background image

Page 6

LZSTL8WS_2D

1000002481  (Rev. C - 11/15)

Service

For proper and safe servicing, please read these instructions completely.

         

DANGER

         •        All Service and Maintenance must be performed by an authorized service personnel. 

         •        Disconnect electrical supply to the unit before any service work to reduce risk of electrocution. 

         •        Shut off water supply serving the unit before any service work to reduce risk of water damage.

         

CAUTION

         •        Tools/Items required but not provided, for Servicing:

                         o      Safety Glasses

                         o      Protective gloves

                         o      5/16” (8mm) Hex Socket or Flathead Screwdriver

                         o      5/32” (4mm) Hex Key

Service: Adjustments

1.     Temperature Control: Factory set for 50ºF ± 5º (10ºC ± 2.8º) water under normal conditions. To adjust water temperature, turn screw on Item

        No. 13 clockwise for colder, counter clockwise for warmer.

2.     Water Stream Height: Stream height is factory set at 35 psig (0.24 MPa). If supply pressure varies greatly from this, adjust screw located on

        the left side below push bar assembly on crossbar. Clockwise adjustment will raise stream and Counterclockwise adjustment will lower

        stream. For best adjustment, stream should hit basin approximately 6-1/2” (165mm) from bubbler on the downward slope of the basin.

3.     Water coming out of Bubbler continuously: When this occurs at the end of the compressor cycle, turn the cold control warmer

       (counterclockwise) ¼ turn. 

Service: Inspection/Cleaning

         •        Inspect Cooler twice each year for proper operation and performance.

         •        Inspection of the unit will require disconnecting electrical supply, removal of panels, etc. and reassembly and return to service

                  practices.

1.     

Cleaning

: Warm, soapy water or mild household cleaning products can be used to clean the exterior panels. Extra caution should be used

        to clean the mirror finished stainless steel panels. They can be easily scratched and should only be cleaned with mild soap and water or

        Windex glass cleaner and a clean, soft cloth. Use of harsh chemicals or petroleum based or abrasive cleaners will void the warranty.

2.     Bubbler: Mineral deposits on the orifice can cause water flow to spurt or not regulate. Mineral deposits may be removed from the orifice with

        a small round file not over 1/8” (3 mm) diameter or small diameter wire.

         •        CAUTION   : DO NOT file or cut orifice material. Care must be taken not to damage the orifice(s)

3.     Condenser Fan Motor: Confirm condenser fan turns freely. If the condenser fan does not spin freely, have an authorized service personnel

        replace.

4.     Ventilation: Cabinet louvers and condenser fins should be periodically cleaned with a brush, air hose or vacuum cleaner. Cleaning should be

        done twice each year or more frequently if needed due to environment. Excess dirt or poor ventilation can cause no cold water and

        compressor cycling on the compressor overload protector.

5.     

Water Flow

: Confirm proper water flow. If water flow is slow, inspect filter or inline strainer for restriction. Replace filter cartridge if required.

        Disassemble inline strainer and clean if required.

6.     Lubrication: Motors are lifetime lubricated.

7.     Actuation of Quick Connect Water Fittings: Cooler is provided with lead-free connectors which utilize o-ring water seal. To remove tubing

        from the fitting, relieve water pressure, push in on the gray collar before pulling on the tubing. To insert tubing, push tube straight into fitting

        until it reaches a positive stop, approximately 3/4” (19mm).  See Figure 10. 

Service: Inspection/Replacement

         •        Inspect Cooler twice each year for proper operation and performance.

         •        Inspection of the unit will require disconnecting electrical supply, removal of panels, etc. and reassembly and return to service practices.

1.     Lower Front Panel and Upper Shroud: To access the refrigeration system and plumbing connections, remove four (4) screws from bottom of

        cooler to remove the lower front panel. To remove the upper shroud (Item 6) for access to the pushbars, regulator, solenoid valve or other

        components located in the top of the unit, remove lower panel, disconnect drain, remove four screws from tabs along lower edge of upper

        shroud, unplug two wires and water tube.

2.     Bubbler: To remove the bubbler, first disconnect the electrical supply. The underside of the bubbler can be reached through the access panel

        on the underside of the upper shroud. Remove the access panel by removing the retaining screw. To remove the bubbler, loosen locknut from

        the underside of the bubbler and remove the tubing from the quick connect fitting (see Figure 10). When installing replacement bubbler and

        pedestal, tighten nut only to hold parts snug in position. Do Not Overtighten.  After servicing, replace the lower front panel and four (4) screws.

3.     Switches Behind the Push Bar: The regulator in an EZ cooler is always held fully open by the use of a single regulator nut.  Water is not

        dispensed until the pushbar is depressed to activate a switch which then opens a solenoid valve. When installing the regulator nut, the

        regulator spring must be depressed while turning the nut.  Single bar units will have the same wiring as side push bar units but will not have

        the extra leads attached to sidebars.  To remove sidebars, from the inside compress the flared tabs and pull out carefully. To reinstall side

        pushbars, the front of the pushbar is inserted first. While keeping the switch depressed, snap the rear of the pushbar into position.

4.     Cleaning Strainer: To clean the strainer, unscrew the cap of the solenoid valve. Remove screen and rinse thoroughly with water. Insert screen

        back into solenoid valve and screw cap on.  Make sure the o-ring is placed properly.

Содержание LZSTL8WSL2K

Страница 1: ...in voltage cycle and phase to that specified on nameplate Electrical supply must have Ground Fault Circuit Interrupter GFCI protection A means for disconnecting electrical supply to the unit must be...

Страница 2: ...rap Remove the slip nut and gasket from the waste trap and install them on the cooler waste line making sure that the end of the waste line fits into the waste trap Assemble the slip nut and gasket to...

Страница 3: ...to ensure proper clearance and free fan action 3 Connect plug end of International Power Cord Set sold separately into electrical outlet WARNING Exposed electrically energized components Use extreme c...

Страница 4: ...4 11mm X 19mm OBROUND HOLES 6 15 381mm 2 7 8 73mm 2 51mm 51 9 16 1310mm 28 13 16 732mm 19 483mm 17 7 16 443mm 13 15 16 354mm 24 1 2 622mm 34 5 16 872mm 2 51mm 22 15 16 583mm 19 7 16 494mm 7 178mm 7 1...

Страница 5: ...4 11mm X 19mm OBROUND HOLES 6 15 381mm 2 7 8 73mm 2 51mm 51 9 16 1310mm 28 13 16 732mm 19 483mm 17 7 16 443mm 13 15 16 354mm 24 1 2 622mm 34 5 16 872mm 2 51mm 22 15 16 583mm 19 7 16 494mm 7 178mm 7 17...

Страница 6: ...ventilation can cause no cold water and compressor cycling on the compressor overload protector 5 Water Flow Confirm proper water flow If water flow is slow inspect filter or inline strainer for restr...

Страница 7: ...be back in run mode Continued from below 2 When the display changes to SETTINGS depress the button again The display will change to show RNG SET Range set for IR sensor UNIT TYP Type of unit REFRIG o...

Страница 8: ...ED IN POSITION PUSH IN COLLET TO RELEASE TUBE PUSHING TUBE IN BEFORE PULLING IT OUT HELPS TO RELEASE TUBE A B C Fig 12 DESCRIPTION 1 2 3 ITEM NO PART NO 51300C 98926C 0000000746 Filter Assy 3000 Gal K...

Страница 9: ...15 LZSTL8WS_2D 19 8A 1 2A 12 19 12 19 4 28 19 16 2B 12 3 6 19 18 19 8B 21 1 15 16 13 5 3 6 5 17 20 7 26 31 22 32 23 Stream Height Adjustment Stream Height Adjustment Unit is pictured without bottle f...

Страница 10: ...Side Push Drier Kit Drain Replacement EZTL8 Brkt Tube Ftg Clamp Kit Drain Replacement EZTLD BF Brkt Tube Ftg Clamp Kit Replacement Cap Screen O Ring Kit Solenoid Valve Regulator Assy Kit Flexi Bubble...

Страница 11: ...basin assembly off the cooler frame 2 Disconnect two 2 black wires coming from the shroud assembly Black wire that connects from shroud assembly to solenoid valve Black wire that connects to white wi...

Страница 12: ...n front of the frame tipped up as shown in picture to the right 2 Connect water line to solenoid valve Reference Figure 10 for operation of quick connect fittings 3 Connect two 2 black wires coming fr...

Страница 13: ...piece to wrapper with 2 screws provided 3 Re install wrapper with 4 screws 4 Dispose of unused cover plate Right Hand Wrapper Low Side 1 Remove existing wrapper by removing the 4 screws from bottom 2...

Страница 14: ...ev C 11 15 PLUMBING DIAGRAMS VERSATILE BI LEVEL Barb capped when not used Barb capped when not used Barb capped when not used Barb capped when not used Bottle Filler Drain Bottle Filler Drain Bottle F...

Страница 15: ...Refrig unit L H Non Refrig unit Bubbler Bubbler Evaporator 3 8 Water Inlet Tee 3 8 Water Line from Bottle Filling Unit H Filter Assembly 1 4 Union Solenoid Valve Solenoid Valve PLUMBING DIAGRAMS FOR E...

Отзывы: