39
USER MANUAL TPS/M/D 62000447 REV 00_
–
31/08/2021
4.7.1.3.
VOLTAGE ALLARM
TPS controls, in addition to the harmonic distortion, the RMS value of the output voltage both in
2WIRE and in 4WIRE configuration.
If the output voltage is not equal to the set value, a special alarm is generated (MAX DV OUTX).
VOLTAGE ALARM does not cause any stop.
4.7.1.4.
INVERTER COMMUNICATION
The alarm appears when there is problem on the communication between the inverter and the
display.
4.7.1.5.
BUS OVERVOLTAGE & UNDERVOLTAGE
TPS can work with network voltage variations of
10%, if these limits are exceeded TPS stops and
show the alarm.
If the network voltage is too low TPS stops and the
UNDERVOLTAGE
alarm is on.
If the network voltage is too high TPS stops and the
OVERVOLTAGE
alarm is on.
If the supply phases have been inverted, both the UNDERVOLTAGE and OVERVOLTAGE alarms
are generated. Check
and invert the phases on the input connector.
4.7.1.6.
OVERTEMPERATURE
The alarm appears in case of high temperature inside of TPS. TPS stops and the
OVERTEMPERTURE
alarm
is active
4.7.1.7.
INVERTER ALARM
In case of bad operations of the overload sections (inverter) TPS stops and the
INVERTER
alarm
is
active
Содержание TPS/M/D
Страница 1: ...1 USER MANUAL TPS M 62000595 REV 03_ 01 06 2021 TPS M D USER MANUAL ...
Страница 13: ...13 USER MANUAL TPS M 62000595 REV 03_ 01 06 2021 1 4 3 TPS M D 6KVA 281 513 ...
Страница 14: ...14 USER MANUAL TPS M 62000595 REV 03_ 01 06 2021 1 4 4 TPS M D 9KVA 281 513 ...
Страница 25: ...25 USER MANUAL TPS M D 62000447 REV 00_ 31 08 2021 2 3 2 4 WIRE CONFIGURATION TPS M D TPS M D ...
Страница 36: ...36 USER MANUAL TPS M D 62000447 REV 00_ 31 08 2021 Limitations is enable both AC and DC mode ...