ELT-KLCD EliteSuite Installation Manual
Figure 6 - 4 Zone Input Duplex Mode (1K and 2K4)
Fire Zone Input Wiring
When wiring a zone to be a fire zone input the current programmed
zone options will determine what resistors and configuration is
required, refer to the General Options Section on Page 16 and the
zone configuration diagrams in the Zone Input Wiring Configuration
on Page 3.
Figure 7 - Fire/Smoke Detection Input
When a fire zone is connected to a zone input that is used in
the duplex zone configuration a fire zone fault will NOT BE
shown when the fire zone has a shorted condition as this is
shown as all zones closed. A Fire Loop trouble will be shown
when the zone is tampered.
Fire zones that are installed in duplex mode operation are not
recommended. Fire zones should ALWAYS be connected using
the EOL resistor method (2R) as this provides both open and
short circuit monitoring.