Calibration of Absolute Measuring Systems
- 20 -
11
Calibration of Absolute Measuring Systems
11.1
Guided FMAX Absolute Linear Encoder
When using an FMAX (
14 „Signal inputs = 4“), a one-time calibration of the measuring system is required.
The calibration is done as follows:
1.
Press the keys
►
+
▲
in the normal mode for 3 seconds at the same time:
appears in the display
2.
Move the FMAX sensor back and forth by approx. 2 cm and press the
►
key:
appears in the display
3.
Now move the FMAX sensor to the desired zero point and press the
►
key:
appears in the display
4.
When the button is released, the system is calibrated and the display shows
REMARK!
In case of replacing the FMAX, a new calibration procedure must be performed.
11.2
Unguided EMAX Absolute Linear Encoder
When using an EMAX (
14 „Signal inputs= 5“), no calibration must be performed.