02/02/22
User Manual CPS/M 62000584_05
22
In case of loads that absorb a current superior than the nominal one, CPS/M works a limitation of
the same current.
This limitation is visualized by means of the led
LIMIT OUT 1
at the voice
CURRENT
.
In case of a limitation of current the output sinusoidal wave is no more guaranteed and so it will
show an harmonic distortion.
Not linear loads with an overload minor than the nominal one but with a very high crest factor
current make the current defence intervene.
Notice that if someone is working by limitation current, CPS/M keeps the effective value of the
output voltage equal to the set off value until the led concerning the voltage alarm switches on
(see at VOLTAGE ALARM).
This kind of alarm does not cause any block to CPS/M.
2.8.4
Voltage alarm
CPS/M more than the output distortion control woks a control of the effective value of the output
voltage either in the configuration 2 wires or in the configuration 4 wires.
If the output voltage is not equal to the set off one a signal of error is visualized by means of the
led
MAX OUT 1
at the voice VOLTAGE.
This kind of alarm does not cause any block to CPS/M.
Содержание 99112103
Страница 15: ...02 02 22 User Manual CPS M 62000584_05 15 1 4 2 CPS M 10KVA 483 270 6U 537 507 84TE MAX 540mm 510mm ...
Страница 29: ...02 02 22 User Manual CPS M 62000584_05 29 3 4 WIRING DIAGRAM 3 4 1 2 WIRE CONFIGURATION ...
Страница 30: ...02 02 22 User Manual CPS M 62000584_05 30 3 4 2 4 WIRE CONFIGURATION ...
Страница 50: ...02 02 22 User Manual CPS M 62000584_05 15 2 2 2 CPS M 10KVA 483 270 6U 537 507 84TE MAX 540mm 510mm ...
Страница 63: ...02 02 22 User Manual CPS M 62000584_05 28 4 5 SCHEMI DI CABLAGGIO 4 5 1 CONFIGURAZIONE 2 WIRE ...
Страница 64: ...02 02 22 User Manual CPS M 62000584_05 29 4 5 2 CONFIGURAZIONE 4 WIRE ...