15
Boiler Manual
PART 5: BOILER PIPING
(CONTINUED)
B. GENERAL PIPING INFORMATION
C. BACKFLOW PREVENTER
Use a backflow preventer specifically designed
for hydronic boiler installations. This valve
should be installed on the cold water fill supply
line per local codes. (See Boiler Piping Details)
D. SYSTEM WATER PIPING METHODS
Expansion tank and make-up water
1. Ensure that the expansion tank size will
handle boiler and system water volume and
temperature. Allow for boiler and its piping:
2. The expansion tank must be located as
shown in Boiler Piping Part 5 or following
recognized design methods. See expansion
tank manufacturer’s instructions for details.
3. Connect the expansion tank to the air
separator only if the air separator is on the
suction side of the circulator. Always install
the system fill connection at the same point
as the expansion tank connection to the
system.
4. Most chilled water systems are piped using a
closed type expansion tank.
Diaphragm (or bladder) expansion tank
1. Always install an automatic air vent on top of
the air separator to remove residual air from
the system.
E. CIRCULATORS
Sizing space heat system piping
1. See Piping Details in this manual Part 5. In all
diagrams, the space heating system is
n
CAUTION
DO NOT install automatic air vents on closed-
type expansion tank systems. Air must remain
in the system and return to the tank to provide
an air cushion. An automatic air vent would
cause air to leave system, resulting in water-
logging the expansion tank.
n
CAUTION
DO NOT use the boiler circulator in any location
other than the ones shown in this manual. The
boiler circulator location is selected to ensure
adequate flow through the Elite Heating Boiler
®
.
Failure to comply to this caution could result in
unreliable performance and nuisance shut
downs from insufficient flow.
CAUTION
Undersized expansion tanks cause system
water to be lost from the relief valve causing
makeup water to be added. Eventual boiler
failure can result due to excessive make-up
water addition. This type of failure is
NOT
covered by warranty.
Elite Heating Boiler
®
EL-80
1.4 Gallons
Elite Heating Boiler
®
EL-110
1.7 Gallons
Elite Heating Boiler
®
EL-150
2.0 Gallons
Elite Heating Boiler
®
EL-220
2.6 Gallons
Elite Heating Boiler
®
EL-299
3.1 Gallons
Elite Heating Boiler
®
EL-399
3.7 Gallons
NOTICE
The Elite Heating Boiler
®
control module uses
temperature sensors to provide both high limit
protection and modulating temperature control.
The control module also provides low water
protection by sensing the water level in the heat
exchanger. Some codes/jurisdictions may
require additional external controls.
CAUTION
All piping methods shown in this manual use
primary/secondary connection to the boiler loop.
This is to avoid the possibility of inadequate flow
through the boiler. For other piping methods,
consult your local Heat Transfer Products
representative or refer to separate Elite Heating
Boiler
®
piping details in this manual (Part 5).
Содержание EL-110 LP
Страница 48: ...47 Boiler Manual PART 8 FIELD WIRING CONTINUED Fig 8 5 LP 293 J Rev 10 1 09 ...
Страница 49: ...48 Boiler Manual PART 8 FIELD WIRING CONTINUED Fig 8 5 LP 293 J Rev 1 14 10 ...
Страница 83: ...82 LP 172 REV 2 16 06 ...
Страница 84: ...83 LP 172 REV 2 16 06 ...
Страница 85: ...84 MAINTENANCE NOTES ...
Страница 86: ...85 MAINTENANCE NOTES ...
Страница 87: ...86 MAINTENANCE NOTES ...
Страница 88: ... 2003 2010 Heat Transfer Products Inc www HTproducts com LP 293 REV 01 06 10 ...