Polarity is defined below:
Value
Type
Description
+
Positive
Active when contact closed
-
Negative
Active when contact open
If multiple outputs are configured to run the same resource, the outputs will be activated in parallel.
4) PWM/OPEN COLLECTOR OUTPUTS AO1 AND AO2
The device has two outputs, configurable as PWM or open collector, which pilot the fans/continuous compressors
(via the CFS modules), if configured as PWM, or another resource via external relay if configured as open collector
(On/Off).
The AO1 output is always present whilst the AO2 output is present on models 4150 and 4180 only.
Parameter Description
M.U.
Min
Max
CF34
Enable analogue output AO1
num
0
1
CF35
Enable analogue output AO2
num
0
1
CF37
Analogue AO1 output phase shift
num
0
90
CF38
Analogue AO2 output phase shift
num
0
90
CF40
Analogue AO1 output pulse length (1 unit=69.4
μ
s)
num
5
40
CF41
Analogue AO2 output pulse length (1 unit=69.4 µs)
num
5
40
CF43
Analogue AO1 output configuration
num
-24*
26*
CF44
Analogue AO2 output configuration
num
-24*
26*
CF51**
Configuration of digital AO1 output
num
-24*
24*
CF52**
Configuration of digital AO2 output
num
-24*
24*
* Values from 16 to 22 are not used.
** Parameters CF51 and CF52 represent the logic assignment of outputs AO01 and AO02 if configured as digital
outputs.