15
Relay plug-in board for SHT 5000
Relay plug-in board, only for SHT 5000, item No. 300747
• additional 4 relays for control signals
• each sensor input has its own potential-free relay permanently assigned
• Changeover relay normally open 5 A / normally closed 3 A / 230V AC
• Functional range -15 ° C ... + 40 ° C
• Dimensions length 60 mm, width 29 mm, height 16 mm
In contrast to the main relay, the relays on the relay plug-in board are not
activated in monitoring mode. The board is simply plugged onto the electronics
of the SHT 5000.
L
L
N
N
PE
PE
S
G
Ö
Relay plug-in card
connection
Operating voltage
230 V AC
50-60 Hz
Sensor 1
Float switch
Sensor 2
Float switch
Sensor 3
Float switch
Sensor 4
Float switch
L
N PE
Relay
8A/230V
Option:
9V battery
INSTALLATION INSTRUCTION
The relay plug-in card is plugged into the electronic circuits of the SHT 5000
water detector. For this, the housing of the SHT 5000 water detector must be
opened.
Place the relay plug-in board onto the 6-pin jack provided. Use the spacer slee
-
ves supplied to secure the board.
Warning: Before opening the device, first disconnect
it from any power source (network power, etc.) and
ensure that it cannot be restarted again!
Relay connection configuration
When connecting additional devices to the potential-free relay, please note
that the switching capacity may not be exceeded.
►
Relay status in monitoring mode: The relay is „energized“ (make contact
closed / break contact open)
►
Relay status in alarm mode: The relay „decreases“ (make contact open /
break contact closed)