Code Action
Notes
Er03 Blocks all compressors and fans
Er04
Blocks all compressors and fans:
- at maximum power (Fn22) in Cool
- OFF in Heat
AL04 is loaded for digital fans whenever a fan is
activated/deactivated, except when the deactivation is due to
the alarm itself; for the inverter fan when activated. If delivery
probe error occurs, minimum alarm is always signalled.
Er05
Blocks all compressors and fans:
- at maximum power (Fn22) in Cool
- OFF in Heat
If inlet probe error occurs, management alarm disabled
Er06 Blocks all compressors and fans
If inlet probe error occurs, management alarm disabled
Er07
Blocks all compressors and fans:
- at maximum power (Fn22) in Cool
- OFF in Heat
If outlet probe error occurs, management alarm disabled
Er08 Blocks all compressors and fans
If outlet probe error occurs, management alarm disabled
Er09 Exclude compressor 1
Er10 Exclude compressor 2
Er11 Exclude compressor 3
Er12 Exclude compressor 4
Er13 Exclude continuous compressor
AL14 is loaded on activation of the block digital input
Er14 Exclude fan 1
Er15 Exclude fan 2
Er16 Exclude fan 3
Er17 Exclude fan 4
Er18 Blocks the system
AL16 is loaded on activation of the block digital input