15
Parameter description
08:04
Minimum running
time of pump
Setting range:
OFF (----)
0.5 ... 60 min
Factory setting:
3 min
Function:
Minimum switch-on time of pump per start.
08:05
Minimum
temperature heat
supplier
Setting range:
OFF (----)
5 ... 80 °C
Factory setting:
OFF
Function:
Irrespective of switching differentials, pump turns on only after
the sensor of heat supplier F3 has exceeded the set value.
08:06
Maximum
temperature heat
supplier
Setting range:
OFF (----)
30 ... 110 °C
Factory setting:
90 °C
Function:
Irrespective of switching differentials, the pump performs a
forced switch-on after the sensor of heat supplier F3 has
exceeded the set value.
08:07
Final switch-off
temperature
Heat supplier
Setting range:
OFF (----)
70 ... 210 °C
Factory setting:
OFF
Function:
Irrespective of switching differentials, the pump performs a
forced switch-off after the sensor of heat supplier F3 has
exceeded the set value.
08:08
Maximum
temperature heat
storage tank
Setting range:
OFF (----)
50 ... 110 °C
Factory setting:
75 °C
Function:
Irrespective of switching differentials, the pump performs a
forced switch-off after the sensor of heat storage tank F1 has
exceeded the set value. This switch-off takes priority over
functions 08:07 and 08:06.
08:09
Burner block
Heat generator
Setting range:
0 ... 2
Factory setting: 1
Function:
0 = OFF
1 = Burner block when pump is active
2 = Burner block only for DHW when pump
is active
Display
Designation
Description