20
R88 System Register 4
Target value window
X
Incremental
error
comp
0 = not active
1 = active
Output / Input Version
0 = D-Sub connector
1 = Relays output / Ria type input
Double
start
at
Prog
end
0 = without
1 = with
Address
Line
switching
0 = at position reached
1 = at start
Default
selection
0 = Elgo standard (EL)
1 = Customer 1 (DR)
2 = Customer 2 (LD)
3 = Customer 3 (AD)
Option
R90 Service register
Only active when
R98
is unlocked. Select button as shown below:
Button 1
- Pressing this button loads default values into all registers
Button 2
– Clear memory
R92 Display brightness
With the setting of this register, the brightness of the display can be altered digitally:
0.0
= dark,
9.9
= max. brightness
R96 Pulse scaling factor
A factor (0.00001… 9.9999) can be entered in this register. The encoder pulses will be
multiplied by this factor, to manipulate the display to required dimensions. If no multipli-
cation is required, this register must be set to 1.00000.
R97 Inch/ mm - selection
This register sets the metric or inch mode. This setting has priority to the external selec-
tion of the input. Active in Ad default.
Target window
X
Option
0 = mm mode
1 = Inch mode 0,001 inch resolution
R98 Security code
Enter
250565
to unlock and change parameters and registers
R99 Service
(only for service), see page 28