56
Boiler Manual
PART 10. START-UP PROCEDURE
(CONTINUED)
Function 1
Factory Program Mode
MODE
INDIRECT
1
This screen indicates that the control is config-
ured correctly. Do not change this screen.
Function 3
DHW Tank Max Temp
DHW TANK MAX TEMP
180°F
3
Description: The Indirect Water Heater maximum
boiler menu setting. This is the maximum tem-
perature that can be selected for the DHW Set
point in the Boiler Menu.
Factory Default is 180°F (Range: 95°F to 185°F)
Function 6
DHW Post Pump Time
DHW POST PUMP TIME
0 MINUTES
6
Description: The Indirect Pump has the ability to
post purge energy from the boiler to run the
pump after the set point has been achieved.
Please note that running the pump for a time
greater than 5 minutes may cause tank energy
to be released back to the boiler heat exchanger
Factory default of 0 Minutes (Range from 0–10
minutes)
Function 7
Warm Weather Shutoff
WARM WEATHER OFF
68 °F
7
Description: Warm weather shut down will dis-
able the boiler if the programmed outdoor tem-
perature is exceeded when used with an out-
door sensor. Factory Default of 68°F (Range 41°F
to 122°F)
Function 8
Min Outdoor Temp
MIN OUTDOOR TEMP
5 °F
8
Description: Allows the user to set the min. out-
door design temperature for the system Factory.
Default is set to 5°F (Range –49° F to 32°F)
Function 9
Max Supply Temp
MAX SUPPLY TEMP
190 °F
9
Description: Allows the user to set the maxi-
mum design supply temperature based on the
minimum outdoor design temperature. Factory
Default 190°F - Range (77° F to 190° F)
Function10
Max Outdoor Temp
MAX OUTDOOR TEMP
68 °F
10
Description: Allows the user to set the maxi-
mum outside design temperature for the system
design. Factory default 68°F – Range (32°F to
95°F)
Function 11
Min Supply Temp
MIN SUPPLY TEMP
95 °F
11
Description: Allows the user to set the design
supply water temperature based on the maxi-
mum outdoor design temperature. Factory
Default 95°F – Range (32°F to 190°F)
Function 12
Min Boiler Temp
MIN BOILER TEMP
68 °F
12
Description: Allows the user to set the design
minimum heat curve temperature for central
heat. Factory Default 68°F – Range (32°F to
190°F)
Function 13
CH Post Pump Time
CH POST PUMP TIME
0 MINUTES
13
Description: Allows the user to set the boiler
pump post purge time once the thermostat is
satisfied: Factory Default: 0 minutes – Range (0
– 10 minutes).
Содержание EL-110 LP
Страница 48: ...47 Boiler Manual PART 8 FIELD WIRING CONTINUED Fig 8 5 LP 293 J Rev 10 1 09 ...
Страница 49: ...48 Boiler Manual PART 8 FIELD WIRING CONTINUED Fig 8 5 LP 293 J Rev 1 14 10 ...
Страница 83: ...82 LP 172 REV 2 16 06 ...
Страница 84: ...83 LP 172 REV 2 16 06 ...
Страница 85: ...84 MAINTENANCE NOTES ...
Страница 86: ...85 MAINTENANCE NOTES ...
Страница 87: ...86 MAINTENANCE NOTES ...
Страница 88: ... 2003 2010 Heat Transfer Products Inc www HTproducts com LP 293 REV 01 06 10 ...