Installation Instructions
5
Step 5
Perform the following tests: Insulation resistance test, a heating cable resistance
test and a floor sensor resistance test. (see page 7) record your findings in the test &
commission form enclosed in the box.
Step 8
With the eRibbon laid and secure the finished floor surface can now be laid. When
using the Duralay Heatflow underlay install directly above the eRibbon
Step 7
Position the floor sensor thermostat probe directly below the electrical connection
point.
The floor sensing probe should be installed in-between two heating ribbons and
secured with the single sided adhesive tape (the floor sensor is used to measure the
maximum temperature beneath the floor).
Step 6
Unfold the eRibbon with the fibreglass net facing up, lay the eRibbons onto the
eFoam insulation. Using the doublesided adhesive tape clearly fixed to the eFoam
ensures the eRibbon is installed with no raised folds. Each pair of cold tails should be
connected to a low level connection point.
Note
After the finished floor covering has been laid perform the following tests:
• Insulation resistance test
• Heating cable resistance test
• Floor sensor resistance test
Record your findings in the test & commission form enclosed in the box.
Register your warranty online at: www.electricunderfloorheating.co.uk/warranty
Note
Do not over lap the eRibbon mats