6.5.1 - Slot Adjustments
Analog Output Card Calibration Adjustments
Figure 6.10 Analog Output Card Calibration Page
6.5.1 - Slot Adjustments
Analog Output Card Calibration Adjustments
The current and voltage outputs of analog ouput channels provided with Analog
Output cards can be calibrated on the screen given in Figure 6.10. For each current
and voltage outputs, 2 LOW and 2 HIGH calibration values must be saved.
By selecting the channels to be calibrated from left of the screen (I.OUT 1-4, V.OUT1-4),
and calibration type HIGH or LOW from top of the screen, calibration process is initiated
for selected output type and calibration value.
After this process, the font color of selected channel and calibration type turn burgundy,
the calibration value turns yellow. A Voltmeter (3(-), 4(+)) or ampermeter (1(+), 2(-))
is connected to the outlet of the channel depending on the type of calibration of the
selected channel.
The value of the calibration is set using the up and down keys. For ease of calibration,
up and down keys are given as two pieces of 100 levels and 10 levels. 100 steps for
coarse changes, 10 steps are used for fine adjustments. LOW and HIGH calibration
values of current outputs are 4 mA and 20 mA respectively. LOW and HIGH calibration
values of voltage output is 2 V and 10 V respectively. Calibration values are saved by
pressing corresponding channel button which has been turned to burgundy to initiate
calibration. To cancel the calibration process, press the CANCEL button under
the screen.
The
button resets the calibration values to factory settings.
Load Factory Settings