Initial and Annual Examination
- 79 -
15
Initial and Annual Examination
In this chapter is described how the auditor can check LIMAX33 CP-00 at initial and annual examination.
The existing local accident prevention regulations and additional especially the rules of the EN81 must be ob-
served when carrying out the tests for examination.
15.1
System Restart
Some checks concerning self-diagnostics of LIMAX33 CP-00 are only performed at start-up of the system.
Therefore, it is mandatory to restart the LIMAX33 CP-00 at annual examination. This can either be done by RE-
SET-button, by reset-command given by CAN or by disconnection/reconnection the main power supply.
15.2
Magnetic Tape
Concerning the magnetic tape, the tape guiding and the tape presence sensor the maintenance-hints of the
manual for the magnetic tape should be followed.
15.3
Software Identification
It is possible to read the ROM-CRC of the LIMAX33 CP-00 software by CANopen.
Refer to CANopen specification.
Display the ROM-CRC of LIMAX33 CP-00 software and compare it with the respective CRC
noted in the certificate in order to verify the correctness of the software version.
15.4
Set of Configuration
The configurable parameter/features of LIMAX33 CP-00 are noted on the info-label on the housing or in the
shaft resp. control cabinet (see section
7.1.2). They must fit the conditions of the lift.
The configuration data of the LIMAX33 CP-00 can be read out via CANopen. Refer to CANopen specification
It must fit the data on the info sheet.
Display the configuration information and compare it with the info label.
15.5
Interference Suppression Measures
It must be checked that the interference suppression measures (refer to “constraints for use, topic
15) are
present and still effective.