Controller MO 36
30
safety contact
profile for gate
OPEN
safety contact
profile for gate
CLOSE
8,2kOhm
8,2kOhm
safety contact
profile for gate
OPEN
safety contact
profile for gate
CLOSE
GND
SLZ
SLA
MO36
Connection plan:
Drawing 22
REMARK!
Several safety contact profiles with 8.2kOhm load resistance can be set-up in serial
connection. The safety category remains the same.
REMARK!
Make sure to check the function of the safety contact profiles by activating each single
one manually. The corresponding LED (SLZ or SLA) has to light red.
REMARK!
Observe the effective direction oft he safety contact profiles. The profiles which react in
direction CLOSE have to be connected to the input terminal SLZ. The profiles which react
in direction OPEN have to be connected to the input terminal SLA.