Parameter description

10

06 Parameter heating circuit

03:04

Building type

Setting range:

1: Light construction (mean value over 6  X3
   hours)
2: Medium construction 
    (mean value over 24 hours)
3: Heavy construction 
    (mean value over 72 hours)

Factory setting:

2

Function:
This parameter considers the building type by adapting the 
calculation of the outside temperature mean value according to 
its setting.

03:05

Climate zone

Setting range:

-50°C … 0°C

X3

Factory setting:

-12?

Function:
The climate zone is the coldest outside temperature value to be 
expected.

03:06

Automatic exit time

Setting range:

0,5 ... 10 Min

X3

Factory setting:

2 min

Function:
When unit is not operated during the set time, the display 
returns to basic display.

03:07

Anti-blocking 
protection

Setting range:

0 = OFF

X3

1 = ON

Factory setting:

OFF

Function:
With this function activated, pump is switched on daily for ca. 20 
seconds as protection against blocking during extended switch-
off phases (> 24h).

03:09

Code heating 
specialist

Setting range:

0 … 999

Factory setting:

0

Function when setting is greater than 0:
Hide parameters marked with X3.

03:10

Total reset

Reset to factory settings

Display

Designation

Description

06:01

Function

Setting range:

0=OFF
1=Unmixed circuit
2=Mixed circuit

Factory setting:

2

Display

Designation

Description

BA_CETA106_EbV_EN_0450021003_0950-10.book  Seite 10  Freitag, 11. Dezember 2009  1:16 13

Содержание CETA 106

Страница 1: ...Operating manual 106 Heating circuit controller with differential temperature Version 0950 10 Art 0450021003 BA_CETA106_EbV_EN_0450021003_0950 10 book Seite 1 Freitag 11 Dezember 2009 1 16 13 ...

Страница 2: ...istance values 20 Declaration of conformity 21 Technical Data 22 Liability 22 Disposal 22 Elektronikbau und Vertriebs GmbH Heisterner Weg 8 12 D 57299 Burbach This document may not be reproduced nor disclosed to third parties particularly competitors in original or copy form without our prior explicit consent The document is subject to our proprietary rights and copyrights BA_CETA106_EbV_EN_045002...

Страница 3: ...evertheless using the device can cause danger to the user or third persons or damage to the unit and other assets The unit must be used exclusively as heating circuit controller or differential temperature controller Safety All electrical connections safety measures and protections have to be carried out by an authorised professional electrician according to the valid standards and VDE guidelines ...

Страница 4: ... parameter Change menu item Esc Exit setting Keep old value Select next higher menu level Esc Long Return to basic display 2 Version display when starting c 106 Type designation Ceta 106 1 5 Version display due to update it can differ from example shown BA_CETA106_EbV_EN_0450021003_0950 10 book Seite 2 Freitag 11 Dezember 2009 1 16 13 ...

Страница 5: ...ircuit Automatic mode heating circuit after timer program I or II Heating mode heating circuit Operating mode AUTOMATIC or HEATING Reduced mode heating circuit Operating mode AUTOMATIC or RED HEATING Standby heating circuit Summer switch off heating circuit Frost protection heating circuit BA_CETA106_EbV_EN_0450021003_0950 10 book Seite 3 Freitag 11 Dezember 2009 1 16 13 ...

Страница 6: ... allows manual start up of the heating circuit or measurement of emission without automatic functions Manual operation has no influence on an activated Delta T control The heating circuit pump runs continuously The mixing valve is de energised Caution This function shall only be used by an authorised professional Heating circuit temperatures are not monitored during measurement of emission Faulty ...

Страница 7: ...c Value1 Prog Value 2 Value n Set parameter value Prog Return without saving Return and save Esc Basic display Prog Esc 01 Info 02 Prog Time programs 27 Sensor adj 28 Relay test Prog Select menu level Select menu level Esc HEZBEGINN Prog HEIZENDE Set parameter value Prog Return without saving Return and save Prog Menu structure time programs BA_CETA106_EbV_EN_0450021003_0950 10 book Seite 5 Freita...

Страница 8: ... Oper mode 06 05 Time program 06 11 Extended pump running time 06 13 Room factor 06 14 Room thermostat function 06 15 Room frost protection limit 06 18 Minimum temperature limit 08 Prog T 08 01 Delta T oper mode 08 02 Switch on differential 08 03 Switch off differential 08 04 Minimum runtime of pump 08 05 Min temp heat supplier 26 Time setting 26 01 Time 26 02 Weekday 27 Sensor adj 27 01 Calibrati...

Страница 9: ...ng curve conductance 06 08 Heating system exponent 06 20 Heat generator parallel shift 06 19 Maximum temperature limit 06 09 System frost protection 06 10 Summer switch off 06 24 Actuator running time 08 06 Max temp heat supplier 08 07 Fin switch off temp heat supplier 08 08 Max temp heat supplier 08 09 Burner block heat generator 08 10 Inhibition heat supplier X4 3 X X3 X3 X3 3 X 3 X 3 X 3 X 3 X ...

Страница 10: ...ng valve in idle position 1 Actuator runs open 2 Actuator runs closed 06 03 Flow heating circuit actual Actual temperature on flow sensor of heating circuit F2 06 04 Flow heating circuit setpoint Flow setpoint temperature for heating circuit 06 05 Room actual Actual temperature in room X4 06 06 Room setpoint Room setpoint temperature for heating circuit 08 03 Display T pump 0 Pump is switched off ...

Страница 11: ...12 00 6 I 06 00 22 00 6 II 12 00 12 00 7 I 06 00 22 00 7 II 12 00 12 00 Display Designation Description 03 01 Code entry Setting range 0 999 Factory setting 0 Function Show parameters marked with X3 03 02 Automatic set function 0 OFF no automatic sensor detection X3 1 ON automatic sensor detection 03 03 Bus address Setting range 31 35 X3 Factory setting 31 Function If more than one CETA 106 has to...

Страница 12: ... 0 5 10 Min X3 Factory setting 2 min Function When unit is not operated during the set time the display returns to basic display 03 07 Anti blocking protection Setting range 0 OFF X3 1 ON Factory setting OFF Function With this function activated pump is switched on daily for ca 20 seconds as protection against blocking during extended switch off phases 24h 03 09 Code heating specialist Setting ran...

Страница 13: ...5 Heating Heating circuit operates continuously according to set room day temp 06 02 Red heating Heating circuit operates continuously according to set room night temp 06 03 under consideration of 06 06 Standby Frost protected switch off of heating circuit 06 05 Time program Setting range 1 Time program 1 2 Time program 2 3 Time program 1 and 2 Factory setting 1 Function Depending on the setting t...

Страница 14: ...ange 1 00 10 00 X3 Factory setting 1 10 Function Curvature of heating circuit s heating curve Recommendation 1 10 Underfloor heating or other panel heating systems 1 30 Radiator heating 2 00 Convector and baseboard heating 3 00 General ventilator applications with high start temperatures Display Designation Description BA_CETA106_EbV_EN_0450021003_0950 10 book Seite 12 Freitag 11 Dezember 2009 1 1...

Страница 15: ...p after heating circuit is switched off by time programs 06 13 Room factor Setting range 0 500 X3 X4 Factory setting 100 Function This function determines to what extent a deviation of the room temperature from the setpoint affects the control of boiler flow temperature Corrected room setpoint set room setpoint deviation x room factor 100 06 14 Room thermostat function Setting range Off X3 X4 0 5 ...

Страница 16: ...tting to adjust the control characteristic of the mixing valve to the running time of the actuator in increments of 0 1 minutes 6 seconds Display Designation Description 08 01 Control mode Setting range 0 Delta T OFF 1 Delta T ON Factory setting 1 Function The differential control can be switched on or off via the setting 08 02 Switch on difference Setting range Switch off difference 3K 30K Factor...

Страница 17: ... switch off temperature Heat supplier Setting range OFF 70 210 C Factory setting OFF Function Irrespective of switching differentials the pump performs a forced switch off after the sensor of heat supplier F3 has exceeded the set value 08 08 Maximum temperature heat storage tank Setting range OFF 50 110 C Factory setting 75 C Function Irrespective of switching differentials the pump performs a for...

Страница 18: ... Setting range 00 00 23 59 Factory setting Current time Function Setting of current time 26 02 Weekday Setting range 1 7 Factory setting Current weekday Function Setting of current weekday Display Designation Description 27 01 Calibration F1 Setting range 5K 5K Factory setting 0K Function Correction of measured sensor value at input of heat storage tank F1 27 02 Calibration F2 See 27 01 on input f...

Страница 19: ...ut open 28 03 Test output 3 mixing valve closed See 28 01 for mixing valve output closed 28 04 Test output 4 charge pump Delta T See 28 01 on input charge pump Delta T Hazard Mounting must be performed by an authorised professional electrician Ensure that unit is de energised before opening it 1 Remove terminal area cover from casing 2 For mounting first put a screw into the wall 3 Hang controller...

Страница 20: ... mixed heating circuit MKB 2 L1 230V Mixing valve OPEN 3 L1 230V Mixing valve CLOSED N Neutral 230V mains mixing valve pumps Connection solar charging pump SOP isolated option Earthing Bus connections for networking see parameter 03 03 Connections without function RC Connection CETA RC option F1 Sensor heat storage tank Delta T KVT20 option F2 Sensor flow heating circuit VF202B F3 Sensor heat supp...

Страница 21: ...sensor F2 See 11 0 12 1 Short circuit sensor F2 See 11 1 13 0 Interruption sensor F3 See 11 0 13 1 Short circuit sensor F3 See 11 1 14 0 Interruption sensor F4 See 11 0 14 1 Short circuit sensor F4 See 11 1 72 6 Data bus CETA RC no signal terminal RC Repair malfunction on data bus to room device CETA RC 73 2 Device bus address collision Terminal AB Set controls of the same type to different bus ad...

Страница 22: ...0 250 1 155 1 194 1 232 1 271 1 309 1 347 1 385 1 423 1 461 1 498 1 536 1 573 1 611 1 648 1 685 1 722 1 758 1 795 1 832 1 868 1 905 1 941 10 12 14 16 18 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 1 783 1 812 1 840 1 869 1 898 1 928 2 002 2 078 2 155 2 234 2 314 2 395 2 478 2 563 2 648 2 735 2 824 2 914 3 005 3 098 3 192 3 287 BA_CETA106_EbV_EN_0450021003_0950 10 book Seite 20 Freitag 11 D...

Страница 23: ...ven by complete adherence to the following standards EMV Requirements for household appliances electric tools and similar devices DIN EN 55014 1 2003 Part1 Transient emission DIN EN 55014 2 2002 Part 2 Immunity EMV Limit values DIN EN 61000 3 2 2002 Part 3 2 Limit values for harmonic current emissions DIN EN 61000 3 3 2002 Part 3 3 Limitation of voltage fluctuations and flicker Automatic electrica...

Страница 24: ...ith applicable statutory regulations of the corresponding country Mains voltage 230V 6 10 Rated frequency 50 60Hz Power input max 2 1VA Fuse 6 3A Output relay contact load 2 2 A Ambient temperature 10 50 C Storage temperature 25 80 C Degree of protection IP 30 Protection class according to EN 60730 II CE compliance 89 336 EEC Casing dimensions 145 5 x 161 x 48 mm W x H x D Casing material ABS V0 W...

Отзывы: