Parameter description
16
26 Time setting
27 Sensor calibration
08:10
Inhibition heat
generator
Setting range:
OFF (----) ... 24h
Function:
After burner block is active, the heat generator is also blocked for
the duration of the set time
08:15
Reset counter
Setting range:
0 = no reset
1 = Reset counter
Factory setting: 0
Function:
When value is changed to 1 and confirmed, all counters (heat
balance, operating hours and starts) are reset.
Display
Designation
Description
26:01
Time
Setting range:
00:00 ... 23:59
Factory setting: Current time
Function:
Setting of current time.
26:02
Weekday
Setting range:
1 ... 7
Factory setting: Current weekday
Function:
Setting of current weekday.
Display
Designation
Description
27:01
Calibration F1
Setting range:
-5K ... +5K
Factory setting: 0K
Function:
Correction of measured sensor value at input of heat storage
tank F1
27:02
Calibration F2
See 27:01 on input flow sensor heating circuit
27:03
Calibration F3
See 27:01 on input heat supplier Delta-T
27:04
Calibration F4
See 27:01 on input outside sensor
Display
Designation
Description