator switch to char...

Страница 15: ...the set point of Low Voltage Disconnect Voltage the controller will stop discharging the battery to protect the battery from being over discharged to break down Load Output Short Circuit Load Output O...

Страница 16: ...vironment Make sure no block on air flow around the inverter charger Clear up any dirt and fragments on radiator Check all the naked wires to make sure insulation is not damaged for serious solarizati...

Страница 17: ...me 20mS Max PV Open Circuit Voltage 150V 138V Max PV Input Power 780W 1040W PV Charging Current 30A 20A Equalization Voltage 29 2V 58 4V Boost Voltage 28 8V 57 6V Utility Input Solar Charging Others M...

Страница 18: ...17 NOTES...

Страница 19: ...18 NOTES...

Страница 20: ...Help Line South Africa 0861 ELLIES 355437 For branch or agent contact details please refer to website www ellies co za...

Отзывы: