background image

3-7

3-3.2  JOG MODE

In Jog Mode, you can control the direction and speed of both the horizontal and vertical axis 

at the same time. When issued, the Left, Right, Up and Down bits of the command buffer 

control which axis is going to move. You can set both a horizontal and vertical Jog bit at the 

same time to do diagonal moves. Jog mode is best used when manual control is needed to 

operate the monitor, for example using a joystick that is connected to the PLC. Any previous 

Jog command will be canceled by entering a new command, either Goto or Jog. This means 

that if you command the monitor to move right at 15.0 degrees per second, and you want 

to slow down the move, you would just issue a new Jog command with the updated speed, 

and the previous move would be automatically canceled and the new move programmed. 

Since we do not stop the motors in between moves, you can use a proportional joystick to 

operate the cannon seamlessly in Jog mode. A Jog command will execute until the following 

happens:

1. A Jog Stop command is issued ( This is a Jog command with none of the jog bits set to a one )
2. A User or Hard limit is reached.
3. Another command is issued to override the previous command

There is a command status buffer that indicates the status of the last executed command. If 

the Command in Process bit is still set, the last command is still in effect, and commanded 

axis is still moving at the last commanded speed. If the Command Complete has occurred, 

it means that one of the previous three conditions has occurred. If the reason that the Jog 

command ended was due to hitting a limit, a Command Error bit is also set. All status bits are 

cleared upon executing a new command.

3-3.3  GOTO MODE

In Goto Mode, you can program a move from the current location to a programmed point in 

the horizontal / vertical axis. For example, if cannon was at the home location, 0 horizontal 

and 0 vertical, and needs to be moved diagonally up and to the right by 45 degrees each, Goto 

command would have to be executed with 450 programmed into the vertical desired position 

and 450 programmed into the horizontal desired position. The Goto speed would then have 

to be programmed to tell the cannon how fast to make the move. The actual distance from 

these two points would be around 63 degrees total, so if we program up 210 ( 21.0 degrees per 

second ) into the Goto speed register, the move would take around 3 seconds to complete. 

To program up a series of moves, you would issue your first Goto command and wait for the 

command complete bit to be set, at which point you would execute your next move. Goto 

commands can also be overridden by a new command.

3-4  CANNON ETHERNET INTERFACE (GATEWAY)

The HydroBlast cannon is typically controlled by a PLC which is programmed by writing 

registers through the PLC Ethernet interface, which are translated by the gateway to CAN 

commands to the cannon. These commands are designed to allow easy programming of 

moves, along with current status of the cannons operation. This following section will explain 

the register interface and give specific technical details for operating the cannon from an Allen 

Bradley ControlLogix PLC. Other PLC controllers may require different gateway commands to 

operate the monitor.

Содержание HydroBlast 7100MG EXM2

Страница 1: ...98613000 REV Rel HydroBlast 7100MG EXM2 Water Cannon Installation Operating Maintenance Instructions 1 574 295 8330 www elkhartbrass com...

Страница 2: ...LS REQUIRED 2 1 2 3 INSTALLATION OVERVIEW 2 2 2 4 INSTALLATION STEP 1 MOUNT MONITOR 2 2 2 5 INSTALLATION STEP 2 MOUNT GATEWAY 2 2 2 6 INSTALLATION STEP 3 WIRE SYSTEM COMPONENTS 2 3 2 7 INSTALLATION ST...

Страница 3: ...e nozzle 1 3 Figure 1 4 HydroBlast CAN to Ethernet IP gateway 1 4 Figure 1 5 Protective Cage 1 4 Figure 2 1 Gateway Enclosure Dimensions 2 2 Figure 2 2 Gateway Enclosure Connections 2 3 Figure 3 2 1 C...

Страница 4: ...shdown system and may not have the opportunity to visit the sites where the product is installed or intended to be installed It is the responsibility of the professional installer described above to p...

Страница 5: ...PA National Fire Protection Association A Ampere V Volts AC Alternating Current VAC Volts AC AWG American Wire Gauge VDC Volts DC cm Centimeters DC Direct Current ft Feet GPM Gallons Per Minute LPM Li...

Страница 6: ...ould be operated from a remote location Do not needlessly expose personnel to dangerous fire conditions Open water valves supplying this equipment slowly so that piping fills slowly thus preventing po...

Страница 7: ...SCRIPTION The HydroBlast washdown system is an automatic remote controllable industrial washdown monitor cannon system which performs wash operations with high flow pressurized water based on customer...

Страница 8: ...can be controlled by hardwired input devices via CAN bus The monitor may be powered with 12 24VDC High power permanent magnet variable speed DC gear motors that drive the horizontal and vertical motio...

Страница 9: ...ion The CCM also provides electrical power connection points for input power to the motors Electronics in the CCM enclosure are fully potted with epoxy to prevent dust and water contact 1 6 NOZZLE The...

Страница 10: ...ctLogix SLC5 05 MicroLogix and other PLC controls HMI and other devices supporting Ethernet IP CIP ModbusTCP messaging and connections Figure 1 4 shows the HydroBlast CAN to Ethernet IP gateway Figure...

Страница 11: ...cessary materials and tools 2 2 1 STANDARD SYSTEM CONTENT Monitor with onboard control module motor and harnesses Nozzle Gateway 2 2 2 ADDITIONAL ITEMS The additional items below are available separat...

Страница 12: ...e onto 2 5 NPT monitor outlet thread and tighten 2 5 INSTALLATION STEP 2 MOUNT GATEWAY If Gateway enclosure will be use follow the steps below to install the gateway enclosure Mark and pre drill holes...

Страница 13: ...ready for Normal Operation The HydroBlast cannon is typically pre calibrated from the factory and will default the user programmable limits to the maximum safe operation of the cannon only limited by...

Страница 14: ...S NO Has stow position been set YES NO Has programming stop limits been set YES NO Are LED indication lights on Cannon onboard control all green YES NO Is correct power cable being used YES NO Is the...

Страница 15: ...unts Top Mechanical Limit 135 45 Pointing Up Figure 3 2 1 Cannon Horizontal Coordinate System Figure 3 2 2 Cannon Vertical Coordinate System The cannon position status is reported in tenths of a degre...

Страница 16: ...ibility that when the cannon is commanded to go to the 45 degree mark it will travel into the lower vertical mechanical stop at around the 48 degree mark If this occurs reset the monitor to its calibr...

Страница 17: ...urred If the reason that the Jog command ended was due to hitting a limit a Command Error bit is also set All status bits are cleared upon executing a new command 3 3 3 GOTO MODE In Goto Mode you can...

Страница 18: ...and is shown here below This buffer is designed to be sent to the gateway where it will be converted into an 8 byte CAN message and sent to the cannon Note that PLC Big Endian 16 bit integers are tran...

Страница 19: ...uration whenever you set a jog bit to true then the cannon will start to move at the programmed speed If you modify the horizontal speed field then the move will change speed dynamically This mode is...

Страница 20: ...r vertical axis the Command in Process bit will be set In the case where the command would result in no movement for example setting all the Jog bits to zero the Command in Process will be cleared and...

Страница 21: ...al move the appropriate distance and speed is calculated to make the horizontal and vertical portions of the moves to complete at the same time Hitting a user or hard limit will stop the movement for...

Страница 22: ...s set to 0xb3ff and the source element field points to the aboveTorque Limit Command Buffer The following is a list ofTorque Limit Commands that can be executed TorqueLimit Command Operational Descrip...

Страница 23: ...the desired speed of 0 5 degrees second is meet Now repeat these same jog commands but with the maximum speed 15 degrees second programmed into the Jog commands Slowly increase the PWM slope from 0 i...

Страница 24: ...LED Indication State Interpretation Power LED ON Cannon is powered Horizontal LED ON Cannon received command from remote control or joystick control to move left or right Vertical LED ON Cannon recei...

Страница 25: ...ing nozzle flow test inspect monitor swivel joints for leaks Inspect all exposed wiring for signs of damage If protective cage is used use the appropriate tool to clean the cage of dust build up Note...

Страница 26: ...low provides descriptions and part numbers available for the HydroBlast wash system Part Number Description 00007100MG HydroBlast Wash System including brass monitor with DN80 flange onboard control b...

Страница 27: ...current 5A Stall current 10A Current trip point 8A Material Silicon Bronze Flange DN80 Table E per AS2129 2 5 inlet ID Seals Industrial grade bearing seals Weight 63 LBS Operating temperature range 4...

Страница 28: ...5 2 5 5 NOTES...

Страница 29: ...5 3...

Страница 30: ...5 4...

Страница 31: ...5 5...

Страница 32: ...khart Brass Manufacturing Co Inc 1302 W Beardsley Avenue Elkhart IN 46514 Tel 574 295 8330 Toll Free 800 346 0250 Fax 574 293 9914 www elkhartbrass com Email eb info safefleet net 98613000 REV Rel 11...

Отзывы: